Johnson Controls TM9T*MP installation manual Furnace Control Diagnostics

Page 35

505309-UIM-D-0511

FURNACE CONTROL DIAGNOSTICS

The furnace has built-in, self-diagnostic capability. A blinking LED light on the control board can flash red, green or amber to indicate various conditions. The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED light will indicate the failure code.

The SLOW flash speed is two seconds on and two seconds off.

The other flash codes listed below have the following timing: LED light will turn on for 1/3 second and off for 1/3 second. This pattern will be repeated the number of times equal to the code. There will be a two- second pause between codes. For example, the six red flash code will flash the LED light on and off six times, then will be off for two seconds. This pattern will repeat as long as the fault condition remains. The con- tinuous flash codes listed below will flash the LED light on and off con- tinuously, with no breaks or longer pauses.

SLOW GREEN FLASH: Normal operation, no thermostat calls.

SLOW AMBER FLASH: Normal operation with call for heat.

LED STEADY OFF – If the LED light does not flash at all, check for power to the board and check for a blown fuse on the board. If the board is properly powered and the fuse is not blown, the control board may need to be replaced.

STEADY ON ANY COLOR: Control failure. Turn power to the furnace off and back on. If the fault code returns, the control board must be replaced. The control board is not field-repairable.

CONTINUOUS RED FLASH: Twinning error, incorrect 24V phasing or no power to twinned unit. Check twinning wiring. Confirm that both twinned units have power.

CONTINUOUS AMBER FLASH: Flame sense current is below 1.5 microamps. Check and clean flame sensor. Check for proper gas flow. Verify that current is greater than 1.5 microamps at flame current test pad.

1 RED FLASH: This indicates that flame was sensed when there was not a call for heat. The control will turn on both the inducer motor and supply air blower. Check for a leaking or slow-closing gas valve.

2 RED FLASHES: This indicates that the pressure switch is closed when it should be open. The control confirms that the pressure switch contacts are open at the beginning of each heat cycle and will not let the ignition sequence continue if the pressure switch contacts are closed when they should be open. Check for a faulty pressure switch or miswiring.

3 RED FLASHES: This indicates the pressure switch contacts are open when they should be closed. Check for faulty inducer, blocked vent pipe, broken pressure switch hose, disconnected pressure switch or inducer wires or faulty pressure switch.

4 RED FLASHES: This indicates that the main limit switch has opened its normally closed contacts. The control will turn on the supply air blower and inducer. Check for a dirty filter, improperly sized duct sys- tem, incorrect blower speed setting, incorrect firing rate, loose limit switch wiring or faulty blower motor.

If the limit switch has not closed within five minutes, the control will assume that the blower is not functioning, will start a hard lockout and will begin to flash the 11 Red Flashes error code. If, after fifteen min- utes, the main limit still has not closed, the control will assume that a manual-reset rollout switch has opened and will begin to flash the 5 Red Flash error code. See the description of “5 Red Flashes” and “11Red Flashes” below.

If the main limit switch opens five times within a single call for heat, the control will indicate 4 Red Flashes and will enter a one-hour soft lock- out.

5 RED FLASHES: This fault is indicated if the limit circuit is open for more than fifteen minutes, usually indicating that a manual-reset rollout switch has opened. Check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. The control will enter a hard lockout and power will have to be cycled off and on to reset the control after the problem has been corrected.

6 RED FLASHES: This indicates that while the unit was operating, the pressure switch opened four times during the call for heat. Check for faulty inducer, blocked vent pipe or faulty pressure switch. The furnace will lock out for one hour and then restart.

7 RED FLASHES: This fault code indicates that the flame could not be established during three trials for ignition. Check that the gas valve switch is in the ON position. Check for low or no gas pressure, faulty gas valve, dirty or faulty flame sensor, faulty hot surface ignitor, loose wires or a burner problem. The furnace will lock out for one hour and then restart.

8 RED FLASHES: This fault is indicated if the flame is lost five times (four recycles) during the heating cycle. Check for low gas pressure, dirty or faulty flame sensor or faulty gas valve. The furnace will lock out for one hour and then restart.

9 RED FLASHES: Indicates reversed line voltage polarity, grounding problem or reversed low voltage transformer wires. Both heating and cooling operations will be affected. Check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis. The furnace will not start the ignition sequence until this problem is corrected.

10 RED FLASHES: Gas valve energized with no call for heat. The main blower and inducer blower will run and no ignition sequence will be started as long as this condition exists. Check gas valve and gas valve wiring.

11 RED FLASHES: This indicates that the limit circuit has remained open for more than five minutes and less than fifteen minutes. This con- dition is usually caused by a failed blower motor or blower wheel. The control will enter a hard lockout and power will have to be cycled off and on to reset the control after the problem has been corrected.

4 AMBER FLASHES: The control is receiving a “Y” signal from the thermostat without a “G” signal. The furnace will operate normally in both heating and cooling, but this fault code will be displayed in order to alert the user that there is a wiring problem. Verify that the “G” wire from the thermostat is connected properly.

SOFT LOCKOUT: This control includes a soft lockout that will reset automatically after one hour. This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example of this is a temporary interruption in gas supply that would prevent the furnace from lighting. The control will keep trying to light each hour and will resume normal operation if the gas supply is restored.

HARD LOCKOUT: Some fault conditions result in a hard lockout, which requires power to the control to be turned off and then back on to reset the control. The control will not automatically restart.

IGNITION CONTROL FLAME SENSE LEVELS Normal flame sense current is approximately 3.7 microamps DC (µa)

Low flame signal warning starts at 1.5 microamps.

Low flame signal control lockout point is

0.1 microamps DC (µa)

Johnson Controls Unitary Products

35

Image 35
Contents List of Tables Models TM9T*MPList of Sections List of FiguresSafety Requirements Section I SafetySpecific Safety Rules and Precautions Codes and Standards Combustion AIR Quality List of ContaminantsFurnace Location and Clearances InspectionDuct Flanges Floor Base and Ductwork Installation DownflowSection II Ductwork Ductwork General InformationCoil Flange Installation Coil InstallationCOIL/FURNACE Assembly MC/FC/PC Series Coils Furnace Assembly MC & FC Series CoilsCritical Coil Projection Coil / Furnace Assembly HC Series CoilsDownflow Duct Connectors Bottom Return and Attic InstallationsDownflow Application Attic InstallationSuspended Furnace / Crawl Space Installation Horizontal ApplicationSide Return Filter InstallationSection III Filters Horizontal Filters GAS SafetyGAS Piping Installation Section IV GAS PipingGAS Orifice Conversion for Propane LP Section V Electrical PowerHigh Altitude Pressure Switch Conversion Electrical Power ConnectionsSupply Voltage Connections LOW Voltage Control Wiring ConnectionsPP32U70124 DN22H00124 DP22U70124 Two Stage Air Conditioner Two Stage PSC FurnaceTWO Stage PSC Furnace OD Models Section VI Twinning Condensate hoses must slope downwards at all points Twinning InstructionsTwinning Operation Condensate Drain LocationTypical. Combustion Pipe Drain Tee Condensate Drain TerminationWill cause the furnace Airflow Horizontal Left Johnson Controls Right ConfigurationModel Input Pipe Size Maximum Combustion AIR and Vent SafetySection Viii Combustion AIR and Vent System Combustion AIR/VENT Pipe SizingFitting Equivalent Length Combustion AIR and Vent Piping AssemblyElbow a Dimension Combustion AIR / VentingHome Layout Vent ClearancesVenting Multiple Units Vent SystemVent Applications and Termination Ambient Combustion Air Supply Downward VentingOutdoor Combustion Air Combustion AIR SupplyFree Area Combustion Air Source From OutdoorsDampers, Louvers and Grilles Canada Only Air Supply Openings and DuctsVent Blower Rotation Specially Engineered InstallationsVentilated Combustion Air Ventilated Combustion Air TerminationIgnition System Sequence Section IX START-UP AdjustmentsGAS Piping Leak Check Calculating the Furnace Input NAT. GASSeconds For Revolution Cu FtRead the manifold gas pressure Adjustment of Manifold GAS Pressure & Input RateRead the inlet gas pressure Adjustment of FAN Control Settings Adjustment of Temperature RiseLeft Side Airflow Data Scfm Blower Performance CFM Any Position without filterBottom Airflow Data Scfm Section XI Normal Operation and Diagnostics Section X Safety ControlsFurnace Control Diagnostics Fabricated Parts Section XII Replacement Parts ListDiagnostic Fault Code Storage and Retrieval Wiring Diagram Section Xiii Wiring DiagramJohnson Controls Unitary Products York Drive Norman, OK