Empire Comfort Systems CHBR-16-3 GAS Supply, Recommended Gas Pipe Diameter

Page 9

GAS SUPPLY

Check all local codes for requirements, especially for the size and type of gas supply line required.

Recommended Gas Pipe Diameter

Pipe Length

Schedule 40 Pipe

Tubing, Type L

 

Inside Diameter

Outside Diameter

 

Nat.

L.P.

Nat.

L.P.

0-10 feet

1/2”

3/8”

1/2”

3/8”

0-3 meters

12.7mm

9.5mm

12.7mm

9.5mm

10-40 feet

1/2”

1/2”

5/8”

1/2”

4-12 meters

12.7mm

12.7mm

15.9mm

12.7mm

40-100 feet

1/2”

1/2”

3/4”

1/2”

13-30 meters

12.7mm

12.7mm

19mm

12.7mm

100-150 feet

3/4”

1/2”

7/8”

3/4”

31-46 meters

19mm

12.7mm

22.2mm

19mm

Note: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.

Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.

A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not ad- equate, contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing. It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet. This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect.

Figure 3

The use of the following gas connectors is recommended:

ANS Z21.24ApplianceConnectors ofCorrugatedMetalTubing and Fittings

ANS Z21.45 Assembled Flexible Appliance Connectors of Other Than All-Metal Construction

The above connectors may be used if acceptable by the authority havingjurisdiction.ThestateofMassachusetts requiresthataflexible appliance connector cannot exceed three feet in length.

Pressure Testing of the Gas Supply System

1.To check the inlet pressure to the gas valve, a 1/8" (3.175mm) N.P.T. plugged tapping, accessible for test gauge connection, must be placed immediately upstream of the gas supply connection to the appliance.

2.The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).

3.The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

Attention! If one of the procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result in a hazardous condition.

16934-3-0806

Page 9

Image 9
Contents Installation Instructions Table of Contents Do not Tamper with Pilot Light Safety System Important Safety InformationLP-GAS Warning Odor Safety Information for Users of LP-GASSpecifications IntroductionProduct Description Well Head Gas Installations Installation on Rugs and TileGeneral Information Before you get startedUnusually Tight Construction Provisions for Adequate Combustion & Ventilation AIRClearances Pressure Testing of the Gas Supply System Installing a New Main Gas CockGAS Supply Recommended Gas Pipe DiameterSET-UP Instructions Placement of Glowing Embers and Lava Rock Thermostat Operation Operation INSTRUCTIONS/FLAME AppearanceCHBR-16 Lighting Instructions For Your Safety Read Before LightingCleaning and Maintenance/Pilot Pilot Flame CharacteristicsTurn OFF Heater and Allow to Cool Before Cleaning Cleaning and ServicingControl Panel Installation WiringCheck System Operation Millivolt SystemHeater produces a whistling noise when main burner is lit Gas odor even when control knob is in OFF positionAppliance produces unwanted odors Appliance shuts off during use. Pilot stays onHOW to Order Repair Parts Parts ListParts View Service Notes

CHBR-16-3 specifications

Empire Comfort Systems CHBR-16-3 is a premier choice for heating solutions, particularly favored for its combination of efficiency and convenience. This model is designed to meet the heating needs of various spaces, from homes to commercial settings, ensuring warmth and comfort even in the coldest winter months.

One of the standout features of the CHBR-16-3 is its impressive heating capacity. With an output of up to 16,000 BTUs, this unit can efficiently heat large areas, making it ideal for living rooms, basements, or even open floor plans. The powerful heat output is further complemented by a thermally efficient design, allowing the unit to operate effectively while keeping energy consumption low.

The CHBR-16-3 utilizes advanced technologies to maintain consistent temperatures. Its built-in blower system ensures an even distribution of heat throughout the space, eliminating cold spots and creating a comfortable environment. This feature is particularly beneficial in larger areas where heat can often be unevenly distributed.

Installation and ease of use are also highlights of this model. The unit is designed for straightforward installation and can be integrated into existing heating systems with relative ease. Additionally, it is equipped with a user-friendly manual control, giving users the ability to adjust settings according to their preferences. Optional remote control capabilities are also available, allowing for added convenience, especially during colder weather.

Safety is another crucial aspect of the CHBR-16-3. The unit is designed with multiple safety features, including an automatic shut-off to prevent overheating and a sealed burner to reduce the risk of carbon monoxide exposure. This attention to safety ensures peace of mind for users, allowing them to enjoy the warmth without worry.

Durability is a hallmark of Empire Comfort Systems products, and the CHBR-16-3 is no exception. Constructed from high-quality materials, this heater is designed to withstand the rigors of regular use. With proper maintenance, users can expect a long lifespan from this heating appliance.

In summary, the Empire Comfort Systems CHBR-16-3 is an excellent heating solution that stands out for its efficiency, user-friendly features, safety measures, and durable construction. Whether for residential or commercial use, this model provides reliable warmth that enhances comfort during the cold months.