Lochinvar 400-801 service manual Maintenance Maintenance and annual startup, Service technician

Page 27

Service Manual

2 Maintenance

Maintenance and annual startup

Table 2-1Service and Maintenance Schedules

Service technician

(see the following pages for instructions)

 

General:

 

 

 

• Address reported problems

 

• Inspect interior; clean and vacuum if

 

necessary;

 

 

 

• Clean condensate trap and fill with fresh

 

water

 

 

 

• Check for leaks (water, gas, flue,

 

condensate)

 

 

 

• Verify flue and air lines in good condition

-UP

and sealed tight

 

 

• Check system

water

pressure/system

START

piping/expansion tank

 

 

 

ANNUAL

• Check control settings

 

• Check ignition and flame sense

 

 

electrodes (sand off any deposits; clean

 

and reposition)

 

 

 

• Check wiring and connections

 

• Perform start-up checkout and

 

performance verification per Section 10

 

in the Knight XL Installation and

 

Operation Manual.

 

 

• Flame inspection (stable, uniform)

 

• Flame signal (at least 10 microamps at

 

high fire)

 

 

 

• Clean the heat exchanger if flue

 

temperature is more than 54°F (30°C)

 

above return water temperature.

 

If combustion

or

performance

 

indicate need:

 

 

Clean heat exchanger

Remove and clean burner using compressed air only

Clean the blower wheel

Owner maintenance

(see the Knight XL User’s Information Manual for

instructions)

 

• Check boiler area

Daily

• Check pressure/temperature

 

gauge

 

• Check vent piping

 

• Check air piping

Monthly

• Check air and vent termination

 

 

screens

 

• Check relief valve

 

• Check condensate drain system

 

• Check air vents

 

 

Periodically

• Test low water cutoff (if used)

 

• Reset button (low water cutoff)

 

 

Every

• Check boiler piping (gas and

water) for leaks

6 months

 

 

• Operate relief valve

End

• Shut boiler down (unless boiler

of season

used for domestic hot water)

 

months

 

27

Image 27
Contents Models 400 Contents Please read before proceeding Handling ceramic fiber materialsNiosh stated First Aid When servicing boiler Troubleshooting What is in this manual?Service MaintenanceNear boiler piping ServiceNavigation Dial Knight XL displayLOW Voltage Connection Board Control inputsControl outputs Smart Control ModuleHow the control module operates Access modesGeneral Operation How the boiler operatesOperation Display From previous page Sequence of Operation Button Screen Operation Display Status Display panel menu accessButton Screen Status Operation Display Display panel parameter accessDescription See User Access Installer Access Display Modify Parameter tableMenu Resetoutdoor ANTI-CYCLING Description See User Access Installer Access Display ModifySoftware Version Temperature units C / FViewable and changeable control parameters Time and DateTemperature Settings Data LoggingFunctions DHW Settings Outdoor Reset Anti-Cycling Control modes Cascade Offset Minimum On/Off TimeCirculation pumps DHW Pump Anti-Seize Delay Boiler Pump DelayDHW Pump Delay Boiler Pump Anti-Seize DelayService Notification Maintenance Maintenance and annual startup Service technicianOwner maintenance Maintenance Flue vent system and air piping Check water systemCheck expansion tank Check boiler relief valve Inspect ignition and flame sense electrodes Check ignition ground wiringCheck all boiler wiring Check control settingsModel Kit Part Component Number Description Check flame signalCleaning boiler heat exchanger Review with ownerTest low water flow conditions Test procedureCheck control module fuses TroubleshootingBefore troubleshooting Check the followingUnit Does No DisplayNo Burner OperationResistance Temperature Checking temperature sensorsTemperature Resistance Temperature Resistance Wire Color R/BK and Y Wire Color G and YSystem Pump NoisyNo Pump Boiler PumpTroubleshooting Flame Fail Ign Temp SwOpen Anti-cyclingFlame Sequence Cont’dOutlet Mrhl Outlet ArhlGV/Relay Fan Low/HighFan Speed Low HighInlet Sensor FaultSensor Shorted Louver ProvingFlue Temp Diff Flue Sensor FaultFatal Error Memory ErrorFlue Temp High Delta T HighOutlet Temp Rem Ctrl Flt Service BlkWatch Dog Error No Error StoredCombustion Analysis Procedure Gas valve adjustment procedure ModelModels 601
Related manuals
Manual 56 pages 37.3 Kb

400-801 specifications

The Lochinvar 400-801 is a high-efficiency commercial boiler that embodies advanced engineering and cutting-edge technology. Designed for a variety of commercial applications, this boiler is known for its reliability, efficiency, and robust performance.

One of the standout features of the Lochinvar 400-801 is its high thermal efficiency, which can reach up to 99%. This efficiency not only reduces fuel consumption but also lowers operating costs, making it an economical choice for businesses seeking to minimize overhead. The boiler employs a stainless steel fire-tube heat exchanger that ensures optimal heat transfer and durability. This construction allows for enhanced resistance to corrosion, thereby extending the boiler's lifespan.

The Lochinvar 400-801 is equipped with advanced control technologies that enhance its performance. With its built-in SMART SYSTEM control, users can easily monitor and manage the boiler’s operations, optimizing performance while ensuring ease of use. This control system features a user-friendly interface that provides real-time data, including temperature settings, pressure readings, and operational status, allowing for quick diagnostics and efficient troubleshooting.

Safety is paramount in the design of the Lochinvar 400-801. The boiler includes a comprehensive safety system that incorporates multiple safety interlocks and a venting system that prevents backflow and ensures safe exhaust. Moreover, the unit is designed to operate with minimal noise, making it suitable for environments where noise reduction is crucial.

Installation and maintenance of the Lochinvar 400-801 are straightforward, thanks to its compact design and multiple venting options. The low-profile construction allows for flexibility in placement, making it an ideal fit for tight spaces. Maintenance tasks are simplified with accessible components, minimizing downtime and ensuring the system operates efficiently over its lifespan.

In conclusion, the Lochinvar 400-801 stands out in the commercial boiler market with its blend of efficiency, reliability, and innovation. With its advanced technologies and features, businesses can achieve significant energy savings while ensuring comfortable and consistent heat for various applications. The Lochinvar 400-801 is an investment in quality and performance, backed by a well-established brand in the heating industry. Whether for a new installation or a replacement, this boiler offers a comprehensive solution for commercial heating needs.