3 Troubleshooting (continued)

Checking temperature sensors

The boiler temperature sensors (inlet water, outlet water, system water, flue, and outdoor air) are all resistance type devices. The following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor

It is important to note that the flue and outlet water sensors have two temperature sensing devices in one housing. These devices are designated as S1a/S1b, outlet sensor and S3a/S3b, flue sensor. Please reference the wiring diagram in the Knight XL Installation and Operation Manual for correct terminal location.

Table 3-2A - Inlet Water/System Sensor Resistance vs. Temperature

Temperature Resistance Temperature Resistance

50

18,780

158

1,990

68

12,263

176

1,458

86

8,194

194

1,084

104

5,592

212

817

1223,893

1402,760

Table 3-2B - Outdoor Air Sensor Resistance vs. Temperature

Temperature Resistance Temperature Resistance

-50

490,813

20

46,218

-40

336,606

30

34,558

-30

234,196

40

26,099

-20

165,180

50

19,900

10

118,018

60

15,311

0

85,362

70

11,883

10

62,465

80

9,299

Table 3-2C - Outlet Water Sensor Resistance vs. Temperature

 

 

 

S1a

 

 

 

 

S1b

 

 

 

 

 

(Wire Color - R/BK and Y)

 

 

 

 

(Wire Color - G and Y)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

 

Resistance

 

Temperature

 

Resistance

Temperature

 

Resistance

 

Temperature

 

Resistance

 

 

50

19,553

158

2,004

50

40,030

158

3,478

 

 

68

12,690

176

1,464

68

25,030

176

2,492

 

 

86

8,406

194

1,084

86

16,090

194

1,816

 

 

104

5,715

212

816

104

10,610

212

1,344

 

 

122

3,958

 

 

 

 

122

7,166

 

 

 

 

 

 

140

2,786

 

 

 

 

140

4,943

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 3-2D - Flue Sensor Resistance vs. Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S3a

 

 

 

 

S3b

 

 

 

 

 

 

(Wire Color - W/B and Y)

 

 

 

 

(Wire Color - PR and Y)

 

 

 

 

Temperature

 

Resistance

 

Temperature

Resistance

Temperature

 

Resistance

 

Temperature

 

Resistance

 

 

50

 

40,030

 

158

 

3,478

50

 

258,500

 

158

 

16,870

 

 

68

 

25,030

 

176

 

2,492

68

 

125,500

 

176

 

12,000

 

 

86

 

16,090

 

194

 

1,816

86

 

80,220

 

194

 

8,674

 

 

104

 

10,610

 

212

 

1,344

104

 

52,590

 

212

 

6,369

 

 

122

 

7,166

 

 

 

 

122

 

35,270

 

 

 

 

 

 

140

 

4,943

 

 

 

 

140

 

24,160

 

 

 

 

 

35

Image 35
Contents Models 400 Contents Niosh stated First Aid Please read before proceedingHandling ceramic fiber materials When servicing boiler Troubleshooting What is in this manual?Service MaintenanceNear boiler piping ServiceNavigation Dial Knight XL displayLOW Voltage Connection Board Control inputsControl outputs Smart Control ModuleHow the control module operates Access modesGeneral Operation How the boiler operatesOperation Display From previous page Sequence of Operation Button Screen Operation Display Status Display panel menu accessButton Screen Status Operation Display Display panel parameter accessMenu Description See User Access Installer Access Display ModifyParameter table Resetoutdoor ANTI-CYCLING Description See User Access Installer Access Display ModifySoftware Version Temperature units C / FViewable and changeable control parameters Time and DateFunctions Temperature SettingsData Logging DHW Settings Outdoor Reset Anti-Cycling Control modes Circulation pumps Cascade OffsetMinimum On/Off Time DHW Pump Anti-Seize Delay Boiler Pump DelayDHW Pump Delay Boiler Pump Anti-Seize DelayService Notification Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check expansion tank Check boiler relief valve Flue vent system and air pipingCheck water system Inspect ignition and flame sense electrodes Check ignition ground wiringCheck all boiler wiring Check control settingsModel Kit Part Component Number Description Check flame signalCleaning boiler heat exchanger Review with ownerTest low water flow conditions Test procedureCheck control module fuses TroubleshootingBefore troubleshooting Check the followingUnit Does No DisplayNo Burner OperationResistance Temperature Checking temperature sensorsTemperature Resistance Temperature Resistance Wire Color R/BK and Y Wire Color G and YSystem Pump NoisyNo Pump Boiler PumpTroubleshooting Flame Fail Ign Temp SwOpen Anti-cyclingFlame Sequence Cont’dOutlet Mrhl Outlet ArhlGV/Relay Fan Low/HighFan Speed Low HighInlet Sensor FaultSensor Shorted Louver ProvingFlue Temp Diff Flue Sensor FaultFatal Error Memory ErrorOutlet Temp Flue Temp HighDelta T High Rem Ctrl Flt Service BlkWatch Dog Error No Error StoredCombustion Analysis Procedure Models 601 Gas valve adjustment procedureModel
Related manuals
Manual 56 pages 37.3 Kb

400-801 specifications

The Lochinvar 400-801 is a high-efficiency commercial boiler that embodies advanced engineering and cutting-edge technology. Designed for a variety of commercial applications, this boiler is known for its reliability, efficiency, and robust performance.

One of the standout features of the Lochinvar 400-801 is its high thermal efficiency, which can reach up to 99%. This efficiency not only reduces fuel consumption but also lowers operating costs, making it an economical choice for businesses seeking to minimize overhead. The boiler employs a stainless steel fire-tube heat exchanger that ensures optimal heat transfer and durability. This construction allows for enhanced resistance to corrosion, thereby extending the boiler's lifespan.

The Lochinvar 400-801 is equipped with advanced control technologies that enhance its performance. With its built-in SMART SYSTEM control, users can easily monitor and manage the boiler’s operations, optimizing performance while ensuring ease of use. This control system features a user-friendly interface that provides real-time data, including temperature settings, pressure readings, and operational status, allowing for quick diagnostics and efficient troubleshooting.

Safety is paramount in the design of the Lochinvar 400-801. The boiler includes a comprehensive safety system that incorporates multiple safety interlocks and a venting system that prevents backflow and ensures safe exhaust. Moreover, the unit is designed to operate with minimal noise, making it suitable for environments where noise reduction is crucial.

Installation and maintenance of the Lochinvar 400-801 are straightforward, thanks to its compact design and multiple venting options. The low-profile construction allows for flexibility in placement, making it an ideal fit for tight spaces. Maintenance tasks are simplified with accessible components, minimizing downtime and ensuring the system operates efficiently over its lifespan.

In conclusion, the Lochinvar 400-801 stands out in the commercial boiler market with its blend of efficiency, reliability, and innovation. With its advanced technologies and features, businesses can achieve significant energy savings while ensuring comfortable and consistent heat for various applications. The Lochinvar 400-801 is an investment in quality and performance, backed by a well-established brand in the heating industry. Whether for a new installation or a replacement, this boiler offers a comprehensive solution for commercial heating needs.