Johnson Controls TM9T*MP Section IV GAS Piping, Horizontal Filters, Downflow Filters, GAS Safety

Page 10

505309-UIM-D-0511

HORIZONTAL APPLICATION

Horizontal Filters

All filters and mounting provision must be field supplied. All installa- tions must have a filter installed.

Any branch duct (rectangular or round duct) attached to the plenum must attach to the vertical plenum before the filter. The use of straps and/or supports is required to support the weight of the external filter box.

Downflow Filters

Downflow furnaces typically are installed with the filters located above the furnace, extending into the return air plenum or duct. Any branch duct (rectangular or round duct) attached to the plenum must attach to the vertical plenum above the filter height.

Filter(s) may be located in the duct system external to the furnace using an external duct filter box attached to the furnace plenum or at the end of the duct in a return filter grille(s). The use of straps and/or supports is required to support the weight of the external filter box.

SECTION IV: GAS PIPING

GAS SAFETY

DANGER

An overpressure protection device, such as a pressure regulator, must be installed in the gas piping system upstream of the furnace and must act to limit the downstream pressure to the gas valve so it does not exceed 0.5 psig [14" w.c. (3.48 kPa)]. Pressures exceeding

0.5psig [14” w.c. (3.48 kPa)] at the gas valve will cause damage to the gas valve, resulting in a fire or explosion or cause damage to the furnace or some of its components that will result in property damage and loss of life.

HIGH STAGE REGULATOR

ADJUSTMENT

 

OUTLET

 

PRESSURE

 

PORT

VENT

 

PORT

INLET

OUTLET

 

WRENCH

 

BOSS

 

INLET

 

PRESSURE

 

PORT

LOW STAGE REGULATOR

ON OFF

SWITCH

ADJUSTMENT

FIGURE 15: Gas Valve

Plan your gas supply before determining the correct gas pipe entry. Use 90-degree service elbow(s), or short nipples and conventional 90-degree elbow(s) to enter through the cabinet access holes.

GAS PIPING INSTALLATION

Properly sized wrought iron, approved flexible or steel pipe must be used when making gas connections to the unit. If local codes allow the use of a flexible gas appliance connection, always use a new listed con- nector. Do not use a connector that has previously serviced another gas appliance.

Some utility companies or local codes require pipe sizes larger than the minimum sizes listed in these instructions and in the codes. The furnace rating plate and the instructions in this section specify the type of gas approved for this furnace - only use those approved gases. The instal- lation of a drip leg and ground union is required. Refer to Figure 16.

To Gas

Supply

Ground

To Gas

NOTE: Ground Union maybe installed inside or outside unit.

 

Supply

 

External

 

 

 

 

 

Ground

 

External

 

Manual

To Gas

 

Union

 

Manual

Ground

Shut-off

 

Supply

 

 

 

 

 

 

Shut-off

 

Union

 

Valve

To Gas

 

 

 

 

Supply

 

To Gas

 

Valve

 

 

 

 

 

 

 

 

 

 

 

Supply

 

 

 

 

 

 

 

Union

Drip

Leg

Gas

Valve

Gas

Pipe

Drip

Leg Ground

Union

Gas

 

 

Pipe

Drip

 

Upflow

Leg

Downflow

Drip Leg

External Manual

GroundShut-off Valve

Union

Gas

Valve

 

Gas

Gas

 

 

To Gas

 

Valve

 

 

Drip

Pipe

 

 

Supply

 

 

 

 

 

Leg

 

 

 

 

Ground

 

 

 

 

 

 

Horizontal

Drip

 

Union

 

 

 

 

FIGURE 16: Gas Piping

An accessible manual shutoff valve must be installed upstream of the furnace gas controls and within 6 feet (1.8 m) of the furnace.

The furnace must be isolated from the gas supply piping system by closing its individual external manual shutoff valve during any pressure testing of the gas supply piping system at pressures equal to or less than 0.5 psig (3.5 kPa).

The gas valve body is a very thin casting that cannot take any exter- nal pressure. Never apply a pipe wrench to the body of the gas valve when installing piping. A wrench must be placed on the octagon hub located on the gas inlet side of the valve. Placing a wrench to the body of the gas valve will damage the valve causing improper opera- tion and/or the valve to leak.

Gas piping may be connected from either side of the furnace using any of the gas pipe entry knockouts on both sides of the furnace. Refer to Figure 13.

10

Johnson Controls Unitary Products

Image 10
Contents List of Figures Models TM9T*MPList of Sections List of TablesSpecific Safety Rules and Precautions Section I SafetySafety Requirements Combustion AIR Quality List of Contaminants Codes and StandardsInspection Furnace Location and ClearancesDuctwork General Information Floor Base and Ductwork Installation DownflowSection II Ductwork Duct FlangesFurnace Assembly MC & FC Series Coils Coil InstallationCOIL/FURNACE Assembly MC/FC/PC Series Coils Coil Flange Installation Bottom Return and Attic Installations Coil / Furnace Assembly HC Series Coils Downflow Duct Connectors Critical Coil ProjectionHorizontal Application Attic InstallationSuspended Furnace / Crawl Space Installation Downflow ApplicationSection III Filters Filter InstallationSide Return Section IV GAS Piping GAS SafetyGAS Piping Installation Horizontal FiltersElectrical Power Connections Section V Electrical PowerHigh Altitude Pressure Switch Conversion GAS Orifice Conversion for Propane LPLOW Voltage Control Wiring Connections Supply Voltage ConnectionsTwo Stage Air Conditioner Two Stage PSC Furnace PP32U70124 DN22H00124 DP22U70124TWO Stage PSC Furnace OD Models Section VI Twinning Condensate Drain Location Twinning InstructionsTwinning Operation Condensate hoses must slope downwards at all pointsCondensate Drain Termination Typical. Combustion Pipe Drain TeeWill cause the furnace Airflow Horizontal Left Right Configuration Johnson ControlsCombustion AIR/VENT Pipe Sizing Combustion AIR and Vent SafetySection Viii Combustion AIR and Vent System Model Input Pipe Size MaximumCombustion AIR / Venting Combustion AIR and Vent Piping AssemblyElbow a Dimension Fitting Equivalent LengthVent Clearances Home LayoutVent Applications and Termination Vent SystemVenting Multiple Units Combustion AIR Supply Downward VentingOutdoor Combustion Air Ambient Combustion Air SupplyAir Supply Openings and Ducts Combustion Air Source From OutdoorsDampers, Louvers and Grilles Canada Only Free AreaVentilated Combustion Air Termination Specially Engineered InstallationsVentilated Combustion Air Vent Blower RotationCalculating the Furnace Input NAT. GAS Section IX START-UP AdjustmentsGAS Piping Leak Check Ignition System SequenceRevolution Cu Ft Seconds ForRead the inlet gas pressure Adjustment of Manifold GAS Pressure & Input RateRead the manifold gas pressure Adjustment of Temperature Rise Adjustment of FAN Control SettingsBottom Airflow Data Scfm Blower Performance CFM Any Position without filterLeft Side Airflow Data Scfm Section X Safety Controls Section XI Normal Operation and DiagnosticsFurnace Control Diagnostics Diagnostic Fault Code Storage and Retrieval Section XII Replacement Parts ListFabricated Parts Section Xiii Wiring Diagram Wiring DiagramJohnson Controls Unitary Products York Drive Norman, OK