Johnson Controls TM9T*MP installation manual Vent Clearances, Home Layout

Page 24

505309-UIM-D-0511

VENT CLEARANCES

D

 

FIXED

 

E

CLOSED

V

 

 

 

 

 

L

V

B

 

C

 

 

 

 

 

 

V

 

 

F

V

 

 

 

 

 

B

 

FIGURE 29: Home Layout

G

V

A

H

B B

BI

 

V

M

V

X

 

 

 

 

V

 

B

J

 

 

 

OPERABLE

X

V

K

FIXED CLOSED

VVENT TERMINAL

XAIR SUPPLY

AREA WHERE TERMINAL IS NOT PERMITTED

Direct Vent Terminal Clearances

Canadian Installations1,3

US Installation2,3

A. Clearance above grade, veranda, porch, deck, or

12” (30.5 cm)

12” (30.5 cm)

 

balcony

 

 

B. Clearance to window or door that may be opened

12” (30.5 cm) for models 100,000 BTUH (30 kW),

Two-pipe (direct vent) applications: 12” (30.5 cm)††

36” (91.4 cm) for models >100,000 BTUH (30 kW).

Single-pipe applications: 4 feet (1.2 m).

 

 

 

 

 

C. Clearance to permanently closed window

12” (30.5 cm)

12” (30.5 cm)

 

 

 

D. Vertical clearance to ventilated soffit located

12” (30.5 cm) or in accordance with local installation

12” (30.5 cm) or in accordance with local installation

 

above the terminal within a horizontal distance

 

codes and the requirements of the gas supplier.

codes and the requirements of the gas supplier.

 

of 2 feet (61 cm) from the center line of the terminal

 

 

 

 

E. Clearance to unventilated soffit

12” (30.5 cm) or in accordance with local installation

12” (30.5 cm) or in accordance with local installation

codes and the requirements of the gas supplier.

codes and the requirements of the gas supplier.

 

 

 

 

 

 

F.

Clearance to outside corner

12” (30.5 cm) or in accordance with local installation

12” (30.5 cm) or in accordance with local installation

codes and the requirements of the gas supplier.

codes and the requirements of the gas supplier.

 

 

G. Clearance to inside corner

3 feet (91.4 cm)

3 feet (91.4 cm)

 

 

 

 

H. Clearance to each side of center line

Above a meter/regulator assembly within 3 feet

Above a meter/regulator assembly within 3 feet

(91.4 cm) horizontally of the vertical center-line of the

(91 cm) horizontally of the vertical center-line of the

 

extended above meter/regulator assembly

regulator vent outlet to a maximum vertical distance of

regulator vent outlet to a maximum vertical distance of

 

 

15 feet (4.5 m) above the meter/regulator assembly.

15 feet (4.5 m) above the meter/regulator assembly.

 

 

 

 

I.

Clearance to service regulator vent outlet

3 feet (91.4 cm)

3 feet (91.4 cm) or in accordance with local installation

codes and the requirements of the gas supplier.

 

 

 

 

 

 

J. Clearance to non-mechanical air supply inlet to

12” (30.5 cm) for models 100,000 BTUH (30 kW),

Two-pipe (direct vent) applications: 12” (30.5 cm)

 

building or the combustion air inlet to any other

 

appliance

36” (91 cm) for models >100,000 BTUH (30 kW).

Single-pipe applications: 4 feet (1.2 m).

 

 

 

 

 

 

 

K. Clearance to a mechanical supply inlet

6 feet (1.83 m)

3 feet (91.4 cm) above if within 10 feet (3 m)

horizontally.

 

 

 

L.

Clearance above paved sidewalk or paved

7 feet (2.13 m)†

7 feet (2.13 m) or in accordance with local installation

 

driveway located on public property

codes and the requirements of the gas supplier.

 

 

 

 

 

 

M. Clearance under veranda, porch, deck, or balcony

12” (30.5 cm)‡

12” (30.5 cm) or in accordance with local installation

codes and the requirements of the gas supplier.

 

 

 

 

 

 

 

1.In accordance with the current CSA B149.1-00, Natural Gas and Propane Installation Code.

2.In accordance with the current ANSI Z223.1 / NFPA 54, National Gas Code.

3.In accordance with the current ANSI Z21.47 * CSA 2.3 American National Standard.

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. †† 12” (30.5 cm) up from the bottom edge of the structure for Two-pipe (direct vent) applications per ANSI Z223.1 / NFPA 54, National Gas Code.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and the distance between the top of the vent termina- tion and the underside of the veranda, porch, or deck is greater than 12” (30.5 cm) as specified in CSA B149.1-00.

A vent shall not terminate less than 12” (30.5 cm) above a grade level.

Any fresh air or make up inlet for dryer or furnace area is considered to be forced air inlet.

Avoid areas where condensate drippage may cause problems such as above planters, patios, or adjacent to windows where steam may cause fogging.

A terminus of a vent shall be fitted with a cap in accordance with the vent manufacturer’s installation instructions, or in accordance with the installation instructions for a special venting system.

Responsibility for the provision of proper adequate venting and air supply for application shall rest with the installer.

Vent shall extend high enough above building, or a neighboring obstruction, so that wind from any direction will not create a positive pressure in the vicinity of the vent.

Consideration must be given for degradation of building materials by flue gases. Sidewall termination may require sealing or shielding of building surfaces with a corrosion resistant material to protect against combustion product corrosion. Consideration must be given to wind direction in order to prevent flue products and/or condensate from being blown against the building surfaces. If a metal shield is used it must be a stainless steel material at a minimum dimension of 20 inches (51 cm). It is recommended that a retaining type collar be used that is attached to the building sur- face to prevent movement of the vent pipe.

24

Johnson Controls Unitary Products

Image 24
Contents Models TM9T*MP List of SectionsList of Figures List of TablesSection I Safety Specific Safety Rules and PrecautionsSafety Requirements Combustion AIR Quality List of Contaminants Codes and StandardsInspection Furnace Location and ClearancesFloor Base and Ductwork Installation Downflow Section II DuctworkDuctwork General Information Duct FlangesCoil Installation COIL/FURNACE Assembly MC/FC/PC Series CoilsFurnace Assembly MC & FC Series Coils Coil Flange InstallationCoil / Furnace Assembly HC Series Coils Downflow Duct ConnectorsBottom Return and Attic Installations Critical Coil ProjectionAttic Installation Suspended Furnace / Crawl Space InstallationHorizontal Application Downflow ApplicationFilter Installation Section III FiltersSide Return GAS Safety GAS Piping InstallationSection IV GAS Piping Horizontal FiltersSection V Electrical Power High Altitude Pressure Switch ConversionElectrical Power Connections GAS Orifice Conversion for Propane LPLOW Voltage Control Wiring Connections Supply Voltage ConnectionsTwo Stage Air Conditioner Two Stage PSC Furnace PP32U70124 DN22H00124 DP22U70124TWO Stage PSC Furnace OD Models Section VI Twinning Twinning Instructions Twinning OperationCondensate Drain Location Condensate hoses must slope downwards at all pointsCondensate Drain Termination Typical. Combustion Pipe Drain TeeWill cause the furnace Airflow Horizontal Left Right Configuration Johnson ControlsCombustion AIR and Vent Safety Section Viii Combustion AIR and Vent SystemCombustion AIR/VENT Pipe Sizing Model Input Pipe Size MaximumCombustion AIR and Vent Piping Assembly Elbow a DimensionCombustion AIR / Venting Fitting Equivalent LengthVent Clearances Home LayoutVent System Vent Applications and TerminationVenting Multiple Units Downward Venting Outdoor Combustion AirCombustion AIR Supply Ambient Combustion Air SupplyCombustion Air Source From Outdoors Dampers, Louvers and Grilles Canada OnlyAir Supply Openings and Ducts Free AreaSpecially Engineered Installations Ventilated Combustion AirVentilated Combustion Air Termination Vent Blower RotationSection IX START-UP Adjustments GAS Piping Leak CheckCalculating the Furnace Input NAT. GAS Ignition System SequenceRevolution Cu Ft Seconds ForAdjustment of Manifold GAS Pressure & Input Rate Read the inlet gas pressureRead the manifold gas pressure Adjustment of Temperature Rise Adjustment of FAN Control SettingsBlower Performance CFM Any Position without filter Bottom Airflow Data ScfmLeft Side Airflow Data Scfm Section X Safety Controls Section XI Normal Operation and DiagnosticsFurnace Control Diagnostics Section XII Replacement Parts List Diagnostic Fault Code Storage and RetrievalFabricated Parts Section Xiii Wiring Diagram Wiring DiagramJohnson Controls Unitary Products York Drive Norman, OK