Carrier 58MVP instruction manual →44

Page 15

Wait at least 5 minutes after disconnecting line voltage from equipment before opening blower motor to prevent electric shock which can cause personal injury or death.

44.

Remove tape from door switch and turn power off at main disconnect.

Ð

Ð

45

45.

Disconnect PL10 from blower assembly.

Ð

Ð

46

46.

Remove control box assembly from blower shelf and position out of the way.

Ð

Ð

47

47.

Remove blower assembly from furnace.

Ð

Ð

48

48.

Disconnect both multi-pin connectors from blower control module attached to the blower motor. Be

Ð

Ð

49

sure to depress release latches on connectors or they may get damaged.

 

 

 

 

49.

Remove two 1/4-in. hex head bolts from blower control module attached to blower motor. DO NOT

Ð

Ð

50

REMOVE TORX HEAD SCREWS located next to 1/4-in. hex head bolts.

 

 

 

 

50.

Carefully lift blower control module off blower motor. Depress latch on internal connector to discon-

 

 

 

nect blower control module from motor portion of blower motor. DO NOT PULL ON WIRES. GRIP

Ð

Ð

51

 

PLUG ONLY.

 

 

 

 

When blower control module is completely detached from blower motor, verify with standard ohm-

 

 

 

 

meter that the resistance from each motor lead in motor plug to unpainted motor end plate is

 

 

 

51.

greater than 100k ohms. Then verify motor windings are not shorted or open by measuring resis-

Ð

Ð

52

tance between each combination of pins in motor plug (there are three different combinations, pin

 

 

 

 

 

1-2, pin 2-3, and pin 1-3). Resistance should be approximately equal across each combination of

 

 

 

 

pins.

 

 

 

52.

Did the motor pass the resistance check?

53

55

Ð

53.

Does blower wheel turn freely with blower control module removed?

54

55

Ð

54.

Replace blower control module. Inspect failed blower control module for water damage. If present,

Ð

Ð

5

find source of water and fix. Check A-coil and/or humidifier.

 

 

 

 

55.

Replace entire blower motor including blower control module. Inspect blower control module for wa-

Ð

Ð

5

ter damage. If present, find source of water and fix. Check A-coil and/or humidifier.

 

 

 

 

 

 

 

 

 

Fault Code 13

LIMIT SWITCH LOCKOUTÐThis fault indicates the limit switch has tripped 10 times in a row in high fire or 3 times in a row in low fire during a call for heat. Control will auto-reset in 3 hr.

NOTE: After 2 low-fire limit trips, the control is locked into high-heat mode; however, a third low-heat cycle can be forced due to excessive restriction in air delivery system.

NOTE: Boards with date codes of 9506 or later will lock into high-heat mode after 2 low-fire limit trips and CANNOT be forced into a third low-heat cycle. Therefore, units with these boards can only lock out if the limit switch trips 10 times in a row in high fire during a call for heat.

STEP

ACTION

YES

NO

GO TO

1.

Turn power off and remove blower access panel. Disconnect all thermostat leads from furnace con-

Ð

Ð

2

trol board.

 

 

 

 

2.

Depress door switch. Use a piece of tape to hold switch closed.

Ð

Ð

Ð

3.

Put setup switch SW-1 in ON position.

Ð

Ð

4

 

Is a Fault Code 44 present in the fault history.

 

 

 

4.

NOTE: Read fault codes until they repeat. The last fault code that occurred will flash first fol-

46

5

Ð

 

lowed by the lowest number fault code. (EXAMPLE: 13, 13, 44)

 

 

 

5.

Put setup switch SW-1 in OFF position.

Ð

Ð

42

6.

Does furnace have proper limit switch, limit shield, blower baffle (if used), and rear air baffle (if

10

48

Ð

used)? If so are limit switch, limit shield, and heat exchangers properly aligned?

 

 

 

 

7.

Replace limit switch.

Ð

Ð

9

8.

Replace furnace control board.

Ð

Ð

9

9.

Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.

Ð

Ð

INDEX

10.

Put setup switch SW-2 in ON position.

Ð

Ð

11

11.

Jumper R and W/W1 thermostat terminals on furnace control board.

Ð

Ð

12

12.

Is furnace considerably overfired (10% or more)? Clock input rate. Do not use manifold pressure

13

14

Ð

method unless using propane.

 

 

 

 

13.

Ensure gas inlet pressure and burner orifices (natural or propane) are correct. Then adjust gas

 

 

 

valve to proper rate per Installation, Start-Up, and Operating Instructions. If it cannot be adjusted to

Ð

Ð

9

 

proper rate, replace gas valve.

 

 

 

14.

Is the personality connector PL5 properly wired per furnace model sizing chart in upper left-hand

50

15

Ð

corner of wiring schematic?

 

 

 

 

15.

Replace or rewire personality connector.

Ð

Ð

9

15

Image 15
Contents Troubleshooting Guide Start Here Section ExampleÐCooling Mode ÐVariable Speed Furnace Control ÐWith DE Connection Lowed by the lowest number fault code. Example 13, 13 Service Status Code Example → ÐService Label/Fault Code InstructionsStep Action YES GO to ÐAir Conditioning A/C Airflow Setup Switch Position LEDs 1, 2, 3, or 4 on Solid Solid means on continuously Step Action YES GO to Fault Code Motor MTR2 →44 Page Lowed by the lowest number fault code. Example 14, 14 Fault Code ÐTwo-Speed AC/HP Airflow Requirements CFM ÐContinuous Fan CF Airflow Setup Switch PositionPage · LOW Heat Page →18 →40 Utes 14ÐIGNITION Lockout Ber indicated in Index for Fault Code →26 Turn power off Is inducer blower wheel okay? 55 ¬ Rpmrpm highlow ¬ →20 Index for Fault Code Cleanup and START-UP Instructions Board Layout and Schematic Appendix aControl Center Schematic Diagram Wiring SchematicIsolation Circuits Pressure Check DiagramAppendix B Appendix CAppendix D Quick Motor Test Procedure→33 →59 Example AIR Delivery Curve Ð Appendix EAir Delivery CurveÐ120-20 Air Delivery CurvesAir Delivery Curve Ð Air Delivery CurveÐ100-20Closet Ð Downflow Application Static Pressure Reading Location DiagramsBasement Ð Upflow Application Upflow Total Static Pressure Reading LocationsAttic Ð Horizontal Application Duct Static Check Sheet Quick Reference Information Appendix FThermostat Staging Algorithm Appendix GVariable Speed Condensing Furnace Algorithm Service Training
Related manuals
Manual 12 pages 2.11 Kb

58MVP specifications

The Carrier 58MVP is a high-efficiency gas furnace designed for optimal performance and energy savings. This model represents Carrier's commitment to innovative engineering and advanced technology, making it a preferred choice for homeowners seeking reliable heating solutions.

One of the standout features of the 58MVP is its impressive Annual Fuel Utilization Efficiency (AFUE) rating, which can reach up to 96 percent. This high AFUE rating indicates that the furnace uses less energy to produce heat, leading to lower utility bills and a reduced carbon footprint. The furnace is equipped with a two-stage gas valve that allows it to operate on a low setting during mild weather, providing increased efficiency and comfort.

The 58MVP also features Carrier's Infinity Control system, an advanced programmable thermostat that enables homeowners to customize their heating preferences. This system allows for precise temperature control and scheduling, ensuring that the home remains at a comfortable temperature while minimizing energy consumption.

In addition to its efficiency, the 58MVP is designed with noise reduction technology, including a quiet operating blower and insulated cabinet. This reduces operational sound, allowing for a more peaceful home environment. The model's multi-speed blower motor enhances comfort by providing consistent airflow and further optimizing efficiency.

Durability is a key characteristic of the Carrier 58MVP. It has a stainless-steel heat exchanger that promotes longevity and performance. The furnace is also equipped with a galvanized steel cabinet featuring a powder-coated finish, which protects against rust and corrosion.

The 58MVP is compatible with Carrier's advanced air purification systems, optimizing indoor air quality while heating. With features designed for efficiency, comfort, and durability, the Carrier 58MVP is an exceptional choice for homeowners looking to enhance their heating systems. The combination of advanced technologies, such as the two-stage operation and Infinity Control, positions this furnace as a leader in the market, meeting the needs of today's energy-conscious consumers. Ideal for both new constructions and retrofits, the Carrier 58MVP continues to set the standard for residential heating solutions.