Desa (V)T36EPA installation manual Test Pressures Equal To or Less Than Psig 3.5 kPa

Page 22

Fireplace

Installation

Continued

Pressure Testing Gas Supply

Piping System

Test Pressures In Excess Of 1/2 PSIG

(3.5 kPa)

1. Disconnect fireplace and its individual equip- ment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator.

2. Cap off open end of gas pipe where equipment shutoff valve was connected.

3. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace, or using compressed air.

4. Check all joints of gas supply piping system. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5. Reconnect fireplace and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than

1/2 PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Figure 33).

2. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace, or using compressed air.

3. Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 34 or 35). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Equipment

Open

Shutoff Valve

 

Closed

Figure 33 - Equipment Shutoff Valve

 

Equipment

Propane/LP

Shutoff Valve

Supply Tank

 

 

Gas Valve

Figure 34 - Checking Gas Joints for

Propane/LP Gas Fireplace

Equipment Shutoff Valve

Gas

Meter

Gas Valve

Figure 35 - Checking Gas Joints for

Natural Gas Fireplace

Pressure Testing Fireplace Gas

Connections

1. Open equipment shutoff valve (see Figure 33).

2. Open main gas valve located on or near gas meter for natural gas or open supply tank valve for propane/LP gas.

3. Make sure control knob of fireplace is in the OFF position.

4. Check all joints from equipment shutoff valve to thermostat gas valve (see Figure 34 or 35). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5. Light fireplace (see Operating Fireplace, page

28). Check all other internal joints for leaks.

6. Turn off fireplace (see To Turn Off Gas to Appliance, page 29).

22

www.desatech.com

111251-01E

Image 22
Contents What to do if YOU Smell GAS Table of Contents Safety InformationSafety Information Product Identification Product FeaturesLocal Codes High traffic areasLocation and space requirements Pre-Installation PreparationProper clearances must be maintained Front Top of Standoffs Vent See venting ClearancesFraming and finishing Venting clearancesLocation of Termination Cap Balcony with Perpendicular Side WallVenting Installation Instructions Installation PrecautionsInstallation Planning Installing Horizontal Vent Cap Noncombustible Exterior Ground Floor Installation 32 minSnorkel Termination Installation Recommended Applications Corner ground floor installationHorizontal System Installation Using TWO 90 Elbows Flat Ceiling Installation Installation for vertical terminationConnect a section of pipe and extend up through the hole Twist-lock the vent cap onto the last section of vent pipe High Altitude Installation Vertical VentingDesa Terminations Desa Venting AccessoriesDesa Elbows Number DescriptionModel BK Installation Fireplace InstallationInstalling optional blower accessories Check GAS TypeModel BKT Installation Plug in blower power cord to duplex outletBlower Wiring Diagram Installing Gas Piping to Fireplace LocationInstallation Items Needed Connecting Fireplace to GAS Supply Checking GAS ConnectionsPressure Testing Fireplace Gas Connections Test Pressures Equal To or Less Than Psig 3.5 kPaRemoving Louver Panels Cleaning Glass DoorRemoving/Replacing Glass Door Removing Glass DoorInstalling logs, lava rock and glowing embers Close top and bottom louversInstalling Log No Wall Switch Installation Optional Remote control Installation model WRCOpen lower louver panel of firebox Pilot Gas Wiring DiagramLine Operating Fireplace For your safety Read before lightingLighting Instructions Optional Remote Operation Inspecting BurnersTo Turn OFF GAS To Appliance Burner Flame PatternPilot and burners Cleaning MaintenanceGlass Door LogsObserved Problem Possible Cause Remedy Cleaning and MaintenanceTroubleshooting Venting systemGas leak. See Warning Clean out air holes at burner Tery power is low RemoteImproper log placement Glass soots Flame impingement on logsIllustrated Parts Breakdown Parts List Illustrated Parts Breakdown KEY Description Technical Service Replacement PartsService Hints SpecificationsAccessories Keep this Warranty Warranty InformationLimited Warranty DIRECT-VENT Fireplace