Desa MSBVBP Installing Vent System in a Chase, Checking Vent Capacity, Chimneys, Relining Systems

Page 10

SUN VALLEY STOVE COMPANY

B-VENT FREESTANDING FIREPLACE

VENTING INSTALLATION

Continued

INSTALLING VENT SYSTEM IN A CHASE

A chase is a vertical boxlike structure built to enclose venting that runs along the out- side of a building. A chase is not required for such venting.

NOTICE: Treatment of firestops and construction of the chase may vary from building type to building type. These instructions are not substitutes for the re- quirements of local building codes. You must follow all local building codes.

Note: When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially im- portant in cold climates. Minimum clear- ance between vent pipes and combustible materials such as insulation is 1".

CHECKING VENT CAPACITY

Complete all gas piping, electrical, and vent connections. After adjusting the fireplace and lighting the main burners, allow a couple of minutes for warm-up. Hold a lighted match just under the rim of the draft hood relief opening. Proper venting will draw the flame toward or into the draft hood. Im- proper venting, indicated by escape or spill- age of burned gas, will cause match to flicker or go out. Smoke from a cigarette will also be pulled into the draft hood if the vent is drawing properly.

CHIMNEYS

Complete familiarity with chimney con- dition, height, size, clearance to combus- tibles and other factors is essential.

NOTICE: Consult the authority having jurisdiction in your area regarding masonry chimney vent- ing applications.

NOTICE: A complete chimney inspection by a qualified person should be performed.

Appliances using B-vent connectors to vent into a masonry or factory-built chimney should not exceed 1 1/2 feet in length for every inch of connector diam- eter (3" vent connector has a maximum 4 1/2 foot length; 5" connector has maxi- mum 7 1/2 foot length).

Oversized chimneys should be relined with appropriate listed relining systems.

Cleanout access may be required.

RELINING SYSTEMS

Suitability and approval of relining ma- terials should be determined.

Condition, size, height, and termina- tion of the chimney to be relined must be determined.

No substitution of components should be made.

Joints and connectors should be made according to manufacturer’s instructions.

NOTICE: Consult the authority having jurisdiction in your area regarding listed chimney liner venting applications.

WARNING: Operation of im- properly installed and maintained venting system could result in serious injury, property damage, or loss of life.

 

Figure 27 - Typical Straight Installation

 

with Listed Chimney Liner

Figure 25 - Test for Proper Venting

Figure 26 - Straight Installation into

Masonry Chimney

10

106022

Image 10
Contents For Your Safety What to do if YOU Smell GAS For Your SafetyMSBVBN, Msbvbp Remote Ready Safety Information SUN Valley Stove CompanyOperation Product FeaturesProduct Identification Local Codes Piezo IgnitorPRE-INSTALLATION Preparation Location and Space RequirementsLift off corrugated box enclosing stove body crating Freestanding Fireplace AssemblyStove Body Assembly Remove plastic bag from stove bodySet three top grate sections into stove top Attaching Stove LegsInstalling Optional Blower Accessory Installing Fireplace Into Stove BodyInstalling GA3700/DA3610T Blowers Installing Rear Cover Venting InstallationInstallation Precautions Installation of Listed B-1 Vent Use only vents labeled for EXTE- Rior USE above the rooflineChimneys Installing Vent System in a ChaseChecking Vent Capacity Relining SystemsFlue GAS Spillage Troubleshooting Venting ProblemsHigh Altitude Installation Causes of Spillage and Corrective ActionInstallation Items Needed Fireplace InstallationInstalling GAS Piping to Fireplace Location Check GAS TypePressure Testing Gas Supply Piping System Connecting Fireplace to GAS SupplyChecking GAS Connections Close manual shutoff valve see Fig- ure Pressure Testing Fireplace Gas ConnectionsOpen manual shutoff valve see Fig- ure Installing Optional Wall Mounted Thermostat GWMT1, GWMS2 Installing 9-Volt Battery in Hand- Held Remote Control Unit Installing Remote ReceiverREMOVING/REPLACING Glass Door Installing LOGS, Lava Rock and Glowing Embers Installing Log NoOperating Fireplace For Your Safety Read Before LightingManual Lighting Procedure Lighting InstructionsGhrc Series Operation Optional Remote OperationThermostat Control Operation Ghrct Series OperationInspecting Burners Operating Optional Blower AccessoryPilot Assembly Operating Optional GWMT1 Wall Mounted ThermostatPilot and Burners Cleaning and MaintenanceGlass Door LogsAfter pilot lights, keep control knob TroubleshootingPressed in 30 seconds Company OrificeInlet gas pressure is too low Pane/LP or natural gas companyNance, Fireplace produces unwanted odorsPilot is partially clogged Inner vent pipe leaking exhaust gassesWiring Diagram Replacement PartsTechnical Service Service HintsSpecifications Msbvbn MsbvbpAccessories Illustrated Parts Breakdown Msbvbn MsbvbpParts List KEY Part Number Description QTYSUN Valley Stove MC* Series Indicates Color Suffix DesignationKEY Part Description QTY Warranty Information International