Johnson Controls TM9T*MP Combustion Air Source From Outdoors, Air Supply Openings and Ducts

Page 27

505309-UIM-D-0511

This type of installation requires that the supply air to the appliance(s) be of a sufficient amount to support all of the appliance(s) in the area. Operation of a mechanical exhaust, such as an exhaust fan, kitchen ventilation system, clothes dryer or fireplace may create conditions requiring special attention to avoid unsatisfactory operation of gas appliances. A venting problem or a lack of supply air will result in a hazardous condition, which can cause the appliance to soot and gen- erate dangerous levels of CARBON MONOXIDE, which can lead to serious injury, property damage and / or death.

An unconfined space is not less than 50 cu.ft (1.42 m3) per 1,000 Btu/ hr (0.293 kW/h) input rating for all of the appliances installed in that area.

Rooms communicating directly with the space containing the appli- ances are considered part of the unconfined space, if doors are fur- nished with openings or louvers.

A confined space is an area with less than 50 cu.ft (1.42 m3) per 1,000 Btu/hr (0.293 kW/h) input rating for all of the appliances installed in that area. The following must be considered to obtain proper air for combus- tion and ventilation in confined spaces.

Combustion Air Source From Outdoors

The blocking effects of louvers, grilles and screens must be given con- sideration in calculating free area. If the free area of a specific louver or grille is not known, refer to Table 12, to estimate free area.

Table 12: Estimated Free Area

Wood or Metal

Wood 20-25%*

Louvers or Grilles

Metal 60-70% *

Screens+

1/4” (6.4 mm)

mesh or larger 100%

 

* Do not use less than 1/4” (6.4 mm) mesh

+Free area of louvers and grille varies widely; the installer should follow louver or grille manufacturer’s instructions.

Dampers, Louvers and Grilles (Canada Only)

1.The free area of a supply air opening shall be calculated by sub- tracting the blockage area of all fixed louvers grilles or screens from the gross area of the opening.

2.Apertures in a fixed louver, a grille, or screen shall have no dimen- sion smaller than 1/4” (6.4 mm).

3.A manually operated damper or manually adjustable louvers are not permitted for use.

4.A automatically operated damper or automatically adjustable lou- vers shall be interlocked so that the main burner cannot operate unless either the damper or the louver is in the fully open position.

When a Category I furnace is removed or replaced, the original vent- ing system may no longer be correctly sized to properly vent the attached appliances.

An improperly sized vent system can cause CARBON MONOXIDE to spill into the living space causing personal injury, and or death.

Table 13: Unconfined Space Minimum Area

BTUH Input Rating

Minimum Free Area Required for Each Opening

 

60,000

 

 

 

60 in2 (387 cm2)

 

 

80,000

 

 

 

80 in2 (516 cm2)

 

 

100,000

 

 

100 in2 (645 cm2)

 

 

120,000

 

 

120 in2 (742 cm2)

 

 

Table 14: Free Area

 

 

 

 

 

 

 

 

 

 

 

Minimum Free Area Required for Each Opening

 

BTUH Input

 

Horizontal Duct

Vertical Duct or

Round Duct

 

Rating

 

 

Opening to Outside

 

 

 

(2,000 BTUH)

(4,000 BTUH)

 

 

 

 

 

 

(4,000 BTUH)

 

 

60,000

 

 

30 in2 (193 cm2)

15 in2 (97 cm2)

5” (13 cm)

 

80,000

 

 

40 in2 (258 cm2)

20 in2 (129 cm2)

5” (13 cm)

 

100,000

 

 

50 in2 (322 cm2)

25 in2 (161 cm2)

6” (15 cm)

 

120,000

 

 

60 in2 (387 cm2)

30 in2 (193 cm2)

7” (18 cm)

 

EXAMPLE:

Determining Free Area.

 

 

 

Appliance

 

 

1 Appliance

2 Total Input

 

 

100,000

+

 

30,000 = (130,000 ÷ 4,000) = 32.5 Sq. In. Vertical

 

Appliance

 

 

1 Appliance

2 Total Input

 

 

100,000

+

 

30,000 = (130,000 ÷ 2,000) = 65 Sq. In. Horizontal

 

 

 

Gas

Gable

 

Vent

Vent

Ventilated

 

 

 

Optional

Attic

 

Top Above

 

Inlet (a)

 

Insulation

 

 

 

Soffit

Outlet

 

Vent

Air (a)

rnaceuF

 

Gas

 

 

 

Water

 

 

Heater

 

 

Ventilated

 

 

Crawl Space

 

 

 

Gas

 

 

 

 

Gable

Vent

 

 

 

 

 

 

 

 

 

Vent

 

 

 

 

 

Ventilated

 

 

 

 

 

Attic

 

 

 

 

 

Top Above

 

 

 

 

 

Insulation

 

 

 

 

Soffit

 

 

 

Outlet

 

Vent

 

 

 

 

 

 

 

Air (b)

 

 

 

 

 

 

 

Heater

Furnace

Inlet

Inlet

Heater

 

Gas

 

 

 

Gas

Inlet

Water

 

 

 

Water

 

 

 

 

 

Air (b)

 

 

Air (a)

Air (b)

 

Gas

Vent

 

Outlet

 

Air (a)

Furnace

Inlet

 

 

Air (a)

FIGURE 38: Outside and Ambient Combustion Air

Air Supply Openings and Ducts

1.An opening may be used in lieu of a duct to provide to provide the outside air supply to an appliance unless otherwise permitted by the authority having jurisdiction. The opening shall be located within 12” (30.5 cm) horizontally from, the burner level of the appliance. Refer to “AIR SOURCE FROM OUTDOORS AND VENT AND SUPPLY AIR SAFETY CHECK” in these instructions for additional informa- tion and safety check procedure.

2.The duct shall be either metal, or a material meeting the class 1 requirements of CAN4-S110 Standard for Air Ducts.

3.The duct shall be least the same cross-sectional area as the free area of the air supply inlet opening to which it connects.

4.The duct shall terminate within 12” (30.5 cm) above, and within 24” (61 cm) horizontally from, the burner level of the appliance having the largest input.

5.A square or rectangular shaped duct shall only be used when the required free area of the supply opening is 9 in2 (58.06 cm2) or larger. When a square or rectangular duct is used, its small dimen- sion shall not be less than 3” (7.6 cm).

6.An air inlet supply from outdoors shall be equipped with a means to prevent the direct entry of rain and wind. Such means shall not reduce the required free area of the air supply opening.

7.An air supply inlet opening from the outdoors shall be located not less than 12” (30.5 cm) above the outside grade level.

Johnson Controls Unitary Products

27

Image 27
Contents List of Tables Models TM9T*MPList of Sections List of FiguresSection I Safety Specific Safety Rules and PrecautionsSafety Requirements Codes and Standards Combustion AIR Quality List of ContaminantsFurnace Location and Clearances InspectionDuct Flanges Floor Base and Ductwork Installation DownflowSection II Ductwork Ductwork General InformationCoil Flange Installation Coil InstallationCOIL/FURNACE Assembly MC/FC/PC Series Coils Furnace Assembly MC & FC Series CoilsCritical Coil Projection Coil / Furnace Assembly HC Series CoilsDownflow Duct Connectors Bottom Return and Attic InstallationsDownflow Application Attic InstallationSuspended Furnace / Crawl Space Installation Horizontal ApplicationFilter Installation Section III FiltersSide Return Horizontal Filters GAS SafetyGAS Piping Installation Section IV GAS PipingGAS Orifice Conversion for Propane LP Section V Electrical PowerHigh Altitude Pressure Switch Conversion Electrical Power ConnectionsSupply Voltage Connections LOW Voltage Control Wiring ConnectionsPP32U70124 DN22H00124 DP22U70124 Two Stage Air Conditioner Two Stage PSC FurnaceTWO Stage PSC Furnace OD Models Section VI Twinning Condensate hoses must slope downwards at all points Twinning InstructionsTwinning Operation Condensate Drain LocationTypical. Combustion Pipe Drain Tee Condensate Drain TerminationWill cause the furnace Airflow Horizontal Left Johnson Controls Right ConfigurationModel Input Pipe Size Maximum Combustion AIR and Vent SafetySection Viii Combustion AIR and Vent System Combustion AIR/VENT Pipe SizingFitting Equivalent Length Combustion AIR and Vent Piping AssemblyElbow a Dimension Combustion AIR / VentingHome Layout Vent ClearancesVent System Vent Applications and TerminationVenting Multiple Units Ambient Combustion Air Supply Downward VentingOutdoor Combustion Air Combustion AIR SupplyFree Area Combustion Air Source From OutdoorsDampers, Louvers and Grilles Canada Only Air Supply Openings and DuctsVent Blower Rotation Specially Engineered InstallationsVentilated Combustion Air Ventilated Combustion Air TerminationIgnition System Sequence Section IX START-UP AdjustmentsGAS Piping Leak Check Calculating the Furnace Input NAT. GASSeconds For Revolution Cu FtAdjustment of Manifold GAS Pressure & Input Rate Read the inlet gas pressureRead the manifold gas pressure Adjustment of FAN Control Settings Adjustment of Temperature RiseBlower Performance CFM Any Position without filter Bottom Airflow Data ScfmLeft Side Airflow Data Scfm Section XI Normal Operation and Diagnostics Section X Safety ControlsFurnace Control Diagnostics Section XII Replacement Parts List Diagnostic Fault Code Storage and RetrievalFabricated Parts Wiring Diagram Section Xiii Wiring DiagramJohnson Controls Unitary Products York Drive Norman, OK

TM9T*MP specifications

Johnson Controls TM9T*MP is a state-of-the-art HVAC unit designed for modern commercial and residential applications. With its innovative technology and robust features, the TM9T*MP offers exceptional performance, efficiency, and reliability. This unit is engineered to provide optimal climate control, ensuring that indoor environments remain comfortable regardless of external weather conditions.

One of the main features of the TM9T*MP is its variable-speed compressor, which allows for precise temperature regulation and energy-efficient operation. This technology enables the unit to adjust its output based on the current demand, significantly reducing energy consumption compared to traditional systems. By operating at lower speeds during mild weather, the TM9T*MP minimizes energy costs while maintaining user comfort.

Another significant aspect of the TM9T*MP is its advanced multi-stage filtration system. This system includes a high-efficiency air filter capable of capturing a wide range of airborne particles, including dust, pollen, and allergens. This feature not only improves indoor air quality but also helps to promote a healthier living environment for occupants. Furthermore, the TM9T*MP is compatible with smart home technology, allowing users to monitor and control their HVAC system remotely through mobile devices or voice-controlled assistants.

The TM9T*MP also boasts a compact design, making it versatile for various installation environments. Its sleek profile allows for easy integration into existing spaces without requiring extensive modifications. Durability is another hallmark of this unit, as it is built with high-quality materials designed to withstand the rigors of daily use while providing long-lasting performance.

Additionally, the TM9T*MP incorporates advanced diagnostics and troubleshooting capabilities. This feature simplifies maintenance by alerting technicians to potential issues before they escalate, ensuring smooth operation and reducing downtime. Moreover, with a user-friendly interface, occupants can easily adjust settings, access energy usage data, and schedule maintenance reminders for peak performance.

In summary, Johnson Controls TM9T*MP sets a new standard in HVAC technology with its variable-speed compressor, multi-stage filtration, compact design, and smart capabilities. Committed to energy efficiency and indoor air quality, it promises to deliver comfort and sustainability in every setting.