Lochinvar 400-801 service manual Gas valve adjustment procedure, Models 601

Page 47

3 Troubleshooting (continued)

Gas valve adjustment procedure

If adjustment of the gas valve is deemed necessary, use the following procedures: (Note: The procedures below are model specific.)

CAUTION

Under normal operating conditions this

valve should not need adjusting.

Model 400

Locate the throttle adjustment screw on the top of the gas valve, see FIG. 3-2. Using a screwdriver, turn the screw 1/8 turn counterclockwise to increase CO2 levels or 1/8 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 46 of this manual to measure the combustion.

If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3-6 on page 46 or replace the gas valve.

Figure 3-2Gas Valve Adjustment: Model 400

THROTTLE ADJUSTMENT

SCREW

Model 501

Locate the throttle adjustment screw on top of the gas valve, see FIG. 3-3. Using a screwdriver, turn the screw a 1/4 turn counterclockwise to increase CO2 levels or a 1/4 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 46 of this manual to measure the combustion.

If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3-6 on page 46 or replace the gas valve.

Service Manual

Figure 3-3Gas Valve Adjustment: Model 501

Models 601 - 801

Locate the throttle adjustment screw on top of the gas valve, see FIG. 3-4. Using an Allen wrench, turn the screw a 1/4 turn counterclockwise to increase CO2 levels or a 1/4 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 46 of this manual to measure the combustion.

If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3-6 on page 46 or replace the gas valve.

Figure 3-4Gas Valve Adjustment: Models 601 - 801

THROTTLE

ADJUSTMENT

SCREW

(REMOVE BLUE CAP)

47

Image 47
Contents Models 400 Contents Niosh stated First Aid Please read before proceedingHandling ceramic fiber materials When servicing boiler Troubleshooting What is in this manual?Service MaintenanceNear boiler piping ServiceNavigation Dial Knight XL displayLOW Voltage Connection Board Control inputsControl outputs Smart Control ModuleHow the control module operates Access modesGeneral Operation How the boiler operatesOperation Display From previous page Sequence of Operation Button Screen Operation Display Status Display panel menu accessButton Screen Status Operation Display Display panel parameter accessMenu Description See User Access Installer Access Display ModifyParameter table Resetoutdoor ANTI-CYCLING Description See User Access Installer Access Display ModifySoftware Version Temperature units C / FViewable and changeable control parameters Time and DateFunctions Temperature SettingsData Logging DHW Settings Outdoor Reset Anti-Cycling Control modes Circulation pumps Cascade OffsetMinimum On/Off Time DHW Pump Anti-Seize Delay Boiler Pump DelayDHW Pump Delay Boiler Pump Anti-Seize DelayService Notification Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check expansion tank Check boiler relief valve Flue vent system and air pipingCheck water system Inspect ignition and flame sense electrodes Check ignition ground wiringCheck all boiler wiring Check control settingsModel Kit Part Component Number Description Check flame signalCleaning boiler heat exchanger Review with ownerTest low water flow conditions Test procedureCheck control module fuses TroubleshootingBefore troubleshooting Check the followingUnit Does No DisplayNo Burner OperationResistance Temperature Checking temperature sensorsTemperature Resistance Temperature Resistance Wire Color R/BK and Y Wire Color G and YSystem Pump NoisyNo Pump Boiler PumpTroubleshooting Flame Fail Ign Temp SwOpen Anti-cyclingFlame Sequence Cont’dOutlet Mrhl Outlet ArhlGV/Relay Fan Low/HighFan Speed Low HighInlet Sensor FaultSensor Shorted Louver ProvingFlue Temp Diff Flue Sensor FaultFatal Error Memory ErrorOutlet Temp Flue Temp HighDelta T High Rem Ctrl Flt Service BlkWatch Dog Error No Error StoredCombustion Analysis Procedure Models 601 Gas valve adjustment procedureModel
Related manuals
Manual 56 pages 37.3 Kb

400-801 specifications

The Lochinvar 400-801 is a high-efficiency commercial boiler that embodies advanced engineering and cutting-edge technology. Designed for a variety of commercial applications, this boiler is known for its reliability, efficiency, and robust performance.

One of the standout features of the Lochinvar 400-801 is its high thermal efficiency, which can reach up to 99%. This efficiency not only reduces fuel consumption but also lowers operating costs, making it an economical choice for businesses seeking to minimize overhead. The boiler employs a stainless steel fire-tube heat exchanger that ensures optimal heat transfer and durability. This construction allows for enhanced resistance to corrosion, thereby extending the boiler's lifespan.

The Lochinvar 400-801 is equipped with advanced control technologies that enhance its performance. With its built-in SMART SYSTEM control, users can easily monitor and manage the boiler’s operations, optimizing performance while ensuring ease of use. This control system features a user-friendly interface that provides real-time data, including temperature settings, pressure readings, and operational status, allowing for quick diagnostics and efficient troubleshooting.

Safety is paramount in the design of the Lochinvar 400-801. The boiler includes a comprehensive safety system that incorporates multiple safety interlocks and a venting system that prevents backflow and ensures safe exhaust. Moreover, the unit is designed to operate with minimal noise, making it suitable for environments where noise reduction is crucial.

Installation and maintenance of the Lochinvar 400-801 are straightforward, thanks to its compact design and multiple venting options. The low-profile construction allows for flexibility in placement, making it an ideal fit for tight spaces. Maintenance tasks are simplified with accessible components, minimizing downtime and ensuring the system operates efficiently over its lifespan.

In conclusion, the Lochinvar 400-801 stands out in the commercial boiler market with its blend of efficiency, reliability, and innovation. With its advanced technologies and features, businesses can achieve significant energy savings while ensuring comfortable and consistent heat for various applications. The Lochinvar 400-801 is an investment in quality and performance, backed by a well-established brand in the heating industry. Whether for a new installation or a replacement, this boiler offers a comprehensive solution for commercial heating needs.