Johnson Controls TM9T*MP installation manual Blower Performance CFM Any Position without filter

Page 33

505309-UIM-D-0511

Blower Performance CFM - Any Position (without filter)

Bottom Airflow Data (SCFM)

Models

Speed

 

 

 

Ext. Static Pressure (in. H2O)

 

 

 

 

 

 

 

 

 

 

 

 

 

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

1492

1442

1378

1325

1243

1176

1075

966

849

655

060B12MP11

Medium High

1236

1201

1161

1139

1082

1011

919

830

715

590

Medium Low

986

950

961

916

872

831

757

703

600

510

 

 

Low

824

795

783

744

713

659

624

554

489

389

 

High

1597

1537

1484

1435

1370

1286

1230

1155

1075

925

080B12MP11

Medium High

1338

1307

1273

1223

1179

1123

1065

998

928

812

Medium Low

1113

1094

1077

1043

1008

972

924

868

803

798

 

 

Low

937

916

900

877

854

817

775

718

639

560

 

High

1919

1865

1802

1738

1671

1600

1517

1414

1322

1201

080C16MP11

Medium High

1532

1533

1513

1499

1465

1416

1352

1283

1198

1084

Medium Low

1232

1313

1291

1280

1250

1209

1207

1148

1055

937

 

 

Low

826

821

853

858

838

817

794

776

760

711

 

High

1909

1880

1823

1776

1706

1637

1562

1474

1375

1252

100C16MP11

Medium High

1465

1463

1469

1485

1477

1416

1386

1324

1250

1114

Medium

1190

1222

1216

1215

1224

1189

1158

1145

1087

996

 

 

Low

787

834

819

836

819

810

790

761

690

707

 

High

2284

2205

2114

2021

1934

1848

1752

1653

1505

1397

100C20MP11

Medium High

1967

1905

1824

1763

1712

1628

1551

1473

1379

1213

Medium Low

1610

1563

1513

1480

1430

1367

1319

1261

1101

1012

 

 

Low

1326

1304

1267

1232

1183

1143

1080

1003

871

798

 

High

2341

2245

2153

2072

1977

1876

1769

1642

1506

1306

120D20MP11

Medium High

2002

1952

1878

1823

1739

1657

1563

1458

1322

1185

Medium Low

1615

1579

1533

1473

1430

1368

1282

1186

1091

953

 

 

Low

1352

1295

1259

1245

1190

1141

1076

998

938

820

 

 

 

Left Side Airflow Data (SCFM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models

Speed

 

 

 

Ext. Static Pressure (in. H2O)

 

 

 

 

 

 

 

 

 

 

 

 

 

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

1470

1406

1361

1309

1241

1155

1060

920

775

628

060B12MP11

Medium High

1211

1186

1139

1101

1042

980

896

796

681

545

Medium Low

970

957

927

889

853

796

745

660

568

450

 

 

Low

793

781

756

724

694

653

585

530

469

382

 

High

1605

1562

1514

1454

1393

1330

1251

1169

1073

940

080B12MP11

Medium High

1372

1318

1280

1255

1205

1161

1093

1023

943

849

Medium Low

1087

1073

1052

1003

993

953

897

843

775

709

 

 

Low

916

896

881

854

831

802

757

708

642

574

 

High

1956

1907

1846

1778

1717

1647

1573

1483

1353

1209

080C16MP11

Medium High

1543

1543

1516

1504

1477

1446

1382

1309

1202

1099

Medium Low

1238

1241

1243

1241

1252

1242

1201

1140

1074

967

 

 

Low

906

902

903

910

888

866

859

829

795

743

 

High

1828

1829

1789

1768

1727

1671

1601

1505

1390

1272

100C16MP11

Medium High

1422

1444

1437

1424

1396

1326

1301

1253

1200

1100

Medium

1224

1229

1243

1234

1219

1193

1168

1135

1088

977

 

 

Low

813

819

818

814

783

762

756

732

690

642

 

High

2391

2286

2165

2079

2004

1934

1839

1692

1560

1366

100C20MP11

Medium High

1945

1878

1838

1782

1694

1642

1565

1451

1334

1163

Medium Low

1549

1530

1495

1430

1431

1365

1284

1192

1097

1022

 

 

Low

1256

1229

1189

1159

1089

1033

1008

950

871

784

 

High

2343

2253

2167

2071

1979

1881

1785

1668

1473

1351

120D20MP11

Medium High

1954

1892

1846

1781

1714

1637

1548

1429

1238

1171

Medium Low

1596

1539

1511

1458

1399

1341

1254

1180

942

988

 

 

Low

1299

1261

1229

1177

1111

1053

993

937

882

782

NOTES:

1.Airflow expressed in standard cubic feet per minute (CFM). 2.Return air is through side opposite motor (left side). 3.Motor voltage at 115 V.

4.Airflow through across motor side (right side) may be slightly less than the data shown above.

Johnson Controls Unitary Products

33

Image 33
Contents List of Sections Models TM9T*MPList of Figures List of TablesSection I Safety Specific Safety Rules and PrecautionsSafety Requirements Codes and Standards Combustion AIR Quality List of ContaminantsFurnace Location and Clearances InspectionSection II Ductwork Floor Base and Ductwork Installation DownflowDuctwork General Information Duct FlangesCOIL/FURNACE Assembly MC/FC/PC Series Coils Coil InstallationFurnace Assembly MC & FC Series Coils Coil Flange InstallationDownflow Duct Connectors Coil / Furnace Assembly HC Series CoilsBottom Return and Attic Installations Critical Coil ProjectionSuspended Furnace / Crawl Space Installation Attic InstallationHorizontal Application Downflow ApplicationFilter Installation Section III FiltersSide Return GAS Piping Installation GAS SafetySection IV GAS Piping Horizontal FiltersHigh Altitude Pressure Switch Conversion Section V Electrical PowerElectrical Power Connections GAS Orifice Conversion for Propane LPSupply Voltage Connections LOW Voltage Control Wiring ConnectionsPP32U70124 DN22H00124 DP22U70124 Two Stage Air Conditioner Two Stage PSC FurnaceTWO Stage PSC Furnace OD Models Section VI Twinning Twinning Operation Twinning InstructionsCondensate Drain Location Condensate hoses must slope downwards at all pointsTypical. Combustion Pipe Drain Tee Condensate Drain TerminationWill cause the furnace Airflow Horizontal Left Johnson Controls Right ConfigurationSection Viii Combustion AIR and Vent System Combustion AIR and Vent SafetyCombustion AIR/VENT Pipe Sizing Model Input Pipe Size MaximumElbow a Dimension Combustion AIR and Vent Piping AssemblyCombustion AIR / Venting Fitting Equivalent LengthHome Layout Vent ClearancesVent System Vent Applications and TerminationVenting Multiple Units Outdoor Combustion Air Downward VentingCombustion AIR Supply Ambient Combustion Air SupplyDampers, Louvers and Grilles Canada Only Combustion Air Source From OutdoorsAir Supply Openings and Ducts Free AreaVentilated Combustion Air Specially Engineered InstallationsVentilated Combustion Air Termination Vent Blower RotationGAS Piping Leak Check Section IX START-UP AdjustmentsCalculating the Furnace Input NAT. GAS Ignition System SequenceSeconds For Revolution Cu FtAdjustment of Manifold GAS Pressure & Input Rate Read the inlet gas pressureRead the manifold gas pressure Adjustment of FAN Control Settings Adjustment of Temperature RiseBlower Performance CFM Any Position without filter Bottom Airflow Data ScfmLeft Side Airflow Data Scfm Section XI Normal Operation and Diagnostics Section X Safety ControlsFurnace Control Diagnostics Section XII Replacement Parts List Diagnostic Fault Code Storage and RetrievalFabricated Parts Wiring Diagram Section Xiii Wiring DiagramJohnson Controls Unitary Products York Drive Norman, OK

TM9T*MP specifications

Johnson Controls TM9T*MP is a state-of-the-art HVAC unit designed for modern commercial and residential applications. With its innovative technology and robust features, the TM9T*MP offers exceptional performance, efficiency, and reliability. This unit is engineered to provide optimal climate control, ensuring that indoor environments remain comfortable regardless of external weather conditions.

One of the main features of the TM9T*MP is its variable-speed compressor, which allows for precise temperature regulation and energy-efficient operation. This technology enables the unit to adjust its output based on the current demand, significantly reducing energy consumption compared to traditional systems. By operating at lower speeds during mild weather, the TM9T*MP minimizes energy costs while maintaining user comfort.

Another significant aspect of the TM9T*MP is its advanced multi-stage filtration system. This system includes a high-efficiency air filter capable of capturing a wide range of airborne particles, including dust, pollen, and allergens. This feature not only improves indoor air quality but also helps to promote a healthier living environment for occupants. Furthermore, the TM9T*MP is compatible with smart home technology, allowing users to monitor and control their HVAC system remotely through mobile devices or voice-controlled assistants.

The TM9T*MP also boasts a compact design, making it versatile for various installation environments. Its sleek profile allows for easy integration into existing spaces without requiring extensive modifications. Durability is another hallmark of this unit, as it is built with high-quality materials designed to withstand the rigors of daily use while providing long-lasting performance.

Additionally, the TM9T*MP incorporates advanced diagnostics and troubleshooting capabilities. This feature simplifies maintenance by alerting technicians to potential issues before they escalate, ensuring smooth operation and reducing downtime. Moreover, with a user-friendly interface, occupants can easily adjust settings, access energy usage data, and schedule maintenance reminders for peak performance.

In summary, Johnson Controls TM9T*MP sets a new standard in HVAC technology with its variable-speed compressor, multi-stage filtration, compact design, and smart capabilities. Committed to energy efficiency and indoor air quality, it promises to deliver comfort and sustainability in every setting.