Carrier 58MVP instruction manual Troubleshooting Guide

Page 1

58MVP Variable-Speed 2-Stage Electronic Condensing Furnace

Visit www.carrier.com

Troubleshooting Guide

NOTE: Read the entire instruction manual before starting the installation.

SAFETY CONSIDERATIONS

 

INDEX

 

 

PAGE

Instructions

1

Example

2

Sequence of Operation

1-5

Self-Test Mode

2

Heating Mode

2

Heating Mode-Two Stage

2

Emergency Heat Mode

2-3

Cooling Mode

3

Heat Pump Mode

3-4

Continuous Fan Mode

4

Component Test

4-5

Bypass Humidifier Mode

5

Dehumidification Mode

5

Zone Mode

5

Start Here

6

Service Label/Fault Code Instructions

7-8

Improper Operation With No Flashing Fault Code

9

Not Enough Cooling Airflow

10

High-Fire Temperature Rise Too Low (Cold Blow)

11

LEDs 1, 2, 3, or 4 On Solid

11-12

RED LED2 Flashing

12

Fault Code 11ÐNo Fault in Recent History Display

13

Fault Code 12ÐBlower Calibration Lockout

13-15

Fault Code 13ÐLimit Switch Lockout

15-16

Fault Code 14ÐIgnition Lockout

17

Fault Code 21ÐInvalid Model Selection

17

Fault Code 22ÐSet Up Error

18

Fault Code 23ÐInvalid Blower Airflow Selection

18

Fault Code 24ÐSecondary Voltage Fuse Is Open

19-20

Fault Code 31ÐHigh-Pressure Switch Fault

21-22

Fault Code 32ÐLow-Pressure Switch Fault

23-24

Fault Code 33ÐLimit Switch Fault

24-25

Fault Code 34ÐIgnition Proving Fault

26-27

Fault Code 41ÐBlower Outside Valid Speed Range

27-28

Fault Code 42ÐInducer Outside Valid Speed Range

29-30

Fault Code 43ÐPressure Switch Calibration Fault

30-31

Fault Code 44ÐBlower Calibration Fault

32

Cleanup and Start-Up Instructions

33

APPENDIX AÐBoard Layout & Wiring Schematic

34-35

APPENDIX BÐIsolation Circuits

36

APPENDIX CÐPressure Check Diagram

36

APPENDIX DÐQuick Motor Test Procedure

37-39

APPENDIX EÐVariable-Speed Condensing Furnace Duct Static

and Blower Operation

40-44

APPENDIX FÐQuick Reference Information

45

APPENDIX GÐThermostat Staging Algorithm

46-47

INSTRUCTIONS

This guide uses your expertise and observations to lead you to the trouble spot as efficiently as possible. This is only intended as a guide and should not be used blindly. Your experience and expertise are of high value when troubleshooting this unit. Do not disregard all of your instincts.

The microprocessor furnace control was designed with diagnostic capabilities built in. LEDs are used to flash a fault code which will lead you to 1 of the subsections as listed in the Index.

You should ALWAYS begin in the START HERE subsection (see Index for page number) which will guide you to the appropriate subsection where a minimal number of steps will be used to correct the problem. If you are very experienced at how this furnace operates and you suspect the problem is either the blower motor, inducer motor, or furnace control board, you can use the quick motor test procedure at the end of the troubleshooting guide to isolate the problem or direct you to appropriate section in main troubleshooting guide.

Once in a subsection, read the statement or question. A statement will have a number in the "GO TO" column. Do whatever the statement says, then proceed to step indicated in the "GO TO" column.

If the step is a question (a question will have a number in the "YES" or "NO" column), answer it "YES" or "NO." If the answer is "YES," go to step indicated in "YES" column. If the answer is "NO," go to step indicated in "NO" column.

Let's try our guide out using the EXAMPLE section below, and see how it works. Suppose that the problem is a defective low-pressure switch (for example will not make). This is an internal problem and cannot simply be seen. We go to the START HERE section to Step 1.

Additional Service Tools are available for current variable speed condensing furnaces. The Advanced Product Monitor Kit KGAFP0101APM includes a harness and diskette that allows communication with the control board through a personal com- puter (RS-485 adapter required). The ICM Motor Simulator Kit KGASD0101FMS is a plug-in device to help trooubleshoot ICM inducer and blower motors and control boards. Reference price pages for current kit numbers.

SEQUENCE OF OPERATION

Furnace control must be grounded for proper operation, or control will lock out. Control is grounded through green wire routed to gas valve and burner box screw.

Using schematic diagram (see Appendix A), follow sequence of operation through different modes. This furnace has a new control system. Read and follow wiring diagram carefully.

NOTE: If 115-v power supply to furnace or blower access panel switch is interrupted during a call for heat, blower operates at low-heat speed for 60 sec when power is restored before heating cycle is resumed.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

PC 101

Catalog No. 535-754

Printed in U.S.A.

Form 58MVP-8SM

Pg 1

9-99

Replaces: 58MVP-6SM

Tab

6a

8a

 

 

 

 

 

 

 

Image 1
Contents Troubleshooting Guide Start Here Section ExampleÐCooling Mode ÐVariable Speed Furnace Control ÐWith DE Connection Lowed by the lowest number fault code. Example 13, 13 Service Status Code Example → ÐService Label/Fault Code InstructionsStep Action YES GO to ÐAir Conditioning A/C Airflow Setup Switch Position LEDs 1, 2, 3, or 4 on Solid Solid means on continuously Step Action YES GO to Fault Code Motor MTR2 →44 Page Lowed by the lowest number fault code. Example 14, 14 Fault Code ÐTwo-Speed AC/HP Airflow Requirements CFM ÐContinuous Fan CF Airflow Setup Switch PositionPage · LOW Heat Page →18 →40 Utes 14ÐIGNITION Lockout Ber indicated in Index for Fault Code →26 Turn power off Is inducer blower wheel okay? 55 ¬ Rpmrpm highlow ¬ →20 Index for Fault Code Cleanup and START-UP Instructions Appendix a Board Layout and SchematicControl Center Schematic Diagram Wiring SchematicAppendix B Pressure Check DiagramAppendix C Isolation CircuitsAppendix D Quick Motor Test Procedure→33 →59 Example AIR Delivery Curve Ð Appendix EAir Delivery Curve Ð Air Delivery CurvesAir Delivery CurveÐ100-20 Air Delivery CurveÐ120-20Basement Ð Upflow Application Static Pressure Reading Location DiagramsUpflow Total Static Pressure Reading Locations Closet Ð Downflow ApplicationAttic Ð Horizontal Application Duct Static Check Sheet Quick Reference Information Appendix FThermostat Staging Algorithm Appendix GVariable Speed Condensing Furnace Algorithm Service Training
Related manuals
Manual 12 pages 2.11 Kb

58MVP specifications

The Carrier 58MVP is a high-efficiency gas furnace designed for optimal performance and energy savings. This model represents Carrier's commitment to innovative engineering and advanced technology, making it a preferred choice for homeowners seeking reliable heating solutions.

One of the standout features of the 58MVP is its impressive Annual Fuel Utilization Efficiency (AFUE) rating, which can reach up to 96 percent. This high AFUE rating indicates that the furnace uses less energy to produce heat, leading to lower utility bills and a reduced carbon footprint. The furnace is equipped with a two-stage gas valve that allows it to operate on a low setting during mild weather, providing increased efficiency and comfort.

The 58MVP also features Carrier's Infinity Control system, an advanced programmable thermostat that enables homeowners to customize their heating preferences. This system allows for precise temperature control and scheduling, ensuring that the home remains at a comfortable temperature while minimizing energy consumption.

In addition to its efficiency, the 58MVP is designed with noise reduction technology, including a quiet operating blower and insulated cabinet. This reduces operational sound, allowing for a more peaceful home environment. The model's multi-speed blower motor enhances comfort by providing consistent airflow and further optimizing efficiency.

Durability is a key characteristic of the Carrier 58MVP. It has a stainless-steel heat exchanger that promotes longevity and performance. The furnace is also equipped with a galvanized steel cabinet featuring a powder-coated finish, which protects against rust and corrosion.

The 58MVP is compatible with Carrier's advanced air purification systems, optimizing indoor air quality while heating. With features designed for efficiency, comfort, and durability, the Carrier 58MVP is an exceptional choice for homeowners looking to enhance their heating systems. The combination of advanced technologies, such as the two-stage operation and Infinity Control, positions this furnace as a leader in the market, meeting the needs of today's energy-conscious consumers. Ideal for both new constructions and retrofits, the Carrier 58MVP continues to set the standard for residential heating solutions.