Desa CD36M-A2, CD32M-2, CD36M-A1, CD42M-A2, CD32M-1 Vertical Termination with Offset and Wall Strap

Page 8

 

INSTALLATION

Direct-Vent Pipe

 

 

 

 

 

 

 

 

 

Continued

CD32M and

 

 

Siding Standoff

 

 

 

 

 

 

CD36M-A

 

 

6.

For vertical installation, a vertical termination is

 

 

(Optional)

4 1/4" Inner and

 

 

available. Also for vertical venting application,

7 1/4" Outer

 

 

Minimum Pipe

 

install vertical flue restrictor into inner collar of

CD42M-A

 

 

 

fireplace as shown in Figure 6, page 7.

5" Inner and 8"

Overlap 1 1/4"

 

When installing a length of pipe for vertical

Outer

 

 

 

 

termination that is over 3 ft., support the pipe

 

Wall Firestop

 

 

every 3 ft. using metal wall straps. Vertical to

 

 

 

 

 

 

 

horizontal pipe must be kept at a 1 ft. to 4 ft. ratio

 

 

 

 

 

Deflector

 

with a maximum run of no more than 20 ft.

 

 

 

 

 

Shield

 

 

 

 

 

 

 

 

 

 

 

 

If an offset is necessary in the attic to avoid

 

 

 

 

 

 

 

obstruction, it is important to support the

Maintain 1"

 

 

 

 

vent pipe every 3

ft. to avoid excessive

 

 

 

 

Minimum

 

 

 

 

stress on the elbows and possible separation

 

 

 

 

Air Space

 

 

 

 

(see Figure 8).

 

 

 

 

 

 

Screws

 

 

 

 

 

Around Outer

 

 

Clearances must be maintained between the roof

 

 

Pipe when

 

 

Horizontal

 

and the termination.

Refer to chart below.

 

 

 

Penetrating a

 

 

 

Termination

 

 

 

 

 

 

Wall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Vent Cap)

 

Roof Pitch

Minimum Height

 

 

 

 

 

 

 

 

 

 

 

Exterior Wall

 

 

 

 

 

Above Roof

Framed Openings

 

Flat - 7/12

 

1 ft. (30.48 cm)

CD32M and

 

with Vinyl

 

 

 

Siding

 

 

CD36M-A

 

 

 

 

 

 

 

 

 

 

 

7/12 - 8/12

 

 

 

 

 

 

 

 

 

1

 

10" x 10"

 

 

 

 

1

/2 ft. (45.72 cm)

 

 

 

 

8/12 - 9/12

 

2 ft (60.96 cm)

CD42M-A

 

 

 

 

 

10

3

/4" x 10

3

/4"

 

 

 

 

 

 

 

 

 

 

 

9/12 - 10/12

2

1

/2 ft (76.20 cm)

Figure 7 - Vent Termination (Horizontal)

 

 

 

 

 

 

 

 

 

10/12 - 11/12

4 ft (121.92 cm)

 

 

 

 

 

 

 

11/12 - 14/12

5 ft (152.40 cm)

 

 

 

 

 

 

 

14/12 - 16/12

6 ft (182.88 cm)

 

 

 

 

 

Roof

 

 

 

 

 

 

Flashing

 

 

 

 

 

 

 

 

 

 

 

 

16/12 - 18/12

7 ft (213.36 cm)

 

 

 

 

 

 

 

18/12 - 20/12

7

1

/2 ft (228.60 cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20/12 - 21/12

8 ft (243.84 cm)

 

 

 

 

 

 

 

 

 

 

 

 

Wall Strap

 

 

 

45° Elbows

Ceiling Firestop

Figure 8 - Vertical Termination with

Offset and Wall Strap

8

www.desatech.com

111916-01F

Image 8
Contents What to do if YOU Smell GAS CD32MTable of Contents Before YOU Begin IntroductionSelecting Location Mantel Clearances PreparationClearances to Combustibles Framing PRE-INSTALLATION PreparationVent Termination Clearances Minimum Clearances for Vent Terminations Venting Installation InstallationVenting Installation Precautions Vertical Termination with Offset and Wall Strap GAS Line HOOK-UP Electrical Hookup and Remote Receiver DiagramGAS Supply Testing Pilot Adjustment Removing Glass PanelInstalling LOG SET Models CD32M and CD36M-A SeriesCD42M-A Face Extension for Model CD32M only Burner Flame AdjustmentDecorative Facing For Your Safety Read Before Lighting Operating Fireplace Operation GuidelinesOperating Fireplace Lighting InstructionsTo Turn OFF GAS To Appliance Converting PilotConverting Fireplace from Natural GAS to PROPANE/LP GAS Converting Control ValveTroubleshooting Observed Problem Possible Cause RemedyIllustrated Parts Breakdown Models CD32M and CD36M-A SeriesParts List Description QTYModel CD42M-A KEY Part Number Description QTY Specifications Wiring DiagramAccessory and Replacement Parts ValveNot a UPC