Confined Space Air Requirements for |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
| (a) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
U.S. Installations |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Refer to Figure 6 (a), (b), (c) or (d) for proper sizing and |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
location of combustion air ducts and openings. CHECK |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
LOCAL CODES. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
(a) Equipment located in confined spaces; all air from |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| PERMANENT |
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OPENINGS |
|
|
| |||||||||
inside the building. |
|
|
| CONFINED |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
Two permanent openings shall be provided connecting |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| UNCONFINED |
|
|
| ||||||||||||
|
|
| SPACE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
the confined space (e.g., closet, small room) with the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SPACE |
|
|
| ||||||||||
unconfined space. Each opening shall have a free area |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
of one square inch per 1,000 BTU/hour input (22 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
cm²/kW) of all appliances in the confined space, but not |
|
|
|
|
|
|
| EQUIPMENT LOCATED IN CONFINED SPACES; |
|
|
|
|
|
|
| ||||||||||||||||
less than 100 square inches (645 cm²). The top open- |
|
|
|
|
|
|
| ALL AIR FROM INSIDE THE BUILDING. |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
ing shall commence within 300mm (12 in.) of the top of |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
| (b) |
|
|
|
|
| COMBUSTION |
|
|
|
|
|
|
|
| PERMANENT |
|
| |||||||||||
space and the bottom opening shall commence within |
|
|
|
|
|
|
|
|
| 300mm |
| VENTILATION |
|
| |||||||||||||||||
300mm (12 in.) of the bottom of the enclosure. |
|
|
|
|
|
|
|
|
| AIR DUCT |
| (12 in.) |
|
|
|
|
|
|
| AIR. |
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 300mm |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
(b) Basement installation, equipment located in con- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (12 in.) |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ABOVE |
|
|
| ||||||
fined spaces; all air from outdoors. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| GRADE |
|
|
| |||||
|
| CONFINED |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OR |
|
|
| |||||||
When supplying air directly from the outdoors, each |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SNOW |
|
|
| |||||||||
|
|
| SPACE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
opening shall have a minimum free area of one square |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LINE |
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
inch per 4,000 BTU/hour input (5.5 cm²/kW) of total |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| GRADE |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
input rating of all appliances in the confined space. The |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
inlets shall be a minimum of 300mm (12 in.) above the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
grade (snow) line. The top opening shall commence |
|
|
|
|
| BASEMENT INSTALLATION, EQUIPMENT LOCATED |
|
|
|
|
|
|
| ||||||||||||||||||
within 300mm (12 in.) of the top of the confined space. |
|
|
|
|
| 300mm |
|
|
| ||||||||||||||||||||||
|
|
|
|
|
|
|
| IN CONFINED SPACES; ALL AIR FROM OUTDOORS | (12 in.) |
|
|
| |||||||||||||||||||
(c) Equipment located in confined spaces; all air from |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
| (c) |
|
|
|
|
|
|
|
|
|
|
| OUTDOORS |
|
|
|
|
| |||||||||||
outdoors. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| AIR DUCT |
|
|
| |||||||||||||
When supplying air directly from the outdoors using hor- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
izontal ducting, each opening shall have a free mini- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 300mm (12 in.) |
|
| ||||||||||
mum area of one square inch per 2,000 BTU/hour (11 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
cm²/kW) of total input rating of all appliances in the con- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
fined space. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
(d) Equipment located in confined spaces; all air from |
|
| CONFINED |
|
|
|
|
|
|
|
|
|
|
|
|
| VENTILATION |
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| COMBUSTION |
|
|
| |||||||||||||
|
|
| SPACE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
outdoors through ventilated attic. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
When supplying air directly through vertical ducting, |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
each opening shall have a free minimum area of one |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
square inch per 4,000 BTU/hour (5.5 cm²/kW) of total |
|
|
|
|
|
|
| EQUIPMENT LOCATED IN CONFINED |
|
|
| 300mm (12 in.) |
|
|
| ||||||||||||||||
input rating of all appliances in the confined space. |
|
|
|
|
|
|
| SPACES; ALL AIR FROM OUTDOORS. |
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| (d) |
|
|
|
|
| ATTIC LOUVERS TO OUTDOORS |
|
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OUTLET |
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| AIR |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| INLET AIR |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| DUCT |
|
|
|
| ||||||
|
|
|
|
|
| CONFINED |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| SPACE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
| Burn Hazard |
|
|
|
|
|
|
|
|
|
| 300mm (12 in.) |
|
|
|
|
|
|
| ||||||||||||
| Do not touch vent. |
|
|
|
| EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR |
|
|
|
|
|
|
| ||||||||||||||||||
| Doing so can result in |
|
|
|
|
|
|
| FROM OUTDOORS THROUGH VENTILATED ATTIC. |
|
|
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Figure 6 | Combustion Air Supply Openings And Ducts | ||||||||||||||||||||||||||||||
| burns. | ||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
| (U.S.A.) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||