8 | Stove Installation (for qualified installers only) |
Floor Protection Requirements
•Stove must be placed on the Travis Industries legs or Pedestal.
•Floor protection must extend 6" to the sides and rear of the stove and 16" to the front of the stove (36" wide by
•Floor protection must be
Stove Placement Requirements
Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or other means approved by local building or fire officials.
•Stove must be placed so that no combustibles are within, or can swing within (e.g. drapes, doors), 36" of the front of the stove
•If the stove is placed in a location where the ceiling height is less than 7', it must follow the requirements in the section "Alcove Installation Requirements"
•Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):
Clearances
• The following clearances must be met (see Figure 2 and Figure 3) |
| |||
|
|
|
| |
| Minimum Clearance | Singlewall | Reduced | |
|
|
| Connector | Clearance* |
|
|
|
|
|
| A | Sidewall to stove | 15" | 13" |
| B | Backwall to stove | 15” | |
| C | Cornerwall to stove | 15" | |
| D | Connector to sidewall | 24" | |
| E | Connector to backwall | ||
| F | Connector to cornerwall | 24" | 15" |
|
|
|
|
|
*Reduced clearance installations require one of the chimneys and connectors listed below:
DURAVENT model DVL with DURATEC or
GSW Super Chimney
I.C.C. Excel
METALFAB model DW connector with TG chimney
OLIVER MACLEOD PROVENT model PV connector with model 3103 chimney
SECURITY model DP connector with SECURITY model ASHT or S2100 chimney
SELKIRK METALBESTOS model DS connector with model SSII chimney
Standard Masonry Chimney with any one of the above listed connectors
NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be required.
NOTE: Standard residential installations with reduced clearance connector may use the clearance determined by the manufacturer of the connector for the connector to wall clearance or the clearance listed in this manual. Offsets must be used to maintain the stove to wall clearance.
© Travis Industries | 4040608 |