Carrier Understanding Furnace Fault Codes: Error Code 43 and Error Code 33

Page 30

43.

If possible, replace inducer wheel. Otherwise, replace inducer motor assembly.

Ð

Ð

8

44.

Is there any frost build-up on combustion-air inlet?

45

46

Ð

45.

The problem is caused by reversed vent and combustion-air pipes or some other moist air entering

Ð

Ð

14

combustion-air pipe.

 

 

 

 

46.

You have inadequate combustion-air supply. This may be caused by:

 

 

 

- Excessive restriction in combustion-air or vent pipe.

Ð

Ð

14

 

- Internal restriction in coupling box or secondary heat exchangers

 

 

 

47.

Replace pressure switch assembly.

Ð

Ð

70

48.

Is unit a trophy unit?

50

49

Ð

49.

Does fault occur before blower motor turns ON?

47

51

Ð

 

Replace pressure switch assembly with pressure switch assembly used in NON-trophy models or

 

 

 

50.

replace furnace control board. If you replace furnace control board make sure replacement control

Ð

Ð

70

has a date code of 9837 or later. Only replace the pressure switch assembly or the furnace control

 

 

 

 

 

board NOT both.

 

 

 

51.

Replace furnace control board.

Ð

Ð

70

52.

Turn power off and disconnect jumper wire across R and W/W1 thermostat terminals.

Ð

Ð

53

53.

Turn power on and wait several sec before proceeding to next step.

Ð

Ð

54

54.

Disconnect collector box tube to pressure switch assembly.

Ð

Ð

55

55.

Jumper R and W/W1 thermostat terminals on furnace control board.

Ð

Ð

56

56.

Does Fault Code 42 occur within 11 sec after a call for heat?

57

58

Ð

57.

Reconnect collector box tube to pressure switch assembly.

Ð

Ð

10

58.

Reconnect collector box tube to pressure switch assembly.

Ð

Ð

36

59.

Go to page number indicated in Index for CLEANUP AND STARTUP INSTRUCTIONS. If problem

Ð

Ð

INDEX

persists on an intermittent basis, contact your distributor.

 

 

 

 

60.

Turn power off and disconnect jumper wire across R and W/W1 thermostat terminals.

Ð

Ð

61

61.

Turn power on and wait several sec, then jumper R, W/W1, and W2 thermostat terminals on fur-

Ð

Ð

62

nace control board.

 

 

 

 

 

Does fault occur a few sec after high-pressure switch HPS makes?

 

 

 

62.

NOTE: Check for 24v between the N.O. (Normally Open) contact on high-pressure switch

63

67

Ð

 

HPS and Com on furnace control board to know when high-pressure switch HPS makes.

 

 

 

63.

Turn power off and disconnect jumper wire across R, W/W1, and W2 thermostat terminals.

Ð

Ð

64

64.

Connect 1 side of a slope manometer with a tee to collector box pressure tap. Connect other side

Ð

Ð

65

with a tee to gas valve air pressure fitting. Refer to pressure check diagram in Appendix C.

 

 

 

 

65.

Turn power on and wait several sec, then jumper R, W/W1, and W2 thermostat terminals on fur-

Ð

Ð

66

nace control board.

 

 

 

 

 

 

 

 

 

 

Do you have more than 1.9 in. wc pressure drop across heat exchangers when high-pressure

 

 

 

66.

switch HPS makes?

47

44

Ð

NOTE: Check for 24v between the N.O. (Normally Open) contact on high-pressure switch

 

 

 

 

 

HPS and Com on furnace control board to know when high-pressure switch HPS makes.

 

 

 

 

 

 

 

 

67.

Does fault occur a few sec after main burners ignite?

63

68

Ð

 

 

 

 

 

68.

Observe operation of furnace in high heat for next 8 minutes or until fault occurs.

Ð

Ð

69

 

 

 

 

 

69.

Does the fault occur?

22

59

Ð

 

 

 

 

 

70.

If problem still persists check for internal restriction in coupling box or secondary heat exchangers.

Ð

Ð

14

 

 

 

 

 

Fault Code 43

PRESSURE SWITCH CALIBRATION FAULTÐIndicates low-pressure switch LPS and high-pressure switch HPS "make" points during high-heat purge are not within calibration range. This is determined by reading inducer motor RPM when low-pressure switch LPS and high-pressure switch HPS make. Then the following comparison is made:

0.55¬ RPMRPM (high)(low) ¬ 0.90

If this relationship is not within range specified, furnace control board starts flashing fault colde 43, shuts unit down (inducer runs for 15 sec), waits 2 minutes, stops flashing fault code, and restarts heating cycle.

It can also indicate that the high-pressure switch HPS made before the low-pressure switch LPS during either low-heat or high-heat purge.

STEP

ACTION

YES

NO

GO TO

1.

Turn power off, remove blower access panel, and disconnect all thermostat leads from furnace con-

Ð

Ð

2

trol board.

 

 

 

 

2.

Turn power on and depress door switch. Use a piece of tape to hold switch closed.

Ð

Ð

3

3.

Jumper R, W/W1, and W2 thermostat terminals on furnace control board.

Ð

Ð

4

30

Image 30
Contents Troubleshooting Guide Example Start Here SectionÐCooling Mode ÐVariable Speed Furnace Control ÐWith DE Connection Lowed by the lowest number fault code. Example 13, 13 Service → ÐService Label/Fault Code Instructions Status Code ExampleStep Action YES GO to ÐAir Conditioning A/C Airflow Setup Switch Position LEDs 1, 2, 3, or 4 on Solid Solid means on continuously Step Action YES GO to Fault Code Motor MTR2 →44 Page Lowed by the lowest number fault code. Example 14, 14 Fault Code ÐContinuous Fan CF Airflow Setup Switch Position ÐTwo-Speed AC/HP Airflow Requirements CFMPage · LOW Heat Page →18 →40 Utes 14ÐIGNITION Lockout Ber indicated in Index for Fault Code →26 Turn power off Is inducer blower wheel okay? 55 ¬ Rpmrpm highlow ¬ →20 Index for Fault Code Cleanup and START-UP Instructions Board Layout and Schematic Appendix aControl Center Wiring Schematic Schematic DiagramAppendix C Pressure Check DiagramAppendix B Isolation CircuitsQuick Motor Test Procedure Appendix D→33 →59 Appendix E Example AIR Delivery Curve ÐAir Delivery CurveÐ100-20 Air Delivery CurvesAir Delivery Curve Ð Air Delivery CurveÐ120-20Upflow Total Static Pressure Reading Locations Static Pressure Reading Location DiagramsBasement Ð Upflow Application Closet Ð Downflow ApplicationAttic Ð Horizontal Application Duct Static Check Sheet Appendix F Quick Reference InformationAppendix G Thermostat Staging AlgorithmVariable Speed Condensing Furnace Algorithm Service Training
Related manuals
Manual 12 pages 2.11 Kb

58MVP specifications

The Carrier 58MVP is a high-efficiency gas furnace designed for optimal performance and energy savings. This model represents Carrier's commitment to innovative engineering and advanced technology, making it a preferred choice for homeowners seeking reliable heating solutions.

One of the standout features of the 58MVP is its impressive Annual Fuel Utilization Efficiency (AFUE) rating, which can reach up to 96 percent. This high AFUE rating indicates that the furnace uses less energy to produce heat, leading to lower utility bills and a reduced carbon footprint. The furnace is equipped with a two-stage gas valve that allows it to operate on a low setting during mild weather, providing increased efficiency and comfort.

The 58MVP also features Carrier's Infinity Control system, an advanced programmable thermostat that enables homeowners to customize their heating preferences. This system allows for precise temperature control and scheduling, ensuring that the home remains at a comfortable temperature while minimizing energy consumption.

In addition to its efficiency, the 58MVP is designed with noise reduction technology, including a quiet operating blower and insulated cabinet. This reduces operational sound, allowing for a more peaceful home environment. The model's multi-speed blower motor enhances comfort by providing consistent airflow and further optimizing efficiency.

Durability is a key characteristic of the Carrier 58MVP. It has a stainless-steel heat exchanger that promotes longevity and performance. The furnace is also equipped with a galvanized steel cabinet featuring a powder-coated finish, which protects against rust and corrosion.

The 58MVP is compatible with Carrier's advanced air purification systems, optimizing indoor air quality while heating. With features designed for efficiency, comfort, and durability, the Carrier 58MVP is an exceptional choice for homeowners looking to enhance their heating systems. The combination of advanced technologies, such as the two-stage operation and Infinity Control, positions this furnace as a leader in the market, meeting the needs of today's energy-conscious consumers. Ideal for both new constructions and retrofits, the Carrier 58MVP continues to set the standard for residential heating solutions.