Linear Boiler installation instructions Burner Setup, Burner Manufacturer

Page 10

PAGE 10

BIASI B/40

 

 

8. Burner Setup:

The following information applies only to the BIASI B-40 series boilers at a maximum output for power venters or lined chimneys only.

BURNER MANUFACTURER

 

 

Heatwise

 

 

 

 

Boiler Model

B-406

B-407

B-408

B-409

B-410

B-411

B-412

 

Burner Model

P2-KA

P2-K

P2-K

DE-10

DE-10

DE-10

DE-10

 

Firing Rate

2.2 GPH

2.8 GPH

3.5 GPH

4.25 GPH

5.0 GPH

5.7 GPH

6.4 GPH

 

Insertion Depth

FULL

FULL

FULL

FULL

FULL

FULL

FULL

 

Nozzle

2.00 X 45

2.25 X 60

2.75 X 60

3.25 X 60

3.75 X 60

4.5 X 45

5.50 X 45

 

Spray Pattern

solid

solid

solid

solid

solid

solid

solid

 

Pump Pressure

140 psi

170 psi

175 psi

175 psi

175 psi

160 psi

140 psi

 

Head Position

12

16

18

1

1.5

2

2.5

 

Air Setting

11.50

15.00

18.00

3.5

4.5

5.5

6.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BURNER MANUFACTURER

 

Riello

 

 

 

 

 

Boiler Model

B-406

B-407

B-408

B-409

B-410

B-411

B-412

 

Burner Model

F-10

F-10

F-15

F-15

F-15

F-20

F-20

 

Firing Rate

2.4 GPH

2.6 GPH

3.3 GPH

4.0 GPH

4.6 GPH

5.3 GPH

5.9 GPH

 

Insertion Depth

4.5"

4.5"

4.5"

4.5"

4.5"

4.5"

4.5"

 

Nozzle

2.00X60

2.00X60

2.50X60

3.00X60

3.50X60

4.0X60

4.5X60

 

Spray Pattern

B

B

B

B

B

B

B

 

Pump Pressure

145 PSI

175 PSI

175 PSI

175 PSI

175 PSI

175 PSI

175 PSI

 

Turbulator

3.75

4.5

1.8

2.1

2.8

3.1

5

 

Air Gate

5

6

3

4

5.5

4

6

 

 

 

 

 

 

 

 

 

 

BURNER MANUFACTURER

 

Beckett

 

 

 

 

 

Boiler Model

B-407

B-407

B-408

B-409

B-410

B-411

B-412

 

Burner Model

CF 375

CF 375

CF 500

CF 500

CF 800

CF 800

CF 800

 

Firing Rate

2.1 GPH

2.7 GPH

3.2 GPH

3.7 GPH

4.3 GPH

4.8 GPH

5.3 GPH

 

Insertion Depth

4.5"

4.5"

4.5"

4.5"

4.5"

4.5"

4.5"

 

Nozzle

1.75X60

2.00X45

2.75X45

2.75X45

3.25X45

4.0X30

4.0X30

 

Spray Pattern

ES

hollow

solid

solid

solid

solid

solid

 

Pump Pressure

140 psi

180 psi

140 psi

180 psi

175 psi

145 psi

180 psi

 

Head Type

 

 

 

 

 

 

 

 

Head Position

0

2

3

4.5

3

3

4.5

 

Air Setting

9/0

3/1

7/0

10/0

7/0

8/0

10/2

 

 

 

 

 

 

 

 

 

 

Good, reliable operation with a minimum of service starts with attention to the small details:

1.Setting the nozzle position and electrodes "by the book" using the manufacturer's gauges.

2.Installing a quality micron filter at the burner.

3.Making careful/tight flare connections without couplings on oil suction line.

4.Checking fuel pump pressure.

5.Checking draft at the breeching to insure it is adequate to overcome flue gas resistance.

6.Setting the air band properly with well maintained instruments. A good target is 11% to 12.5% of (CO2) or 6.5% to 3.8% of (O2).

Note: Oil and Gas burners on B40-series boilers cannot be properly commissioned without instruments and gauges.

Image 10
Contents Linear Boiler Page Table of Contents Important Information Please read this page carefullyBiasi B/40 General Information WeightConforming to Codes and Regulations Combustion Air Supply Boiler LocationBoiler Block Assembly Installation of Boiler Trim ComponentsBiasi B/40 Burner Setup Burner ManufacturerFt 3/hr = 3600/sec. Per rev.*Size of gas meter Installation of Sediment Trapand Burner Supply Gas Line PipingInstallation of Sediment Trapand Burner Supply Breeching and Venting Blocked Flue Switch PipingBiasi B/40 Boiler Jacket Assembly Boiler Components Parts Vega B40 SeriesWiring Control Panel Description Relay Circulator Circulator Relay Control Panel Wiring Diagram for Riello Oil Burner Control Panel Wiring Diagram for Heat Wise Gas Burners Maintenance CommissioningInstaller Notes System CheckoutBiasi B/40 Biasi B/40 Warranty For Biasi B40 Series Commercial Cast-Iron Water Boilers