16 | Stove Installation (for qualified installers only) |
Hearth Stove Direct Connection
NOTE:
Direct connections require installation of an airtight,
NOTE: The chimney must have a clay tile liner. If it does not, the installation must use a positive connection (full reline). The entire fireplace and chimney must be clean, undamaged, and meet all local building codes (UBC, etc.). Damage must be repaired prior to installation. The chimney must be 15' to 33' tall.
Max. 8”
Combustible Mantle
Min. 18"
Floor Protection
(See the section "Floor Protection Requirements" for more details)
Clay
Liner
Stainless steel chimney connector must Extend 1' past the
Airtight
Insulated
Remove damper or wire it open
See the section "Stove Placement Requirements" for minimum clearances required.
Figure 14
Interior or Exterior Masonry Chimney
NOTE:
This type of installation requires a UBC approved masonry connector or a factory built (U.L. Listed) wall thimble.
NOTE: The chimney must have a clay tile liner. If it does not, the installation must use a positive connection (full reline). The entire fireplace and chimney must be clean, undamaged, and meet all local building codes (UBC, etc.). Damage must be repaired prior to installation. The chimney must be 15' to 33' tall.
See the section "Stove Placement Requirements" for minimum clearances required.
Chimney connector sections
See the section "Floor Protection Requirements"
Min. 18" |
clearance |
to ceiling |
Clay Liner
This type of installation requires a UBC approved masonry connector or a factory built (U.L. Listed) wall thimble.
Make sure the
Figure 15
© Travis Industries | 4040608 |