Linear Boiler installation instructions Ft 3/hr = 3600/sec. Per rev.*Size of gas meter

Page 11

BIASI B/40

PAGE 11

 

 

8. Burner Setup:

The following information applies only to the BIASI B-40 series boilers at a maximum output for power venters or lined chimneys only.

BURNER MANUFACTURER

 

 

 

Heat Wise

 

 

 

 

Boiler Model

 

B-406

B-407

B-408

B-409

B-410

B-411

B-412

 

Burner Model

 

SU-3

SU-3

SU-4

SU-5

SU-5

SU-6

SU-6

 

Fuel

 

Natural

Natural

Natural

Natural

Natural

Natural

Natural

 

Input

 

315

420

499

577

672

847

954

 

Min. Gas Inlet Size

 

1"

1"

1"

1"

1"

1"

1-1/4"

 

Manifold in w.c.

 

1.95"

3"

3.5"

2"

2.8"

1.16"

1.4"

 

Air

 

9.5

14

21

7.5

9

4.25

5

 

Head

 

6

11

20

2"

2"

2-5/8"

2-5/8"

 

 

 

 

 

 

 

 

 

 

 

 

BURNER MANUFACTURER

 

 

Heat Wise

 

 

 

 

 

Boiler Model

B-406

B-407

B-408

B-409

B-410

B-411

B-412

 

 

Burner Model

SU-3

SU-3

SU-4

SU-5

SU-5

SU-6

SU-6

 

 

Fuel

Propane

Propane

Propane

Propane

Propane

Propane

Propane

 

 

Input

315

420

527

634

740

847

954

 

 

Min. Gas Inlet Size

3/4"

3/4"

1"

1"

1"

1"

1"

 

 

Manifold in w.c.

1.65"

2.4"

2.75"

 

 

1"

1.27"

 

 

Air

7.25

15

21.5

 

 

5.2

5.8

 

 

Head

6

10

18

2"

2"

2-5/8"

2-5/8"

 

 

 

 

 

 

 

 

 

 

 

Good, reliable operation with a minimum of service starts with attention to the small details:

1.Setting the electrode and flame rod settings against manufacturer's specs to insure proper operation.

2.Installing properly sized gas piping according to BTU input required and length of gas line run.

3.Making sure there is proper manifold pressure before and after the gas valve using a calibrated manometer.

4.Checking draft at the breeching to insure it is adequate to overcome flue gas resistance.

5.Setting the air band properly with well maintained instruments. A good target is 9.5% to 10.5% of (CO2) or 5% to 2.5% of (O2) for natural gas, or 10% to 12% of (CO2) or 5% to 2.5% of (O2) for lp gas

Note: Oil and Gas burners on B40-series boilers cannot be properly commissioned without instruments and gauges.

To determine how much gas is coming into the

 

 

 

 

 

 

Seconds per

 

Size of Gas Meter Dial

 

 

 

 

burner, or to set the gas meter correctly, the follow-

 

 

(Cubic Foot)

 

Revolution

 

 

 

ing formula can be used.

0.5

 

1

 

2

 

 

 

 

20

90

 

180

 

360

Ft3/hr = [3600/(sec. Per rev.)]*(Size of gas meter)

25

72

 

144

 

288

30

60

 

120

 

240

 

 

 

 

35

51

 

103

 

206

The chart to the right can be used to determine the

40

45

 

90

 

180

flow rate depending upon the time per revolution and

45

40

 

80

 

160

50

36

 

72

 

144

the size of the gas meter dial.

 

 

55

33

 

65

 

131

 

 

 

 

60

30

 

60

 

120

Image 11
Contents Linear Boiler Page Table of Contents Please read this page carefully Important InformationBiasi B/40 Conforming to Codes and Regulations WeightGeneral Information Boiler Location Combustion Air SupplyInstallation of Boiler Trim Components Boiler Block AssemblyBiasi B/40 Burner Manufacturer Burner SetupFt 3/hr = 3600/sec. Per rev.*Size of gas meter Gas Line Piping Installation of Sediment Trapand Burner SupplyInstallation of Sediment Trapand Burner Supply Breeching and Venting Piping Blocked Flue SwitchBiasi B/40 Boiler Components Parts Vega B40 Series Boiler Jacket AssemblyWiring Control Panel Description Relay Circulator Circulator Relay Control Panel Wiring Diagram for Riello Oil Burner Control Panel Wiring Diagram for Heat Wise Gas Burners Commissioning MaintenanceSystem Checkout Installer NotesBiasi B/40 Biasi B/40 For Biasi B40 Series Commercial Cast-Iron Water Boilers Warranty