PAGE 6 | BIASI B/40 |
|
|
2. General Information:
The Linear series are wet base design, sectional,
The Linear series boilers are shipped from the factory in assembled blocks and each boiler can range from 6 to 12 sections. The sections can then be disassembled before delivery to the jobsite by QHT and then field assembled. The boiler jacket, burner and controls are packed separately for shipping.
Note: All equipment should be inspected upon delivery, and any damage or shortage should be reported immediately.
Boiler |
|
| Input | Input |
|
| Water |
|
|
Model | Number of | Heating | Oil | Gas | Net Output |
| Content | Length | Weight |
Number | Sections | Capacity | G.P.H. | MBH | MBH | Efficiency % | Gals. | (L) inches | (LBS) |
B40/6 | 6 | 265 | 2.20 | 308 | 230 | 86.0 | 17 | 34.8 | 902 |
B40/7 | 7 | 352 | 2.90 | 406 | 305 | 86.7 | 20 | 39.5 | 1023 |
B40/8 | 8 | 437 | 3.60 | 504 | 380 | 86.8 | 23 | 44.4 | 1144 |
B40/9 | 9 | 524 | 4.30 | 602 | 456 | 87.0 | 26 | 49.2 | 1265 |
B40/10 | 10 | 610 | 5.00 | 700 | 532 | 87.2 | 28 | 53.9 | 1386 |
B40/11 | 11 | 696 | 5.70 | 798 | 607 | 87.2 | 31 | 58.8 | 1507 |
B40/12 | 12 | 783 | 6.40 | 896 | 684 | 87.4 | 34 | 63.8 | 1628 |
|
|
|
|
|
|
|
|
|
|
MaximumWater Working Pressure 72 psi |
| MaximumRelief Valve is 50 psi @ 900 MBH |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3. Conforming to Codes and Regulations:
Installation of the boiler, burner, oil tank and related equipment must conform to national, state and local regulating agencies and codes applicable to the installation of the equipment. In the absence of local requirements, the following codes apply:
•ANSI/NFPA - #31 Installation of Oil Burning Equipment
•ANSI/NFPA - #70 National Electric Code
•ANSI/NFPA - #211 Chimneys and Vents
The above codes are available from:
National Fire Protection Association (NFPA)
Battery March Park
Quincy, Massachusetts, 02269