Burnham SERIES 2 manual Sequence of Operation Normal Operation

Page 18

Figure 14: Wiring Diagram, 24 Volt Standing Pilot with Continuous or Gravity Circulation

SEQUENCE OF OPERATION

NORMAL OPERATION

1.When the thermostat call for heat, the vent damper will open (see paragraphs 17A through 17D). The gas valve is energized allowing main gas to flow and operation of the main burners.

2.Where condensation of flue gas is encountered in boiler flues a reverse acting circulator control should be installed to stop the circulator before the boiler water temperature drops to that which flue gas condensation may occur.

3.After the thermostat is satisfied the main valve will close and main burner flames will be extinguished. The vent damper will close (see paragraph 17E). If the boiler is so equipped, circulator will continue to run.

SAFETY SHUTDOWN

1.High Limit Switch

In the event excessive boiler water temperature is developed the high limit switch will open interrupting power to the gas valve. The main burners will be extinguished immediately. Normal operation will be resumed when the boiler water temperature drops to a point where the high limit switch closes.

2.Blocked Vent Switch

In the event excessive blockage in the vent system is developed the blocked vent switch will open interrupt- ing power to the gas valve. The main burners will be extinguished immediately and the vent damper will remain open until the thermostat is turned off. The source of blockage must be corrected by trained and skilled personnel from a qualified service agency before resetting switch.

3.Flame Rollout Switch

In the event excessive blockage in the boiler section flue passageways is developed the flame rollout switch will open interrupting power to the gas valve. The main burners will be extinguished immediately and the vent damper will remain open until the thermostat is turned off. If the flame rollout switch is activated do not attempt to place the boiler in operation. The source of the blockage must be corrected and the flame rollout switch replaced by trained and skilled person- nel from a qualified service agency.

4.Pilot

The thermocouple proves pilot flame and in the absence of such within 45-90 seconds causes the combination gas valve, which is equipped with a 100% shut-off provision, to be de-energized, thus, preventing main gas or pilot gas flow.

18

Image 18
Contents Price $3.00 PartNo.81417032R10-11/99Page 202 Clearances CanadaRemove Crate Determine type of space. Divide Volume by Total Input Boilerpiping Oxygen CorrosionLength Inch w.c. Pressure Drop Feet Installblockedventswitch Equivalent Length of FittingsRefer to in this manual Ifanexistingboilerisremoved Both of the aforementioned standards, AnsiSeal any unused openings in the common venting system Plug-in Damper Installation 54/ANSIZ223.1 VentdampersequenceofoperationEffikal and Johnson Damper Vent Damper Schematic Wiring Diagram Safety Shutdown Sequence of Operation Normal OperationPage Vent Damper will close see Paragraph 17E Page Pilot Sequence of Operation Normal Operation Wiring Schematic, Zone Valves Section II Operating Instructions Initial StartTop View of SV9500, SV9600 VR Gas Valves 21460147 For Your Safety Read Before Operating 81460177 Lighting InstructionsCheck GAS Input Rate to Boiler LP Gas InputCheck Pilot Burner Flame Check Ignition System Safety SHUT-OFF Device Move JumperCombustion Chamber BURN-OFF Typical Pilot Flame, Honeywell Q3450 Troubleshooting Guide, Honeywell Intermittent Ignition Section III Service Burner Cleaning and Installation Lubrication Manifold and Main BurnersPilot Burner and Gas Valve Burnham Corporation Regional Offices Contact Regional Office Indicated for your StateSection Assembly and Canopy Group Canopy Assembly Base Assembly Key Description Boiler QtyUSS Manifold and Main Burners Inch Main Burners Key Description Quantity Manifold and Main Burners 1 Inch Main Burners OnlyManifold and Main Burners Mm Main Burners Manifold and Main Burners 50 mm Main Burners Only Volt Continuous Ignition Standing Pilot Natural Gas Only 40MM Main Burners onlyIntermittent Ignition Only Volt Continuous Ignition Standing Pilot LP Gas OnlyNatural G as, Sea Level to 2000 Ft Burner Only 40mm Burner Only Burner Only 40mm Burner Only 40mm Burners Only Service Notes Key Quantity Description Key Description Quantity Water Trim Nipple, 1¼ NPT x 806600005 Transformer Continuous and Gravity Circulation Only Draft Hood Carton Vent Damper Carton U.S.A. Standard Canada OptionalVent Reducer