Trouble Shooting
Problem | Possible Cause | Solution | |
  | 
  | 
  | |
The main burner  | The gas valve may not be on.  | • Check that the gas control knob is in the “ON” position.  | |
does not ignite  | 
  | 
  | |
Thermostat is not calling for  | • Adjust the thermostat several degrees above ambient temperature.  | ||
when called for.  | heat.  | 
  | |
  | 
  | ||
  | 
  | 
  | |
  | Problem with gas valve.  | • Use a DC voltmeter to measure the voltage across the TPTH and  | |
  | 
  | TP terminals. Main operator voltage: Open circuit ≥ 325mV Closed  | |
  | 
  | circuit ≥ 100mV  | |
  | 
  | • If voltage is not present, check the control circuit for proper  | |
  | 
  | operation.  | |
  | 
  | • If proper control system voltage is present, replace the gas control.  | |
  | 
  | 
  | |
Spark will not  | Defective piezo ignitor.  | • Check connections to ignitor.  | |
light the pilot  | 
  | • If ignitor connections are good but no spark, replace ignitor.  | |
after repeatedly  | 
  | 
  | |
Broken spark electrode.  | • Check for broken ceramic insulation, replace electrode if broken.  | ||
pressing the  | |||
  | 
  | ||
Misaligned spark electrode.  | • If spark is not arcing from electrode to pilot, loosen the screws on the  | ||
spark ignitor.  | |||
  | 
  | pilot base adjust and tighten.  | |
Pilot will not  | Problem with thermocouple  | • Check for proper connection of the thermocouple to the rear of the  | |
remain lit.  | circuit.  | valve. If loose, fully tighten.  | |
  | 
  | • Check pilot for full flame impingement around thermocouple. If flame  | |
  | 
  | is too small, check gas pressure, adjust pilot rate screw, check pilot  | |
  | 
  | head for damage.  | |
  | 
  | • Check thermocouple voltage at valve. It must be greater than 5 mV.  | |
  | 
  | If low, replace thermocouple.  | |
  | 
  | 
  | |
  | Air in gas line (pilot dies while  | • Bleed line.  | |
  | knob is depressed).  | • Check gas line pressure.  | |
  | 
  | • Contact dealer.  | |
  | 
  | 
  | |
Burners will not  | Problem with thermopile  | • Check gas line pressure .  | |
remain lit.  | circuit.  | • Check for flame impingement on thermopile. If low, see “Pilot will not  | |
  | 
  | remain lit”.  | |
  | 
  | • Check thermopile for minimum of 300 mV when burner is switched  | |
  | 
  | on.  | |
  | 
  | • Check wiring to thermostat for breaks.  | |
  | 
  | BV ONLY: Check for spillage at draft hood that may trip spill switch  | |
  | 
  | 
  | |
Flame lifting  | Leak in vent pipe  | • Check for leaks in vent connections.  | |
  | 
  | 
  | |
  | Improper vent configuration  | • Check vent configuration with manual.  | |
  | 
  | 
  | |
  | Terminal may be recirculating  | • Check to see if terminal is on correctly.  | |
  | flue gases  | • May need to install high wind termination cap.  | |
  | 
  | • Contact dealer.  | |
  | 
  | 
  | |
Glass fogs up  | Normal Condition: after the appliance warms up the glass will clear.  | ||
  | **Due to additives in gas, glass may get hazy during operation** Clean as needed.  | ||
  | 
  | 
  | |
Blue Flames  | Normal during start up: flames will yellow as the fireplace heats up.  | ||
  | 
  | 
  | |
Flames are  | Flame impingement  | • Check log positioning.  | |
burning “dirty” or  | 
  | • Increase primary air by opening the venturi shutter and/or by  | |
sooting  | 
  | opening the vent restrictor.  | |
  | 
  | See also “Burners will not remain lit.”  | |
  | 
  | 
  | |
Remote control  | Problem with the remote  | • One or more of the batteries are dead. See remote control  | |
doesn’t work  | 
  | instructions.  | |
  | 
  | 
  | |
  | Problem with fireplace  | • The on/off switch is turned to OFF.  | |
  | 
  | • The gas control valve is turned to PILOT or OFF.  | |
  | 
  | • The pilot has gone out.  | |
  | 
  | 
  | |
BV ONLY: | • Air tight house.  | • Supply make up air to the unit.  | |
Insufficient air  | • A vacuum in room due to  | 
  | |
for combustion  | other   | 
  | |
  | 
  | 
  | |
22