Desa VTD-24NV-JHB Checking GAS Connections, Test Pressures Equal To or Less Than Psig 3.5 kPa

Page 9

Installation

Continued

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak.

Test Pressures Equal To or Less Than

1/2 PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Figure 8).

2. Pressurize supply piping system by either us- ing compressed air or opening main gas valve located on or near gas meter.

3. Check all joints from gas meter to equipment shutoff valve for natural gas or propane/LP supply to equipment shutoff valve for propane/ LP (see Figure 9 or 10). Apply noncorrosive leak detection fluid to all joints. Bubbles form- ing show a leak.

4. Correct all leaks at once.

Apply a noncorrosive leak detec- tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Equipment

Shutoff

Valve

Open

Closed

CAUTION: Make sure ex-

Figure 8 - Equipment Shutoff Valve

ternal regulator has been in- stalled between propane/LP supply and appliance. See guidelines under Connecting to Gas Supply, page 7.

Pressure Testing Gas Supply

Piping System

Test Pressures In Excess Of 1/2 PSIG

(3.5 kPa)

1. Disconnect appliance with its individual equipment shutoff valve from gas supply piping system. Pressure in excess of 1/2 psig

Propane/LP Tank

Equipment

Shutoff Valve

Control Valve

Location

will damage appliance regulator.

2. Cap off open end of gas pipe where equipment shutoff valve was connected.

3. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.

4. Check all joints of gas supply piping system. Apply noncorrosive leak detection fluid to gas joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Reconnect log set and equipment shutoff valve to gas supply. Check reconnected fit- tings for leaks.

Figure 9 - Checking Gas Joints

(Propane/LP Gas Only)

Equipment

Shutoff Valve

Gas Meter

Control Valve

Location

Figure 10 - Checking Gas Joints

(Natural Gas Only)

114370-02Cwww.desatech.com

Image 9
Contents Ansi Z21.60-2003 CSA What to do if YOU Smell GASSafety Information Table of ContentsSafety Information Switch AssemblyProduct Identification Log SetOptional Accessories Product FeaturesInstallation Local CodesFlue Opening Specifications Installation and ClearancesVenting Specifications for Installation Installing Damper ClampConnecting to GAS Supply Installing Appliance AssemblyInstallation Items Needed Flexible Gas Hose If Allowed by Local Codes Control ValveNatural Gas Test Pressures Equal To or Less Than Psig 3.5 kPa Checking GAS ConnectionsPressure Testing Appliance Gas Connections For Your Safety Read Before LightingOperating Appliance Lighting InstructionsTo Turn OFF GAS To Appliance Manual Lighting ProcedureControl Knob Ignitor Shutting Off ApplianceFor purpose of input adjustment Cleaning Maintenance SpecificationsInspecting Burners Burner Flame PatternObserved Problem Possible Cause Remedy TroubleshootingControl Delayed ignition of burner Manifold pressure is too Causing pilot flame to go Out. This problem could beHas been triggered Ignition operationWhite powder residue forming When heated, vapors from Noise when burners are lit Position when burners areTurn control knob to LO Cold Minute Air in gas line Operate burners until air isStatement at top Gas leak. See WarningTechnical Service Service HintsReplacement Parts AccessoriesModels VTD-18NV-JHB, VTD-24NV-JHB, VTD-30Nv-JHB Illustrated Parts BreakdownParts on page 17 of this manual Parts ListWarranty Information Keep this WarrantyLimited Warranty Vented GAS Logs