Desa CD32M-1, CD32M-2, CD36M-A1 PRE-INSTALLATION Preparation, Vent Termination Clearances, Framing

Page 5

PRE-INSTALLATION

PREPARATION

Continued

VENT TERMINATION CLEARANCES

The final position of your fireplace depends on the location of the vent termination in relation to the clearances that must be observed as shown in Figure 5 on page 6.

The vent system serves as the “chimney” as well as the combustion air supply (air intake). The horizontal run must have a rise of 1/4" (.6 cm) for every 12" (30.48 cm) of horizontal run towards the termination. The maximum horizontal run depends on the vertical rise from the fireplace adapter collar to the vent termination (see table below).

VERTICAL

 

HORIZONTAL

 

 

 

0

to

1 ft (30.48 cm)

1 ft (30.48 cm)

to

4 ft (121.92 cm)

2 ft (60.96 cm)

to

8 ft (243.84 cm)

3 ft (91.44 cm)

to

12 ft (365.76 cm)

4 ft (121.92 cm)

to

16 ft (487.68 cm)

5 ft (152.40 cm)

to

15 ft (457.20 cm)

6 ft (182.88 cm)

to

14 ft (426.72 cm)

7 ft (213.36 cm)

to

13 ft (396.24 cm)

8 ft (243.84 cm)

to

12 ft (365.76 cm)

 

 

 

WARNING: Never allow the vent to run downward as this may cause excessive tempera- tures which could cause a fire.

WARNING: Horizontal sec- tions of this vent system require a minimum clearance of 2" from the top of the pipe and 1" mini- mum to the sides and bottom. Vertical sections of this system require a minimum of 1" clear- ance to combustible materials on all sides of the pipe.

FRAMING

Once the final location has been determined, ob- serving height clearances for vent termination, you may construct framing using dimensions shown in Figures 3 and 4, depending on your installation.

If the appliance is to be installed directly on carpet- ing, tile (other than ceramic) or any combustible material other than wood flooring, the appliance must be installed on a metal or wood panel extend- ing the full width and depth of the appliance.

 

CD32M

CD36M-A

CD42M-A

 

 

 

 

A

32 3/8"

36 1/8"

40 1/8"

B

34 5/8"

41 1/4"

48 1/4"

C

19"

23 1/2"

25 5/8"

A

B

C

Figure 3 - Framing Dimension

BDC

A

E

 

F

 

G

Nailing Ta

 

H

 

 

CD32M

CD36M-A

CD42M-A

 

 

 

 

 

 

 

 

 

 

A

28

1

/ "

35

3

/4"

41

5

/8"

 

 

2

 

 

 

 

 

 

B

13

5

/ "

15"

 

21

5

/

"

 

 

8

 

 

 

 

 

8

 

C

39

3

/ "

49

5

/

"

58

1

/

"

 

 

8

 

8

 

 

2

 

D

9 1/2"

10 3/8"

13 1/2"

E

9 7/8"

13 3/4"

16 3/4"

F

34

1

/ "

41

1

/

"

48"

 

 

 

2

 

8

 

 

 

 

 

G

35 1/2"

42 1/8"

48 1/4"

H

54

3

/ "

68

1

/

"

81

1

/2"

 

 

8

 

4

 

 

 

 

Figure 4 - Corner Installation

111916-01F

www.desatech.com

5

Image 5
Contents CD32M What to do if YOU Smell GASTable of Contents Before YOU Begin IntroductionSelecting Location Mantel Clearances PreparationClearances to Combustibles Framing PRE-INSTALLATION PreparationVent Termination Clearances Minimum Clearances for Vent Terminations Venting Installation InstallationVenting Installation Precautions Vertical Termination with Offset and Wall Strap GAS Line HOOK-UP Electrical Hookup and Remote Receiver DiagramGAS Supply Testing Removing Glass Panel Pilot AdjustmentModels CD32M and CD36M-A Series Installing LOG SETCD42M-A Face Extension for Model CD32M only Burner Flame AdjustmentDecorative Facing Operating Fireplace Operation Guidelines For Your Safety Read Before LightingLighting Instructions Operating FireplaceTo Turn OFF GAS To Appliance Converting PilotConverting Control Valve Converting Fireplace from Natural GAS to PROPANE/LP GASObserved Problem Possible Cause Remedy TroubleshootingModels CD32M and CD36M-A Series Illustrated Parts BreakdownDescription QTY Parts ListModel CD42M-A KEY Part Number Description QTY Wiring Diagram SpecificationsValve Accessory and Replacement PartsNot a UPC