Lochinvar 400-801 service manual Test low water flow conditions, Test procedure

Page 32

2 Maintenance

Test low water flow conditions

NOTICE

This test is to be carried out once the

Knight XL boiler is completely piped

 

 

in with adequate gas and water flow.

 

Once the test is completed, ensure

 

that the isolation valve is opened up to

 

allow full water flow.

Test procedure

1.Set the [SH1 SETPOINT:] set point to the max user set point (reference Section 10 of the Knight XL Installation and Operation Manual). Max user set point will allow the boiler to operate without reaching this set point. The boiler will require a load large enough to dissipate a large portion of the heat it is generating.

2.Simulate a call for heat by placing a jumper wire across the enable contacts #19 and 20 on the low voltage terminal strip located at the rear of the unit (FIG. 2-6).

3.Allow the unit to progress through its normal diagnostics and pre-purge programming.

4.Locate the pinhole button below the RESET button on the display board (see page 7). Insert a thin wire (such as a paper clip) into the hole and press the button once and hold for 5 seconds to place the boiler into Service Mode. In Service Mode the boiler will fire at ignition speed and will then modulate up to full fire.

Service Manual

9. When the T reaches 60°F, the control module will turn off the burner. If the control module shuts down, the test was successful.

10.Disconnect the jumper wire from the low voltage terminal strip connected in Step 2.

11.Completely open the isolation valve on the outlet piping of the boiler.

12.Resume operation.

NOTE: This lockout is a soft lockout. Once the T has decreased to an acceptable level and there is a call for heat, the unit will fire again to meet the demand.

Figure 2-6Low voltage terminal strip and enable contacts

LOW VOLTAGE CONNECTION BOARD

ENABLE

CONTACTS

IMG00103

5.Allow the unit to fire and operate until the temperatures stabilize. This occurs when the inlet and outlet

temperatures are rising together and the Delta T ( T) is maintained.

6.When the unit stabilizes, begin to slowly shut off the isolation valve on the outlet piping of the boiler (see FIG. 2-7). This will begin to restrict the flow and simulate a low flow condition.

7.While slowly shutting off the isolation valve, refer to the Status Screens to watch the behavior of the boiler. These screens allow you to monitor the inlet temperature,

outlet temperature, and T.

8. When the T reaches 55˚F, the control will attempt to modulate the firing rate down to protect it from low flow conditions.

Figure 2-7Adjust outlet isolation valve

ADJUST OUTLET

ISOLATION VALVE

ONLY

IMG00098

32

Image 32
Contents Models 400 Contents Niosh stated First Aid Please read before proceedingHandling ceramic fiber materials When servicing boiler What is in this manual? ServiceMaintenance TroubleshootingService Near boiler pipingKnight XL display Navigation DialControl inputs LOW Voltage Connection BoardSmart Control Module Control outputsAccess modes General OperationHow the boiler operates How the control module operatesOperation Display From previous page Sequence of Operation Display panel menu access Button Screen Operation Display StatusDisplay panel parameter access Button Screen Status Operation DisplayMenu Description See User Access Installer Access Display ModifyParameter table Resetoutdoor ANTI-CYCLING See User Access Installer Access Display Modify DescriptionTemperature units C / F Viewable and changeable control parametersTime and Date Software VersionFunctions Temperature SettingsData Logging DHW Settings Outdoor Reset Anti-Cycling Control modes Circulation pumps Cascade OffsetMinimum On/Off Time Boiler Pump Delay DHW Pump DelayBoiler Pump Anti-Seize Delay DHW Pump Anti-Seize DelayService Notification Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check expansion tank Check boiler relief valve Flue vent system and air pipingCheck water system Check ignition ground wiring Check all boiler wiringCheck control settings Inspect ignition and flame sense electrodesCheck flame signal Cleaning boiler heat exchangerReview with owner Model Kit Part Component Number DescriptionTest procedure Test low water flow conditionsTroubleshooting Before troubleshootingCheck the following Check control module fusesNo Display No BurnerOperation Unit DoesChecking temperature sensors Temperature Resistance Temperature ResistanceWire Color R/BK and Y Wire Color G and Y Resistance TemperatureNoisy No PumpBoiler Pump System PumpTroubleshooting Temp Sw OpenAnti-cycling Flame Fail IgnCont’d Flame SequenceOutlet Arhl Outlet MrhlFan Low/High Fan Speed LowHigh GV/RelayFault Sensor ShortedLouver Proving Inlet SensorFlue Sensor Fault Fatal ErrorMemory Error Flue Temp DiffOutlet Temp Flue Temp HighDelta T High Service Blk Watch Dog ErrorNo Error Stored Rem Ctrl FltCombustion Analysis Procedure Models 601 Gas valve adjustment procedureModel
Related manuals
Manual 56 pages 37.3 Kb

400-801 specifications

The Lochinvar 400-801 is a high-efficiency commercial boiler that embodies advanced engineering and cutting-edge technology. Designed for a variety of commercial applications, this boiler is known for its reliability, efficiency, and robust performance.

One of the standout features of the Lochinvar 400-801 is its high thermal efficiency, which can reach up to 99%. This efficiency not only reduces fuel consumption but also lowers operating costs, making it an economical choice for businesses seeking to minimize overhead. The boiler employs a stainless steel fire-tube heat exchanger that ensures optimal heat transfer and durability. This construction allows for enhanced resistance to corrosion, thereby extending the boiler's lifespan.

The Lochinvar 400-801 is equipped with advanced control technologies that enhance its performance. With its built-in SMART SYSTEM control, users can easily monitor and manage the boiler’s operations, optimizing performance while ensuring ease of use. This control system features a user-friendly interface that provides real-time data, including temperature settings, pressure readings, and operational status, allowing for quick diagnostics and efficient troubleshooting.

Safety is paramount in the design of the Lochinvar 400-801. The boiler includes a comprehensive safety system that incorporates multiple safety interlocks and a venting system that prevents backflow and ensures safe exhaust. Moreover, the unit is designed to operate with minimal noise, making it suitable for environments where noise reduction is crucial.

Installation and maintenance of the Lochinvar 400-801 are straightforward, thanks to its compact design and multiple venting options. The low-profile construction allows for flexibility in placement, making it an ideal fit for tight spaces. Maintenance tasks are simplified with accessible components, minimizing downtime and ensuring the system operates efficiently over its lifespan.

In conclusion, the Lochinvar 400-801 stands out in the commercial boiler market with its blend of efficiency, reliability, and innovation. With its advanced technologies and features, businesses can achieve significant energy savings while ensuring comfortable and consistent heat for various applications. The Lochinvar 400-801 is an investment in quality and performance, backed by a well-established brand in the heating industry. Whether for a new installation or a replacement, this boiler offers a comprehensive solution for commercial heating needs.