Weil-McLain 550-110-260/02002 3c Water piping multiple zones, Converted gravity or steam systems

Page 16

GOLD CGs Gas-Fired Water Boiler

3c Water piping — multiple zones

Piping multiple zones Follow instructions on pages 14 and 15 to install near-boiler or single-zone piping. (Also refer to Piping for radiant heating systems or converted gravity systems, below, if applicable.)

See Figure 6 or Figure 7 to complete installation.

Zoning with circulators, return temp over 130 °F

Zoning with zone valves, return temp over 130 °F

Piping for radiant heating systems or converted gravity systems

1.Size each circulator to individual circuit requirements.

2.Do not install circulator on boiler (except for primary/secondary piping).

3.Install isolation (balancing) valves to adjust flow to distribute heat to all zones.

4.Install and wire a separate relay for each zone circulator.

1.Install isolation (balancing) valves to adjust flow to distribute heat to all zones.

2.Provide a separate 24-volt transformer to power the zone valves. Size the transformer to handle the total rated load of all connected zone valves.

Converted gravity (or steam) systems

Whenever possible, use the primary/secondary piping shown in Figures 8 or 9 on page 19. This piping design allows changing boiler flow rate without affecting primary circuit flow rate.

If Figures 8 or 9 cannot be used, use the boiler-bypass piping shown in Figure 10 or Figure

11on page 21. You can also use the piping shown in Figure 12 on page 23 (system-bypass), if the reduced flow rate in the heating system will not cause heat distribution problems.

Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.

Radiant heating systems

Preferably, use primary/secondary piping, as shown in Figures 8 or 9 on page 19. Alternatively, use the method of either Figure 10 or Figure 11 on page 21. Do not use the piping of Figure 12 (system-bypass), because this method does not control radiant system supply temperature.

If radiant system tubing has no oxygen barrier, a heat exchanger must be used.

Radiant heating system piping should include a means of regulating the boiler return water temperature and the system supply temperature (such as provided by an injection pumping control). Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the system supply temperature is relatively constant.

Do not apply the methods in this manual if the system is equipped with an outdoor reset control. Instead, provide controls and piping which can regulate the boiler return water temperature at no less than 130 °F regardless of system supply temperature. Contact your Weil-McLain representative for suggested piping and control methods. Failure to prevent cold return water temperature to the boiler could cause corrosion damage to the sections or burners, resulting in possible severe personal injury, death or substantial property damage.

16

Part number 550-110-260/0200

Image 16
Contents Page How it works ① Control modulePage Contents Please read before proceeding InstallerUser 1a Prepare boiler location codes & checklist 1b Prepare boiler location clearances Residential garage installationFlooring and foundation 1c Prepare boiler location vent system Removing from existing vent1d Prepare boiler location contamination Air contamination1e Prepare boiler location air openings CGs combustion air optionsSizing air openings for CGs installations 2a Prepare boiler placement & setup Orifice replacement procedurePlace boiler/crate near position Inspect orifices and burners2b Prepare boiler pressure test Perform hydrostatic pressure testPrepare boiler for test Fill and pressure test3a Water piping general information 3b Water piping single-zone system Expansion tankDiaphragm-type or bladder-type expansion tank Figure Closed-type expansion tank Figure3c Water piping multiple zones Converted gravity or steam systemsTypical piping multiple-zone installations Temperature gauges Valve adjustment 3d Water piping low temp systemsPrimary/secondary preferred bypass piping For radiant heating or converted gravity systems3e Water piping low temp systems Boiler-bypass alternate piping 3f Water piping low temp systems 3g Water piping refrigeration system 3f system-bypass alternate pipingPrevent chilled water from entering boiler Venting and combustion air Connecting gas supply piping to boilerGas piping Natural Gas LengthField wiring Wiring connectionsThermostat Junction Box furnishedFreeze protection when used 7a Start-up preparationDetermine if water treatment is needed Check for gas leaks7a Start-up preparation 7b Start-up operate boilerCheck burner flames 7c Start-up if boiler doesn’t startCheck for Check-out procedure checklist Installation and service certificate9a Operation sequence Raise room thermostat to call for heat9b Operation wiring diagrams Schematic wiring diagramService For Your Safety Read Before Operating 9c Operation lighting instructions10a Service and maintenance schedule Service technician10b Service & maintenance annual start-up Burners, base and inlet air box Boiler heating surfacesCondensate drain system Inducer motor10b Service & maint. annual start-up Boiler relief valve Lever must be operated AT LeastReview with owner 11a Troubleshooting procedure Before troubleshooting11b Troubleshooting air pressure switch Check pressure switch setting11c Troubleshooting control module Control indicator lights lockout modesControl module connections 11d Troubleshooting control module lights Chart 1 Troubleshooting Power light statusChart 2 Tstat Circ & Power lights flashing Chart 3 Press Switch & Power lights flashing Chart 4 Flame & Power lights flashing Turn OFF Power to boiler at service switch or breaker Does blower motor operate? Verify Sequence of operation, , 12a Replacement parts Page Page Page Page Page 13a Dimensions Dimensional drawing13b Ratings DOEHandling ceramic fiber and fiberglass materials Removal of Combustion Chamber Lining or Base Panels

550-110-260/02002 specifications

Weil-McLain is a well-known manufacturer of high-quality heating systems and boiler solutions, and the 550-110-260/02002 model is a testament to the company's commitment to innovation and performance. This particular boiler is designed for commercial and residential applications, providing exceptional heating efficiency and reliability.

One of the standout features of the Weil-McLain 550-110-260/02002 is its robust construction. Built using durable materials, this boiler is engineered to withstand demanding environments while maintaining optimal performance. The unit boasts a high thermal efficiency rating, which translates to lower energy costs and reduced environmental impact. The advanced design ensures that fuel consumption is minimized while delivering consistent heat output.

The Weil-McLain 550-110-260/02002 utilizes a multi-stage burner that enhances combustion efficiency. This feature not only reduces emissions but also improves overall energy use, making it an environmentally friendly choice. The sophisticated control system allows for precise modulation of the burner, ensuring that the boiler operates at peak efficiency under various load conditions.

The boiler is equipped with a user-friendly digital control interface, providing operators with real-time monitoring and diagnostics. This allows for easy adjustments and troubleshooting, which helps to reduce maintenance downtime. The integrated safety features enhance the operational reliability of the unit, ensuring safe operation in any environment.

Another important characteristic of the Weil-McLain 550-110-260/02002 is its adaptability. It can be configured to work with various types of fuel including natural gas and propane, giving users the flexibility to choose the most cost-effective energy source. This versatility also helps to extend the lifespan of the boiler as it can be easily adapted to changing energy needs.

In conclusion, the Weil-McLain 550-110-260/02002 is a high-performance boiler that combines durability, efficiency, and advanced technology. With its robust construction, efficient burner system, and user-friendly controls, it stands out as a reliable heating solution for both commercial and residential applications. The commitment to quality and innovation makes this model a preferred choice for those seeking dependable heating systems. Whether for new installations or replacements, the Weil-McLain 550-110-260/02002 delivers exceptional performance and value.