HIGH ALTITUDE

INSTALLATION

Your Sun Valley B-vent freestanding fire- place heater has been AGA tested and ap- proved for elevations from 0-2000 feet and CGA certified for elevations from 0-4500 feet.

When installing this fireplace at an eleva- tion above 2000 feet (in the USA), you may need to decrease the input rating by chang- ing the existing burner orifice to a smaller size. Reduce input 4% for each 1000 feet above sea level. Check with your local gas company for proper orifice size identifica- tion and proper orifice for your location.

When installing this fireplace at an eleva- tion above 4500 feet (in Canada), check with local authorities.

For assistance with any high altitude installa- tion contact DESA International’s Technical Service Department at 1-800-DESA-LOG (1-800-337-2564).

TROUBLESHOOTING VENTING PROBLEMS

Most venting problems are caused by incor- rect vent sizing, improper installation, or inadequate air supply. A preliminary check for a field problem might include:

Using a draft meter to determine if venting system draft meets manufacturer’s specifications

Checking the vent sizing according to manufacturer’s specifications, appliance input, and venting configuration

Examining the entire venting system for faults such as disconnected joints for damaged vent sections

Making sure vent and air openings are not obstructed

If these procedures do not reveal the source of the problem, troubleshooting may include attention to common venting problems.

FLUE GAS SPILLAGE

Spillage occurs when flue gases cannot exit the vent system and back up into the dwell- ing. A primary symptom of appliances equipped with a Vent Safety Shutoff System (flue spill switch) is unexplained appliance shutoffs. Other symptoms of flue gas spillage at the draft hood include condensation on walls and windows and/or noticeable odors. Spillage may also result in the release of carbon monoxide, a colorless, odorless, highly toxic gas. A simple spillage test can be con- ducted if spillage is suspected. See Checking Gas Connection, pages 13 and 14.

CAUSES OF SPILLAGE AND CORRECTIVE ACTION

Incorrect Vent Sizing

If the vent is too small or too short, spillage may occur. If the vent is too large, excessive dilution air may cool flue gases and reduce draft, causing spillage. The vent cap size should also be checked. Check manufacturer’s instructions, appliance in- put rating, and appropriate sizing tables.

Venting Condition

Loose joints can affect draft and cause spill- age. “Mashed” vent sections and damaged vent caps can restrict flow and cause spill- age. Examine and replace as needed.

Obstructions

Small animals or birds may get into and block the vent or draft hood outlet. Dust, lint, and foreign objects may obstruct air inlets. Re- move obstructions and clean openings.

Lateral Run

Lengthy horizontal or non-vertical runs cause resistance to flow and may reduce draft enough to cause spillage. The pitch of lateral runs can also be a problem; lateral runs should be pitched 1/4" rise per foot of hori- zontal run from the appliance to the vent.

Elbows

Too many elbows cause excessive restric- tion of flow and may result in spillage. Usually, two 90º turns can be tolerated in a properly sized venting system. More than two may cause problems and necessitate changing the system.

Negative Pressure in the

Dwelling

An extremely tight house may not supply adequate combustion and venting air. Use of mechanical exhaust such as a dryer vent or range vent may worsen the problem. An air exchange system must be installed in the dwelling to correct this problem.

Flue Gas Cooling

Venting exposed to extremely cold tem- peratures or venting of single wall construc- tion loses heat needed to maintain draft; massive masonry chimneys absorb needed heat. If the flue gases cool excessively, draft is reduced and spillage may result. Use proper materials, insulate and protect prop- erly, reline when necessary.

Down Drafts

In certain wind conditions and in certain relationships with nearby structures and objects, high pressure conditions may affect draft negatively. Relocate the vent cap, raise its height, or use an approved high wind cap.

106022

11

Image 11
Contents MSBVBN, Msbvbp Remote Ready For Your SafetyFor Your Safety What to do if YOU Smell GAS SUN Valley Stove Company Safety InformationPiezo Ignitor Product FeaturesProduct Identification Local Codes OperationLocation and Space Requirements PRE-INSTALLATION PreparationRemove plastic bag from stove body Freestanding Fireplace AssemblyStove Body Assembly Lift off corrugated box enclosing stove body cratingAttaching Stove Legs Set three top grate sections into stove topInstalling GA3700/DA3610T Blowers Installing Fireplace Into Stove BodyInstalling Optional Blower Accessory Installation Precautions Venting InstallationInstalling Rear Cover Use only vents labeled for EXTE- Rior USE above the roofline Installation of Listed B-1 VentRelining Systems Installing Vent System in a ChaseChecking Vent Capacity ChimneysCauses of Spillage and Corrective Action Troubleshooting Venting ProblemsHigh Altitude Installation Flue GAS SpillageCheck GAS Type Fireplace InstallationInstalling GAS Piping to Fireplace Location Installation Items NeededChecking GAS Connections Connecting Fireplace to GAS SupplyPressure Testing Gas Supply Piping System Open manual shutoff valve see Fig- ure Pressure Testing Fireplace Gas ConnectionsClose manual shutoff valve see Fig- ure Installing Optional Wall Mounted Thermostat GWMT1, GWMS2 REMOVING/REPLACING Glass Door Installing Remote ReceiverInstalling 9-Volt Battery in Hand- Held Remote Control Unit Installing Log No Installing LOGS, Lava Rock and Glowing EmbersLighting Instructions For Your Safety Read Before LightingManual Lighting Procedure Operating FireplaceGhrct Series Operation Optional Remote OperationThermostat Control Operation Ghrc Series OperationOperating Optional GWMT1 Wall Mounted Thermostat Operating Optional Blower AccessoryPilot Assembly Inspecting BurnersLogs Cleaning and MaintenanceGlass Door Pilot and BurnersPressed in 30 seconds TroubleshootingAfter pilot lights, keep control knob Pane/LP or natural gas company OrificeInlet gas pressure is too low CompanyInner vent pipe leaking exhaust gasses Fireplace produces unwanted odorsPilot is partially clogged Nance,Service Hints Replacement PartsTechnical Service Wiring DiagramMsbvbn Msbvbp SpecificationsAccessories Msbvbn Msbvbp Illustrated Parts BreakdownKEY Part Number Description QTY Parts ListIndicates Color Suffix Designation SUN Valley Stove MC* SeriesKEY Part Description QTY International Warranty Information