Carrier 58MVP instruction manual Appendix E, Example AIR Delivery Curve Ð

Page 40

Appendix E

Variable-Speed Condensing Furnace Duct Static and Blower

Operation

This variable-speed furnace has an Integrated Control and Motor called an ICM. This ICM is controlled as stated in Sequence of Operation section. This furnace does a good job compensating for an improperly sized duct system, but this ICM is not a fix for all bad ductwork.

This troubleshooting guide has shown that the blower does a calibration 20 sec at start of any operation of ICM. Note that blower calibration sequence is different when setup switch SW-5 is turned ON for multi-zone operation. (See Sequence of Operation section.) These blower calibrations help to ensure proper airflow in heating and cooling. In heating mode, this calibration helps ensure proper temperature rise which prolongs life of heat exchanger. In cooling mode, this calibration helps ensure proper CFM per ton of cooling.

If furnace is on a call for heat or cooling and duct static is too high, ICM tries to overcome external static pressure. If duct static is excessive, ICM RPM will be out of range and a Fault Code 44 will flash on circuit board. The ICM RPM range is 250 to 1300 RPM as stated in Fault Code 44 troubleshooting section. To check for excessive static pressure, use the following Air Delivery Curves and Duct Static Check Sheet later in this Appendix.

EXAMPLE: Furnace is a 100,000 Btuh input with a 5 ton blower cooling capacity. We measured total external static pressure (ESP) to be 0.4 in. wc in low-heat operation.

EXAMPLE AIR DELIVERY CURVE Ð 060100

External Static Pressure (in. wc)

 

HIGH

0.8

HEAT

Constant System

 

0.7

Curves

 

 

0.6

 

 

0.5

 

LOW

 

 

HEAT

0.4*

0.3

0.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

212 Ton

 

 

312 Ton

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

2 Ton

 

3 Ton

4 Ton

 

 

5 Ton

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

700

900

1100

1300

1500

1700

1900

2100

CFM

A98451

Use the dashed lines as guide lines. As you can see, the 0.4 in. wc total ESP is in the shaded area. The unit can deliver low heat, but as you follow the dashed guide lines, you see that they do not cross the high-heat line until it is off the chart, somewhere above 1.0 in. wc. The furnaces are rated at 0.5 in. wc total ESP and are tested to 0.8 in. wc total ESP.

See Static Pressure Reading Location Diagrams later in this Appendix for proper static reading locations. When checking total ESP, you must have blower operation without a Fault Code 44 occurring. If you have a Fault Code 44 in cooling and your setting is at 5 tons, set A/C tonnage to 4 tons and see if the Fault Code 44 goes away. If it does not, set switches to 3 tons, and so on until the Fault Code 44 goes away.

NOTE: When adjusting airflow, you must either turn power off or terminate thermostat call after every airflow adjustment. Record all static readings on Duct Static Check Sheet.

Solutions:

1.Dirty filter.

2.Plugged evaporator coil.

3.Re-size ductwork and/or layout.

SPECIAL NOTE: In zoning applications, it is recommended that when zone controls are applied, duct system be designed for sum of the peaks plus 25% oversize to allow furnace to operate within its design parameters. Contact your distributor for further details.

40

Image 40
Contents Troubleshooting Guide Example Start Here SectionÐCooling Mode ÐVariable Speed Furnace Control ÐWith DE Connection Lowed by the lowest number fault code. Example 13, 13 Service → ÐService Label/Fault Code Instructions Status Code ExampleStep Action YES GO to ÐAir Conditioning A/C Airflow Setup Switch Position LEDs 1, 2, 3, or 4 on Solid Solid means on continuously Step Action YES GO to Fault Code Motor MTR2 →44 Page Lowed by the lowest number fault code. Example 14, 14 Fault Code ÐContinuous Fan CF Airflow Setup Switch Position ÐTwo-Speed AC/HP Airflow Requirements CFMPage · LOW Heat Page →18 →40 Utes 14ÐIGNITION Lockout Ber indicated in Index for Fault Code →26 Turn power off Is inducer blower wheel okay? 55 ¬ Rpmrpm highlow ¬ →20 Index for Fault Code Cleanup and START-UP Instructions Appendix a Board Layout and SchematicControl Center Wiring Schematic Schematic DiagramPressure Check Diagram Appendix BAppendix C Isolation CircuitsQuick Motor Test Procedure Appendix D→33 →59 Appendix E Example AIR Delivery Curve ÐAir Delivery Curves Air Delivery Curve ÐAir Delivery CurveÐ100-20 Air Delivery CurveÐ120-20Static Pressure Reading Location Diagrams Basement Ð Upflow ApplicationUpflow Total Static Pressure Reading Locations Closet Ð Downflow ApplicationAttic Ð Horizontal Application Duct Static Check Sheet Appendix F Quick Reference InformationAppendix G Thermostat Staging AlgorithmVariable Speed Condensing Furnace Algorithm Service Training
Related manuals
Manual 12 pages 2.11 Kb

58MVP specifications

The Carrier 58MVP is a high-efficiency gas furnace designed for optimal performance and energy savings. This model represents Carrier's commitment to innovative engineering and advanced technology, making it a preferred choice for homeowners seeking reliable heating solutions.

One of the standout features of the 58MVP is its impressive Annual Fuel Utilization Efficiency (AFUE) rating, which can reach up to 96 percent. This high AFUE rating indicates that the furnace uses less energy to produce heat, leading to lower utility bills and a reduced carbon footprint. The furnace is equipped with a two-stage gas valve that allows it to operate on a low setting during mild weather, providing increased efficiency and comfort.

The 58MVP also features Carrier's Infinity Control system, an advanced programmable thermostat that enables homeowners to customize their heating preferences. This system allows for precise temperature control and scheduling, ensuring that the home remains at a comfortable temperature while minimizing energy consumption.

In addition to its efficiency, the 58MVP is designed with noise reduction technology, including a quiet operating blower and insulated cabinet. This reduces operational sound, allowing for a more peaceful home environment. The model's multi-speed blower motor enhances comfort by providing consistent airflow and further optimizing efficiency.

Durability is a key characteristic of the Carrier 58MVP. It has a stainless-steel heat exchanger that promotes longevity and performance. The furnace is also equipped with a galvanized steel cabinet featuring a powder-coated finish, which protects against rust and corrosion.

The 58MVP is compatible with Carrier's advanced air purification systems, optimizing indoor air quality while heating. With features designed for efficiency, comfort, and durability, the Carrier 58MVP is an exceptional choice for homeowners looking to enhance their heating systems. The combination of advanced technologies, such as the two-stage operation and Infinity Control, positions this furnace as a leader in the market, meeting the needs of today's energy-conscious consumers. Ideal for both new constructions and retrofits, the Carrier 58MVP continues to set the standard for residential heating solutions.