Weil-McLain 550-110-260/02002 manual 3d Water piping low temp systems

Page 18

GOLD CGs Gas-Fired Water Boiler

3d Water piping — low temp systems

Primary/secondary (preferred) bypass piping method

Temperature gauges

Valve adjustment

(Figure 12 and 13 only)

Primary/secondary bypass piping is preferred because the flow rate and temperature drop in the heating circuit(s) is determined only by the heating circuit circulator(s). So adjustment of the bypass valves in the boiler circuit will not cause a change in the heating circuit rate and temperature distribution.

Figures 8 and 9 show suggested bypass arrangements using primary/secondary bypass piping (preferred) for low temperature systems such as radiant heating systems or converted gravity systems. For alternatives, see pages 20 through 23.

The bypass valves (items 7a and 7b) provide mixing of hot boiler outlet water with cooler system return water — set to assure a minimum return water temperature (at least 130 °F) to the boiler. Set the valves as explained below.

Gauge 4a is suggested, but optional on any system.

Gauge 4b is optional on converted gravity systems, but required on radiant heating systems

— to display the water temperature being supplied to the radiant tubing.

Gauge 8 is required on all systems to assure the return water temperature is accurately set for a minimum of 130 °F. If this gauge is not available however, adjust the valves such that the boiler-mounted temperature/pressure gauge reads at least 150 °F when the system return water is cold (approximately 60 °F water temperature).

1.Set the valves while the system is cool, setting for the coldest expected water temperature (usually 60 °F since the system will often drop to room temperature between cycles).

2.Start with valve 7a fully closed and 7b fully open.

3.Gradually open valve 7a while closing valve 7b until the temperature at gauge 8 reads 130 °F when gauge 4a reads 60 °F.

4.Note that valve 7a regulates the amount of hot water from the boiler supply which mixes with return water. Valve 7b regulates the amount of system water flowing through the boiler secondary loop.

Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.

Radiant heating system piping should include a means of regulating the boiler return water temperature and the system supply temperature (such as provided by an injection pumping control).

Boiler return water temperature will be adequately controlled using the methods shown in this manual provided the system supply temperature is relatively constant.

DO NOT apply the methods of this manual if the system is equipped with an outdoor reset control. Instead, provide controls and piping which can regulate the boiler return water temperature at no less than 130 °F regardless of system supply temperature. Contact your Weil-McLain representative for suggested piping and control methods.

Failure to prevent cold return water temperature to the boiler could cause corrosion damage to the sections or burners, resulting in possible severe personal injury, death or substantial property damage.

18

Part number 550-110-260/0200

Image 18
Contents Page How it works ① Control modulePage Contents Installer Please read before proceedingUser 1a Prepare boiler location codes & checklist Residential garage installation 1b Prepare boiler location clearancesFlooring and foundation 1c Prepare boiler location vent system Removing from existing vent1d Prepare boiler location contamination Air contamination1e Prepare boiler location air openings CGs combustion air optionsSizing air openings for CGs installations Place boiler/crate near position 2a Prepare boiler placement & setupOrifice replacement procedure Inspect orifices and burnersPrepare boiler for test 2b Prepare boiler pressure testPerform hydrostatic pressure test Fill and pressure test3a Water piping general information Diaphragm-type or bladder-type expansion tank Figure 3b Water piping single-zone systemExpansion tank Closed-type expansion tank Figure3c Water piping multiple zones Converted gravity or steam systemsTypical piping multiple-zone installations Temperature gauges Valve adjustment 3d Water piping low temp systemsPrimary/secondary preferred bypass piping For radiant heating or converted gravity systems3e Water piping low temp systems Boiler-bypass alternate piping 3f Water piping low temp systems 3f system-bypass alternate piping 3g Water piping refrigeration systemPrevent chilled water from entering boiler Connecting gas supply piping to boiler Venting and combustion airGas piping Natural Gas LengthThermostat Field wiringWiring connections Junction Box furnishedDetermine if water treatment is needed Freeze protection when used7a Start-up preparation Check for gas leaks7a Start-up preparation 7b Start-up operate boiler7c Start-up if boiler doesn’t start Check burner flamesCheck for Check-out procedure checklist Installation and service certificate9a Operation sequence Raise room thermostat to call for heat9b Operation wiring diagrams Schematic wiring diagramService For Your Safety Read Before Operating 9c Operation lighting instructions10a Service and maintenance schedule Service technician10b Service & maintenance annual start-up Condensate drain system Burners, base and inlet air boxBoiler heating surfaces Inducer motor10b Service & maint. annual start-up Boiler relief valve Lever must be operated AT LeastReview with owner 11a Troubleshooting procedure Before troubleshooting11b Troubleshooting air pressure switch Check pressure switch setting11c Troubleshooting control module Control indicator lights lockout modesControl module connections 11d Troubleshooting control module lights Chart 1 Troubleshooting Power light statusChart 2 Tstat Circ & Power lights flashing Chart 3 Press Switch & Power lights flashing Chart 4 Flame & Power lights flashing Turn OFF Power to boiler at service switch or breaker Does blower motor operate? Verify Sequence of operation, , 12a Replacement parts Page Page Page Page Page 13a Dimensions Dimensional drawing13b Ratings DOEHandling ceramic fiber and fiberglass materials Removal of Combustion Chamber Lining or Base Panels

550-110-260/02002 specifications

Weil-McLain is a well-known manufacturer of high-quality heating systems and boiler solutions, and the 550-110-260/02002 model is a testament to the company's commitment to innovation and performance. This particular boiler is designed for commercial and residential applications, providing exceptional heating efficiency and reliability.

One of the standout features of the Weil-McLain 550-110-260/02002 is its robust construction. Built using durable materials, this boiler is engineered to withstand demanding environments while maintaining optimal performance. The unit boasts a high thermal efficiency rating, which translates to lower energy costs and reduced environmental impact. The advanced design ensures that fuel consumption is minimized while delivering consistent heat output.

The Weil-McLain 550-110-260/02002 utilizes a multi-stage burner that enhances combustion efficiency. This feature not only reduces emissions but also improves overall energy use, making it an environmentally friendly choice. The sophisticated control system allows for precise modulation of the burner, ensuring that the boiler operates at peak efficiency under various load conditions.

The boiler is equipped with a user-friendly digital control interface, providing operators with real-time monitoring and diagnostics. This allows for easy adjustments and troubleshooting, which helps to reduce maintenance downtime. The integrated safety features enhance the operational reliability of the unit, ensuring safe operation in any environment.

Another important characteristic of the Weil-McLain 550-110-260/02002 is its adaptability. It can be configured to work with various types of fuel including natural gas and propane, giving users the flexibility to choose the most cost-effective energy source. This versatility also helps to extend the lifespan of the boiler as it can be easily adapted to changing energy needs.

In conclusion, the Weil-McLain 550-110-260/02002 is a high-performance boiler that combines durability, efficiency, and advanced technology. With its robust construction, efficient burner system, and user-friendly controls, it stands out as a reliable heating solution for both commercial and residential applications. The commitment to quality and innovation makes this model a preferred choice for those seeking dependable heating systems. Whether for new installations or replacements, the Weil-McLain 550-110-260/02002 delivers exceptional performance and value.