TROUBLESHOOTING
27
TROUBLESHOOTING
Note: For additional help, visit DESA Heating Products’ technical service web site at www.desatech.com.
Note: All troubleshooting items are listed in order of operation.
WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.
CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/ pilot unit.
OBSERVED PROBLEM | POSSIBLE CAUSE | REMEDY |
| ||
When buttons on remote control are pressed, | 1. | Battery in remote control is either miss- | 1. | Replace battery in remote control | |
there is no response from fireplace |
| ing or has low power |
|
|
|
| 2. | Remote control is not pointed toward | 2. | Point remote control toward lower front | |
|
| fireplace |
| panel of fireplace when operating | |
| 3. | Manual ignition bypass switch not in | 3. | Place manual ignition bypass switch in | |
|
| OFF position |
| OFF position | |
| 4. | No power available to fireplace | 4. | Make sure power cord is plugged into | |
|
|
|
| electrical outlet and outlet has power | |
| 5. | Ignitor electrode not connected to igni- | 5. | Reconnect ignitor cable | |
|
| tor cable |
|
|
|
| 6. | Broken ignitor cable | 6. | Replace ignitor cable | |
| 7. | Ignitor electrode broken | 7. | Replace pilot assembly | |
| 8. | Ignitor electrode positioned wrong | 8. | Replace pilot assembly | |
|
|
|
|
|
|
When wall switch button is pressed, there is | 1. | No power available to fireplace | 1. | Make sure power cord is plugged into | |
no response from fireplace |
|
|
| an electrical outlet and outlet has power | |
| 2. | Manual ignition bypass switch not in | 2. | Place manual ignition bypass switch in | |
|
| OFF position |
| OFF position | |
| 3. | Wall switch wire harness is disconnected | 3. | Check continuity of wall switch wire | |
|
|
|
| harness. Make sure plug on wall switch | |
|
|
|
| wire harness is fully inserted into socket | |
|
|
|
| on circuit board in fireplace. Replace if | |
|
|
|
| necessary | |
|
|
|
|
|
|
Burner does not light after ODS/pilot is lit | 1. | Burner orifice clogged | 1. | Clean burner (see Cleaning and Mainte- | |
|
|
|
| nance, page 26) or replace burner orifice | |
| 2. | Inlet gas pressure is too low | 2. | Contact local gas company | |
|
|
|
|
|
|
Delayed ignition burner | 1. | Manifold pressure is too low | 1. | Contact local natural or propane/LP gas | |
|
|
|
| company | |
| 2. | Burner orifice clogged | 2. | Clean burner (see Cleaning and Mainte- | |
|
|
|
| nance, page 26) or replace burner orifice | |
|
|
|
|
|
|
Burner backfiring during combustion | 1. | Burner orifice is clogged or damaged | 1. | Clean burner (see Cleaning and Mainte- | |
|
|
|
| nance, page 26) or replace burner orifice | |
| 2. | Damaged burner | 2. | Replace damaged burner | |
| 3. | Gas regulator defective | 3. | Replace regulator | |
|
|
|
|
|
|
Slight smoke or odor during initial operation | 1. | Not enough air | 1. | Check burner for dirt and debris. If | |
|
|
|
| found, clean burner (see Cleaning and | |
|
|
|
| Maintenance, page 26) | |
| 2. | Gas regulator defective | 2. | Replace regulator | |
| 3. | Residues from manufacturing processes | 3. | Problem will stop after a few hours of | |
|
| and logs curing |
| operation | |
|
|
|
|
|
|
Moisture/condensation noticed on windows | 1. | Not enough combustion/ventilation air | 1. | Refer to Air for Combustion and Venti- | |
|
|
|
| lation requirements (page 5) |