Ariston 47-116-08. 47-116-09, 47-116-13, 41-116-01 KW 27 kW Exhaust/Air Maximum Extension

Page 14

In calculating the lengths of the pipes, the maximum length must also take into consideration the values for the exhaust/air intake end terminals, as well as 90° elbows for coaxial systems.

The C52 types must comply with the following requirements:

1.The discharge/intake vent pipes must have the same diameter of ø 80 mm.

2.The maximum combined flue length is 17 m for Models Genus 23/27 MFFI/RFFI and 15 m for Model Genus 30 MFFI. In this case the minimum length for the air intake pipe is 1 meter; the maximum length of ver tical exhaust pipe must be a maximum of 12 m.

3.If an elbow is inserted into the discharge/ventilation system, the calculation of the overall extension must take into consideration the values for each curve, as indicated in the table.

4.The exhaust pipe must extend at least 0.5 m above the ridge of the roof if it is located on a side other than that for the air intake (this is not obligatory if the exhaust and air intake pipes are located on the same side of the building).

(*) L = Length of Piping

 

 

Twin Pipe Systems

 

 

Systems

Coaxial

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C52 (xy)

C42 (xy)

C32 (xy)

C12 (xy)

 

C42 (xx)

C32 (xx)

C12 (xx)

 

 

 

Exhaust Type

 

 

 

 

 

 

 

 

 

 

 

 

 

17 m

54 m

54 m

54 m

23 kW

4 m

4 m

4 m

23 kW - 27 kW

 

Exhaust/Air

Maximum Extension

17 m

46 m

46 m

46 m

27 kW

15 m

50 m

50 m

50 m

30 kW

3 m

3 m

3 m

30kW

 

 

 

 

 

 

 

 

 

 

 

 

 

ø 80

ø 80

ø 80

ø 80

 

ø 60/100

ø 60/100

ø 60/100

(mm)

Pipes

Diameter

 

 

 

 

 

 

 

 

 

 

 

 

of

 

 

 

 

 

 

 

 

 

 

 

 

L < 7 m

L < 7 m

L < 7 m

L < 7 m

 

L * < 0.5 m

L * < 0.5 m

L * < 0.5 m

23kW

42 mm

Use of Restrictor

L <

L <

L <

L <

 

L * <

L * <

L * <

27

5 m

5 m

5 m

5 m

 

0.5 m

0.5 m

0.5 m

kW

 

 

on Discharge Side

L < 7.5 m

L < 7.5 m

L < 7.5 m

L < 7.5 m

 

L * < 0.5 m

L * < 0.5 m

L * < 0.5 m

30 kW

45 mm

 

 

 

 

 

 

 

 

 

 

 

 

L > 4.9 m

L > 4.9 m

L > 4.9 m

L > 4.9 m

 

 

 

 

23kW

 

 

Risk of Condensation

L < 5.3 m

L > 6.5 m

L > 6.5 m

L > 6.5 m

 

 

 

 

27 kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L > 4.5 m

L > 4.5 m

L > 4.5 m

L > 4.5 m

 

 

 

 

30 kW

 

 

Forming

 

 

 

 

 

 

 

 

 

 

 

 

 

14

B004

Image 14
Contents Leave These Instructions Adjacent to the GAS Meter Table of Contents General Information General InformationTechnical Information Genus 27 Rffi System Overall ViewSiting the Appliance InstallationReference Standards Overall Dimensions ClearancesGas Connection Mounting the ApplianceElectrical Connection Pipe Work Safety Valve DischargeWater Connections View of the Boiler Connections By-passMains Water Feed Central Heating Flue ConnectionsAir Release Points FillingTower Flue Components 80 mm B004 KW 27 kW Exhaust/Air Maximum Extension Room Thermostat Connection Electrical Diagram ColoursGenus 27 Rffi System CN202 Water Circuit Diagram Removing the Casing CommissioningInitial Preparation Filling the Heating SystemControl Panel Summer/Winter/Flue Analysis ModesInitial Start-up Operational Adjustments Checks to be run before initial start-up are as followsCombustion Analysis Fume Discharge MonitoringBoiler Safety Systems GAS Adjustments Changing the Type of GasMaintenance Wiring Diagram for Two Heating Zones MiscellaneousWiring Diagram for Connection to Ariston Unvented Cylinder TypicalB004 B004 B004 Technical Service Hotline 01494

47-116-08. 47-116-09, 41-116-01, 47-116-13 specifications

Ariston has cemented its reputation as a pioneer in the realm of heating and hot water solutions, consistently delivering quality products that marry efficiency with performance. Among their impressive lineup, models like the Ariston 47-116-13, 41-116-01, 47-116-08, and 47-116-09 stand out due to their innovative technologies and user-centric designs.

One of the defining features of these Ariston models is their advanced heating technology, which efficiently delivers hot water while minimizing energy consumption. They utilize a robust insulation system that prevents heat loss, ensuring that water stays hot for longer periods. This not only enhances convenience but also contributes to lower energy bills.

The 47-116-13 model showcases Ariston's commitment to smart engineering with its built-in digital display. This feature allows users to monitor and adjust temperatures effortlessly, ensuring customized comfort. Additionally, the model is equipped with a sleek design, making it a stylish addition to any home setting.

The 41-116-01 model emphasizes user-friendliness through its intuitive controls and compact design, making it suitable for various installations, from small apartments to larger homes. Its lightweight construction facilitates easier handling and installation, further enhancing its appeal.

In contrast, the 47-116-08 model is designed with durability in mind, featuring a corrosion-resistant tank that promises longevity. This model also incorporates advanced heating elements that ensure rapid heating, allowing users to enjoy hot water whenever they need it.

Finally, the 47-116-09 resonates with environmentally conscious consumers, as it is designed to be energy-efficient while providing reliable performance. This model utilizes a smart control system that adapts to user habits, ensuring optimal energy usage without sacrificing comfort.

In summary, Ariston's 47-116-13, 41-116-01, 47-116-08, and 47-116-09 models exemplify the brand's dedication to creating high-performance, energy-efficient heating solutions. With features such as advanced heating technology, user-friendly controls, and durable materials, these models are ideal for anyone looking to enhance their hot water experience while enjoying significant cost savings and reduced environmental impact.