Johnson Controls TM9T*MP Vent System, Vent Applications and Termination, Venting Multiple Units

Page 25

505309-UIM-D-0511

VENT SYSTEM

This furnace is certified to be installed with one of two possible vent configurations.

1.Horizontal vent system. This vent system can be installed com- pletely horizontal or combinations of horizontal, vertical, or offset using elbows.

2.Vertical vent system. This vent system can be installed completely vertical or a combination of horizontal, vertical, or offset using elbows.

VENT APPLICATIONS AND TERMINATION

When selecting the location for a combustion air / vent termination, the following should be considered:

1.

Observe all clearances listed in vent clearances in these instruc-

 

tions.

2.

Termination should be positioned where vent vapors will not dam-

12” MIN.

12” MIN.

12” Minimum below overhang

12” Minimum separation between bottom of combustion air intake and bottom of vent

Maintain 12” minimumclearance above highest anticipated snow level or grade, whichever is higher

 

age plants or shrubs or air conditioning equipment.

3.

Termination should be located where it will not be affected by wind

 

gusts, light snow, airborne leaves or allow recirculation of flue

 

gases.

4.

Termination should be located where it will not be damaged or

 

exposed to flying stones, balls, etc.

5.

Termination should be positioned where vent vapors are not objec-

 

tionable.

6.

Horizontal portions of the vent system must slope upwards and be

 

supported to prevent sagging.

7.

Direct vent systems must be installed so the vent and the combus-

 

tion air pipes terminate in the same atmospheric zone. Refer to Fig-

 

ures 30 or 31.

Maintain 12” minimum clearance above highest anticipated snow level. Maximum 24” above roof.

12” Min.

12” Min.

FIGURE 30: Termination Configuration - 1 Pipe

FIGURE 32: Termination Configuration - 2 Pipe Basement

VENTING MULTIPLE UNITS

Multiple units can be installed in a space or structure as either a single pipe configuration or a two-pipe configuration.

The combustion air side of the single pipe configuration shown in Figure 30 is referred to in these instructions as ambient combustion air supply. Follow the instructions for ambient combustion air installations, paying particular attention to the section on air source from inside the building. The vent for a single pipe system must be installed as specified in the venting section of these instructions with the vent terminating as shown in Figure 30. Each furnace must have a separate vent pipe. Under NO circumstances can the two vent pipes be tied together.

The combustion air side of the two-pipe configuration shown in Figure 31 can be installed so the combustion air pipe terminates as described in outdoor combustion air or ventilated combustion air sections in these instructions. Follow the instructions for outdoor combustion air or venti- lated combustion air and the instructions for installing the vent system with the vent terminating as shown in Figures 33 or 34. The two-pipe system must have a separate combustion air pipe and a separate vent pipe for each furnace. Under NO circumstances can the two combus- tion air or vent pipes be tied together. The combustion air and vent pipes must terminate in the same atmospheric zone.

VENT

Maintain 12” minimum clearance above highest anticipated snow level.

12” vertical separation

 

between combustion air

12” minimum

intake and vent.

below overhang

 

 

12” minimum

 

separation between

 

bottom of

 

combustion air pipe

 

and bottom of vent.

 

Maintain 12”

 

minimum clearance

 

above highest

 

anticipated snow

 

level or grade,

 

whichever is higher.

COMBUSTION AIR

2”

MIN.

FIGURE 33: Double Horizontal Combustion Air Intake and Vent Termination

MIN.6”

FIGURE 31: Termination Configuration - 2 Pipe

FIGURE 34: Double Vertical Combustion Air Intake and Vent Termination

Johnson Controls Unitary Products

25

Image 25
Contents List of Sections Models TM9T*MPList of Figures List of TablesSpecific Safety Rules and Precautions Section I SafetySafety Requirements Codes and Standards Combustion AIR Quality List of ContaminantsFurnace Location and Clearances InspectionSection II Ductwork Floor Base and Ductwork Installation DownflowDuctwork General Information Duct FlangesCOIL/FURNACE Assembly MC/FC/PC Series Coils Coil InstallationFurnace Assembly MC & FC Series Coils Coil Flange InstallationDownflow Duct Connectors Coil / Furnace Assembly HC Series CoilsBottom Return and Attic Installations Critical Coil ProjectionSuspended Furnace / Crawl Space Installation Attic InstallationHorizontal Application Downflow ApplicationSection III Filters Filter InstallationSide Return GAS Piping Installation GAS SafetySection IV GAS Piping Horizontal FiltersHigh Altitude Pressure Switch Conversion Section V Electrical PowerElectrical Power Connections GAS Orifice Conversion for Propane LPSupply Voltage Connections LOW Voltage Control Wiring ConnectionsPP32U70124 DN22H00124 DP22U70124 Two Stage Air Conditioner Two Stage PSC FurnaceTWO Stage PSC Furnace OD Models Section VI Twinning Twinning Operation Twinning InstructionsCondensate Drain Location Condensate hoses must slope downwards at all pointsTypical. Combustion Pipe Drain Tee Condensate Drain TerminationWill cause the furnace Airflow Horizontal Left Johnson Controls Right ConfigurationSection Viii Combustion AIR and Vent System Combustion AIR and Vent SafetyCombustion AIR/VENT Pipe Sizing Model Input Pipe Size MaximumElbow a Dimension Combustion AIR and Vent Piping AssemblyCombustion AIR / Venting Fitting Equivalent LengthHome Layout Vent ClearancesVent Applications and Termination Vent SystemVenting Multiple Units Outdoor Combustion Air Downward VentingCombustion AIR Supply Ambient Combustion Air SupplyDampers, Louvers and Grilles Canada Only Combustion Air Source From OutdoorsAir Supply Openings and Ducts Free AreaVentilated Combustion Air Specially Engineered InstallationsVentilated Combustion Air Termination Vent Blower RotationGAS Piping Leak Check Section IX START-UP AdjustmentsCalculating the Furnace Input NAT. GAS Ignition System SequenceSeconds For Revolution Cu FtRead the inlet gas pressure Adjustment of Manifold GAS Pressure & Input RateRead the manifold gas pressure Adjustment of FAN Control Settings Adjustment of Temperature RiseBottom Airflow Data Scfm Blower Performance CFM Any Position without filterLeft Side Airflow Data Scfm Section XI Normal Operation and Diagnostics Section X Safety ControlsFurnace Control Diagnostics Diagnostic Fault Code Storage and Retrieval Section XII Replacement Parts ListFabricated Parts Wiring Diagram Section Xiii Wiring DiagramJohnson Controls Unitary Products York Drive Norman, OK

TM9T*MP specifications

Johnson Controls TM9T*MP is a state-of-the-art HVAC unit designed for modern commercial and residential applications. With its innovative technology and robust features, the TM9T*MP offers exceptional performance, efficiency, and reliability. This unit is engineered to provide optimal climate control, ensuring that indoor environments remain comfortable regardless of external weather conditions.

One of the main features of the TM9T*MP is its variable-speed compressor, which allows for precise temperature regulation and energy-efficient operation. This technology enables the unit to adjust its output based on the current demand, significantly reducing energy consumption compared to traditional systems. By operating at lower speeds during mild weather, the TM9T*MP minimizes energy costs while maintaining user comfort.

Another significant aspect of the TM9T*MP is its advanced multi-stage filtration system. This system includes a high-efficiency air filter capable of capturing a wide range of airborne particles, including dust, pollen, and allergens. This feature not only improves indoor air quality but also helps to promote a healthier living environment for occupants. Furthermore, the TM9T*MP is compatible with smart home technology, allowing users to monitor and control their HVAC system remotely through mobile devices or voice-controlled assistants.

The TM9T*MP also boasts a compact design, making it versatile for various installation environments. Its sleek profile allows for easy integration into existing spaces without requiring extensive modifications. Durability is another hallmark of this unit, as it is built with high-quality materials designed to withstand the rigors of daily use while providing long-lasting performance.

Additionally, the TM9T*MP incorporates advanced diagnostics and troubleshooting capabilities. This feature simplifies maintenance by alerting technicians to potential issues before they escalate, ensuring smooth operation and reducing downtime. Moreover, with a user-friendly interface, occupants can easily adjust settings, access energy usage data, and schedule maintenance reminders for peak performance.

In summary, Johnson Controls TM9T*MP sets a new standard in HVAC technology with its variable-speed compressor, multi-stage filtration, compact design, and smart capabilities. Committed to energy efficiency and indoor air quality, it promises to deliver comfort and sustainability in every setting.