GSW 72090 manual Confined Space Air Requirements for Canadian Installations, Local Codes

Page 9

Air Requirements

Important: Air for combustion and ventilation must not come from a corrosive atmosphere. Any failure due to cor- rosive elements in the atmosphere is excluded from war- ranty coverage.

Installations in or for certain places including, but not limited to, those listed below will require outdoor air for combustion due to chemical exposure:

Beauty shops

Photo processing labs Buildings with indoor pools

Water heaters installed in laundry, hobby or craft rooms Water heaters installed near chemical storage areas

In such circumstances, outdoor combustion air may reduce, but will not eliminate, the presence of corrosive chemicals in the air. Combustion air must be free of acid-forming chemi- cals such as sulfur, fluorine and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresheners, paint and varnish removers, refrig- erants and many other commercial and household prod- ucts. When burned, vapors from these products form highly corrosive acid compounds. These products should not be stored or used near the water heater or air inlet.

The area in which the heater is located is classified as either “an unconfined space” or “a confined space”.

An unconfined space is defined as a space having a vol- ume not less than 50 cubic feet per 1000 BTU/hour (4.8 cubic metres per kilowatt) of combined input rating of all appliances using the space. Adjacent open rooms may be included as part of the unconfined space, provided there are no closeable doors between these rooms. An example of this is an open basement.

A confined space is one smaller than described above. For buildings using tight construction (newer and renovated structures), the air supply shall be introduced from the out- doors, regardless of whether the space is confined or unconfined.

Confined Space Air Requirements for Canadian Installations

Refer to Figure 5 (a), or (b), and Table 1 for proper sizing and location of combustion air ducts and openings. CHECK

LOCAL CODES.

(a). Two permanent openings shall be provided connecting the confined space (e.g., closet, small room) with the unconfined space. Each opening shall have a free area of one square inch per 1,000 BTU/hour input (22 cm²/kW) of all appliances in the confined space. The top opening shall be located as close to the ceiling as prac- tical but never lower than the top of the heater. (see Figure 5 (a)). The bottom opening shall be located nei- ther more than 450mm (18 in.), nor less than 150mm (6 in.), above floor level.

(b). When using a single air supply, the duct shall terminate within 300mm (12 in.) above and within 600mm (24 in.) horizontally of the burner level of the appliance having the largest input. For example: GSW’s water heaters’ burners are 150mm (6 in.) from the floor, plus 300mm

(a)

PERMANENT

OPENINGS

CONFINED

SPACEUNCONFINED SPACE

EQUIPMENT LOCATED IN CONFINED SPACES;

ALL AIR FROM INSIDE THE BUILDING.

 

 

 

 

 

 

 

300mm

 

 

(b)

CONFINED

 

(12 in.)

 

SPACE

 

 

(MIN)

 

 

GRADE

COMBINATION

COMBUSTION/

VENTILATION

AIR DUCT

600mm (24 in.)

450mm (18 in.)

BASEMENT INSTALLATION, EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM OUTDOORS

Figure 5 Combustion Air Supply Openings And Ducts (Can.)

Combined Input

 

 

Acceptable Round

Required

Duct Size Diameter

of All Appliances

in Confined

Free Area

A**

 

B***

 

Space*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BTU / h

(kW / hr)

cm2

in.2

mm

 

in.

mm

 

in.

25,000

8

45

7

76

 

3

100

 

4

50,000

15

45

7

76

 

3

100

 

4

75,000

23

70

11

100

 

4

125

 

5

100,000

30

90

14

100

 

4

125

 

5

125,000

37

120

18

125

 

5

150

 

6

150,000

45

140

22

125

 

5

150

 

6

*All appliances refers to, and includes, those appliances using the same air source (e.g. water heater, furnace, boiler, clothes dryer etc.).

**Maximum allowable length of ductwork listed in column A is 6.1 equivalent metres (20 ft.).

***Maximum allowable length of ductwork listed in column B is 15.2 equivalent metres (50 ft.)

Table 1 Air Supply Sizing (Can.)

(12 in.) equals 450mm (18 in.) as shown in Figure 5 (b). All exterior vent openings are to be at least 300mm (12 in.) above the ground and clear of snow levels.

– 9 –

Image 9
Contents What to do if YOU Smell GAS For Your SafetyPage Viii Troubleshooting Guide IX Repair Parts IllustrationLimited Warranty For Installations in Canada Introduction II SafetyFor Installations in the United States User ResponsibilitiesSafety Warning Scalding Safety Warning Flammable VapoursSafety Warning Carbon Monoxide Backflow Prevention Clearances and Accessibility Location Requirements Earthquake Zones Failure to Properly Install this Heater MAY Gas SupplyResult in a Fire Hazard Gas Leak Testing Gas PressureGas line purging Confined Space Air Requirements for Canadian Installations Air RequirementsLocal Codes Confined Space Air Requirements for Installations Water Supply Exhaust VentingLicensed plumber repair it Valve is dripping or leaking, have aDo not plug valve Do not remove valveInstallations Check Temperature And Pressure Relief ValveDischarge Line Temperature Adjustment IV Operating Instructions Water Temperature RegulationWhat to do if YOU Smell GAS Lighting Instructions Robertshaw 110RLighting Instructions Robertshaw 220R Avant Lighting Instructions White-Rodgers 37CEmergency Shut Down Operation Burner FlamesChecking the Draft Operating ConditionsVI Maintenance Draining and FlushingPeriodic Inspection External Cleaning Flame-arrester Resetting and Replacing the Safety TCO SwitchTemperature and Pressure Relief Valve System Requirements VII Combo HeatingProblem Possible Causes Correction Viii Troubleshooting GuideThermostat Fails to Shut Repair Parts IX Repair Parts IllustrationWHO is Covered Limited WarrantyHOW the Original Owner can Make a Warranty Claim