BIASI B/40 | PAGE 11 |
|
|
8. Burner Setup:
The following information applies only to the BIASI
BURNER MANUFACTURER |
|
|
| Heat Wise |
|
|
|
| |
Boiler Model |
|
| |||||||
Burner Model |
|
| |||||||
Fuel |
| Natural | Natural | Natural | Natural | Natural | Natural | Natural |
|
Input |
| 315 | 420 | 499 | 577 | 672 | 847 | 954 |
|
Min. Gas Inlet Size |
| 1" | 1" | 1" | 1" | 1" | 1" |
| |
Manifold in w.c. |
| 1.95" | 3" | 3.5" | 2" | 2.8" | 1.16" | 1.4" |
|
Air |
| 9.5 | 14 | 21 | 7.5 | 9 | 4.25 | 5 |
|
Head |
| 6 | 11 | 20 | 2" | 2" |
| ||
|
|
|
|
|
|
|
|
|
|
| BURNER MANUFACTURER |
|
| Heat Wise |
|
|
|
| |
| Boiler Model |
| |||||||
| Burner Model |
| |||||||
| Fuel | Propane | Propane | Propane | Propane | Propane | Propane | Propane |
|
| Input | 315 | 420 | 527 | 634 | 740 | 847 | 954 |
|
| Min. Gas Inlet Size | 3/4" | 3/4" | 1" | 1" | 1" | 1" | 1" |
|
| Manifold in w.c. | 1.65" | 2.4" | 2.75" |
|
| 1" | 1.27" |
|
| Air | 7.25 | 15 | 21.5 |
|
| 5.2 | 5.8 |
|
| Head | 6 | 10 | 18 | 2" | 2" |
| ||
|
|
|
|
|
|
|
|
|
|
Good, reliable operation with a minimum of service starts with attention to the small details:
1.Setting the electrode and flame rod settings against manufacturer's specs to insure proper operation.
2.Installing properly sized gas piping according to BTU input required and length of gas line run.
3.Making sure there is proper manifold pressure before and after the gas valve using a calibrated manometer.
4.Checking draft at the breeching to insure it is adequate to overcome flue gas resistance.
5.Setting the air band properly with well maintained instruments. A good target is 9.5% to 10.5% of (CO2) or 5% to 2.5% of (O2) for natural gas, or 10% to 12% of (CO2) or 5% to 2.5% of (O2) for lp gas
Note: Oil and Gas burners on
To determine how much gas is coming into the |
|
|
|
|
|
|
Seconds per |
| Size of Gas Meter Dial |
| |||
|
|
| ||||
burner, or to set the gas meter correctly, the follow- |
|
| (Cubic Foot) |
| ||
Revolution |
|
|
| |||
ing formula can be used. | 0.5 |
| 1 |
| 2 | |
|
|
| ||||
| 20 | 90 |
| 180 |
| 360 |
Ft3/hr = [3600/(sec. Per rev.)]*(Size of gas meter) | 25 | 72 |
| 144 |
| 288 |
30 | 60 |
| 120 |
| 240 | |
|
|
| ||||
| 35 | 51 |
| 103 |
| 206 |
The chart to the right can be used to determine the | 40 | 45 |
| 90 |
| 180 |
flow rate depending upon the time per revolution and | 45 | 40 |
| 80 |
| 160 |
50 | 36 |
| 72 |
| 144 | |
the size of the gas meter dial. |
|
| ||||
55 | 33 |
| 65 |
| 131 | |
|
|
| ||||
| 60 | 30 |
| 60 |
| 120 |