MAINTENANCE
CAUTION: ANY SAFETY SCREEN ORGUARDREMOVEDFORSERV- ICING AN APPLIANCE MUST BE REPLACED PRIOR TO OPERAT- ING THE APPLIANCE.
CLOTHING OR OTHER FLAMMA- BLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLI- ANCE.
NEVEROPERATETHEAPPLIANCE WITHOUTTHEGLASSPROPERLY SECURED IN PLACE.
THERMOPILE/
THERMOCOUPLE
1)Loosen the thermocouple or thermopile with a 7/16" wrench at bracket.
2)Disconnect thermocouple by loosening nut from the valve with a 9mm wrench. Discon- nect thermopile by loosening 2 screws marked TP on the valve.
3)Drop the thermocouple or thermopile down from the bracket and pull it out of the unit.
4)Reinstall the new ones in reverse order.
PILOT ADJUSTMENT
Periodically check the pilot flames. Cor- rect flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).
Note: If you have an incorrect flame pat- tern, contact your Regency dealer for further instructions.
GENERAL VENT
MAINTENANCE
Conduct an inspection of the venting system at least annually. Recommended areas to inspect are:
1)Check areas of the Venting System which are exposed to the elements for corrosion. These will appear as rust spots or streaks, and in extreme cases, holes. These com- ponents should be replaced immediately.
2)Remove the Cap, and shine a flashlight down the Vent. Remove any birds nests, or other foreign material.
3)Check for evidence of excessive conden- sation, such as water droplets forming in the liner, and subsequently dripping out the joints, Continuous condensation can cause corrosion of caps, pipe, and fittings. It may be caused by having excessive lateral runs, too many elbows, or exterior portions of the system being exposed to cold weath- er.
4)Inspect joints, to verify that no pipe sections or fittings have been disturbed, and conse- quently loosened. Also check mechanical supports such as Wall Straps for rigidity.
AERATION
ADJUSTMENT
The aeration adjustment rod is attached to the air shutter on the burner. The air shutter adjust- ment rod is located under the ashlip on the right side. The rod is used to adjust the aeration on the burner. This adjustment is performed by the installer and is primarily used in installations at high elevations. Push the rod in for a yellow flame, or pull out on the rod for a bluer flame.
Air shutter opening: |
|
Natural Gas | 7/16" |
Propane | Wide open |
Top View of pilot flame
Incorrect flame pattern will have small, probably yellow flames, not coming into proper contact with the rear burner or thermopile or thermocouple.
Top View of pilot flame
Closed - Tall Yellow flame
Open - Short Blue flame
Caution: Carbon will be produced if air shutter is closed too much.
Note: Aeration Adjustment should only be performed by an authorized Regency Installer at the time of installation or service.
16 | Regency CLASSIC |