Lochinvar Comprehensive Crest Service Manual for Efficient Boiler Maintenance

Page 35

Service Manual

2 Maintenance (continued)

Review with owner

1.Review the Crest User’s Information Manual with the owner.

2.Emphasize the need to perform the maintenance schedule specified in the Crest User’s Information Manual (and in this manual as well).

3.Remind the owner of the need to call a licensed contractor should the boiler or system exhibit any unusual behavior.

4.Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.

Cleaning boiler heat exchanger

1.Shut down boiler:

Follow the “To Turn Off Gas to Appliance” instructions for the boiler in Section 9 - Startup.

Do not drain the boiler unless it will be exposed to freezing temperatures. If using freeze prevention fluid in system, do not drain.

2.Allow time for the boiler to cool to room temperature if it has been firing.

3.Remove the top access panel to remove the gas/air manifold assembly.

4.Remove the nuts securing the burner to the burner mounting plate. Remove the burner (FIG. 11-2).

5.Remove the nuts securing the burner mounting plate from the heat exchanger and set aside. Remove the entire burner mounting plate assembly.

￿WARNING The boiler contains ceramic fiber materials. Use care when handling these materials per

instructions on this page. Failure to comply could result in severe personal injury.

6.Use a vacuum cleaner to remove any accumulation on the tube sheet surfaces. Do not use any solvent.

7.Brush the heat exchanger (tube sheet, combustion chamber walls, and tube entry) while dry using a nylon bristle brush. Caution: DO NOT use a metal brush. Re-vacuum the heat exchanger.

8.Finish cleaning using a clean cloth dampened with warm water.

9.Temporarily remove the condensate drain line from the condensate trap and route directly to a drain.

10.Rinse out debris with a low pressure water supply. The water will drain through the condensate connection.

11.Allow the heat exchanger to thoroughly dry.

12.Reconnect the condensate drain line to the condensate trap.

13.Close isolation valves on piping to isolate boiler from system. Attach a hose to the boiler drain and flush boiler thoroughly with clean water by using purging valves to allow water to flow through the water make-up line to the boiler.

14.When securing the burner, be sure to tighten the nuts, but DO NOT over-tighten. Tighten the nuts to a torque setting of no more than 6.2 ft.-lbs. When securing the burner mounting plate be sure to tighten the nuts, but DO NOT over-tighten. Tighten the nuts to a torque setting of no more than 15.5 ft.-lbs.

15.Replace the burner mounting plate assembly and gas/air manifold assembly. Ensure gaskets are in good condition and positioned properly. Restore boiler to operation.

16.Perform start-up and check-out procedures in the Check Flame and Combustion - Section 9 - Startup of the Crest Installation and Operation Manual.

Handling ceramic fiber materials

REMOVAL OF COMBUSTION CHAMBER LINING

￿WARNING The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created to convert the ceramic fibers in this appliance to cristobalite.

The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines.

Avoid breathing dust and contact with skin and eyes.

Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written.

Other types

of

respirators

may

be

needed depending

on

the

job

site

conditions.

 

Current

NIOSH

recommendations

can

be found

on

the

NIOSH

website

at

http://

w w w . c d c . g o v / n i o s h / h o m e p a g e . html. NIOSH approved respirators, manufacturers, and phone numbers are also listed on this website.

Wear long-sleeved, loose fitting clothing, gloves, and eye protection.

Apply enough water to the combustion chamber lining to prevent airborne dust.

Remove the combustion chamber lining from the boiler and place it in a plastic bag for disposal.

Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.

NIOSH stated First Aid.

Eye: Irrigate immediately.

Breathing: Fresh air.

35

Image 35
Contents Models 1.5 2.0 2.5 3.0 Contents Niosh stated First Aid Please read before proceedingHandling ceramic fiber materials When servicing boiler Troubleshooting What is in this manual?Service MaintenanceBoiler piping ServiceHome Screen Control inputs Smart Control ModuleStrip Control outputsHow the control modules operate Access modesGeneral Operation How the boiler operatesTo adjust and save parameters reference FIG Sequence of operation Menu Sub Parameter Name See Min Max Default User InstallerValue Access Parameter tableDelay Ramp BMS Setup Setback HWG Night Pumps Set Points Initial SetupViewable and changeable control parameters Outdoor Reset Ramp Delay Advanced Setup SH/HWG Night Setback Minimum On/Off Time ModBusCascade Cascade OffsetPumps Service Notification Cycles Service NotificationService Notification in Months Service Notification Running Hours8Cascade Screen Service Cascade Screen9Graph ScreenParameter Selection Graph Screen11History ScreenLockout Faults Service History Screen13History ScreenRuntime History 14Service Screen Service ScreenSee the Crest User’s Information Manual for Instructions Maintenance Maintenance and annual startupService technician Owner maintenanceMaintenance Check boiler relief valve Flue vent system and air pipingCheck water system Check expansion tankCheck flame signal Check ignition ground wiringCheck all boiler wiring Check control settingsReview with owner Cleaning boiler heat exchangerCheck control module fuses TroubleshootingBefore troubleshooting Check the followingTroubleshooting Checking temperature sensors No Pump Cutoff Open Low WaterIgnition Anti-cyclingFlame Failure Running Flame Out SequenceFlame Out Unit was running and lost the flame Gas Valve / Relay FailureHigh Limit Open Auto ResetManual Reset High LimitFault Description Corrective Action Outlet Temp Louver Proving Sw OpenFlue Temp High Delta T HighParameters Saved Service BlkOutlet Temp High Rem Ctrl FltFlue Sensor Switch OpenSensor Open Sensor ShortedDifferential TemperatureBurner Supply Writing to Resets Try LaterInternal Fault Too ManyCRC Parameters Watch Dog ErrorNo Error Stored Write EEPromGas Supply Pressure Combustion Analysis ProcedureGas Valve Adjustment Or Obstruction2Gas Valve Adjustment Models 1.5 Gas valve adjustment procedurePage
Related manuals
Manual 60 pages 56.2 Kb Manual 16 pages 3.68 Kb Manual 12 pages 30.87 Kb Manual 20 pages 6.19 Kb Manual 52 pages 37.07 Kb Manual 16 pages 33.86 Kb

3, 2, 3.5, 2.5, 1.5 specifications

Lochinvar is a leader in manufacturing high-efficiency water heating solutions, and their Lochinvar 1.5, 1.3, and 1.0 models exemplify the company's commitment to innovation and performance. These advanced heating systems are designed to meet the diverse needs of commercial and residential applications, providing reliable hot water while ensuring energy efficiency and environmental sustainability.

The Lochinvar 1.5, 1.3, and 1.0 models incorporate cutting-edge technologies that set them apart from traditional water heaters. One of the most notable features is their use of high-efficiency condensing technology, which extracts maximum heat from the combustion process. This process allows the units to achieve high thermal efficiencies, often exceeding 95%, which not only reduces energy costs but also lowers greenhouse gas emissions.

In terms of design, Lochinvar's models are constructed with durable materials, ensuring longevity and reliability in demanding environments. The stainless steel heat exchanger is a key element that contributes to the durability and performance of the units. This material is resistant to corrosion and scale build-up, enhancing the lifespan of the heater and reducing maintenance requirements.

The Lochinvar 1.5, 1.3, and 1.0 models feature advanced control systems that provide precise temperature management and easy operation. The intuitive digital display allows users to monitor performance metrics, temperature settings, and energy consumption with ease. Additionally, these units are equipped with intelligent modulating gas valves that optimize fuel usage based on demand, ensuring efficient operation across various load conditions.

Safety is a priority in the design of Lochinvar's water heaters. The models come with built-in safety features, including flame failure detection, overheat protection, and venting safeguards. These systems work together to ensure the safe operation of the units, giving users peace of mind.

Another characteristic that makes the Lochinvar 1.5, 1.3, and 1.0 models popular among users is their compact design. These units are engineered to fit in tight spaces, making them ideal for installations where space is at a premium. Despite their small footprint, they deliver powerful performance, ensuring that users have access to the hot water they need.

In summary, Lochinvar's 1.5, 1.3, and 1.0 water heating models represent the pinnacle of efficiency, safety, and reliability. With their advanced technologies, durable construction, and user-friendly features, these units are an excellent choice for anyone seeking a high-performance water heating solution.