Crown Boiler MWC116ELL, MWC Series, MWC116ENL, MWC116ENT, MWC116ELT manual VI Air for Ventilation

Page 12

VI Air for Ventilation

WARNING

Outdoor combustion air must be piped to the air intake. Never pipe combustion air from areas containing contaminates such as areas where swimming pool chemicals are stored. Contaminated combustion air will damage the boiler and may cause property damage, personal injury or loss of life.

Air for combustion and ventilation, of the National Flue Gas Code, ANSI Z223.1/NFPA 54 CAN/CSA B 149.1 Natural Gas and Propane Installation Code, or applicable provisions of the local building codes.

Air for combustion must always be obtained directly from outdoors, however sufficient air for ventilation must still be provided in the boiler room. Air for ventilation is required to keep various boiler components from overheating and is always obtained from indoors. To ensure an adequate ventilation air supply, perform the following steps:

Step 1: Determine whether the boiler is to be installed in a confined space - A confined space is defined by

the National Fuel Gas Code,ANSI Z223.1./NFPA 54 and/or CAN/CSA B 149.1 Natural Gas and Propane Installation Code. as having a volume less than 50 cubic feet per 1000 BTU/hr input of all appliances

installed in that space. To determine whether the boiler room is a confined space:

A.Total the input of all appliances in the boiler room in thousands of BTU/hr. Round the result to the next highest 1000 BTU/hr.

B.Find the volume of the room in cubic feet. The volume of the room in cubic feet is:

Length (ft) x width (ft) x ceiling height (ft)

In calculating the volume of the boiler room, consider the volume of adjoining spaces only if no doors are installed between them. If doors are installed between the boiler room and an adjoining space, do not consider the volume of the adjoining space, even if the door is normally left open.

C. Divide the volume of the boiler room by the input in thousands of BTU/hr. If the result is less than 50, the boiler room is a confined space.

Example:

A MWC116 and a water heater are to be installed in a room measuring 6ft – 3 in x 7ft with an 8 ft ceiling. The water heater has an input of 30000 BTU/hr:

Total input in thousands of BTU/hr = (116000 BTU/hr + 30000 BTU/hr) / 1000 = 146 MBTU/hr

Volume of room = 6.25 ft x 7 ft x 8 ft = 350 ft3

350/146 = 2.40. Since 2.33 is less than 50, the boiler room is a confined space.

Step 2a: If the boiler is to be placed in a confined space, provide two openings into the boiler room, one near the floor and one near the ceiling. The top edge of the upper opening must be within 12” of the ceiling and the bottom edge of the lower opening must be within 12” of the floor (Fig 6.1). The minimum opening dimension is

3inches.

If the MWC boiler is the only gas-burning appliance in the boiler room, these openings must each have a minimum free area of 54 square inches.

If other gas-burning appliances are in the boiler room, size the openings in accordance with the appliance manufacturer’s instructions or the National Fuel Gas Code ANSI Z223.1.

/NFPA 54 and/or CAN/CSA B 149.1. Minimum opening free area is

54 square inches even if opening requirements for other appliances are less.

10

Image 12
Contents MWC Series Page Table of Contents Product Description Key ComponentMWC Boiler Principle Components II Specifications RatingsMaximum Vent Lengths Other SpecificationsIII Before Installing Clearances To Combustible Or Non-combustible Material Mounting The Boiler Wall Mounting Hole Locations Boiler Mounting VI Air for Ventilation Page VII Venting Vent System DesignPage Horizontal Concentric Venting Vent Options 3a Crown Concentric 60/100 Vent Components Vent Options 1,2 3b Crown Concentric 80/125 Vent Components Vent Options 3,54c Positioning Vent Terminal Under Overhangs Vent/ Air Intake Fitting Equivalent Length Vertical Concentric Vent System Vent Option Removing an Existing Boiler From a Common Chimney All cuts are square and allow for proper insertion 21 Dimension L 22 Cutting Outer Pipe 25 Attaching 60/100mm Terminal Section 30 Installation Of 80/125 Adaptor On Boiler 31a Cuttable Straight Section 32 Cutting Straight Pipe 33a Joining Cuttable Pipe 34a Dimension L, 80/125mm Horizontal Terminal 34c Cutting Inner Pipe Of 80/125mm Horizontal Terminal 35a Dimension H 35b Cutting Vertical Terminal 36 Chimney Chase Installation Condensate Trap and Drain Line 40 Condensate Piping ArrangementViii Gas Piping Gas Connection To Boiler IX System Piping Standard PipingBasic Piping Relief Valve Installation Piping for Special Situations Internal Boiler PipingPrimary-Secondary Piping MWC116E*T Combi Internal Boiler-Side Piping Schematic MWC116E*L Heat-Only Internal Piping Schematic Domestic Water Piping DHW Piping MWC116E*T Combi Internal DHW-Side Piping Schematic XI Wiring Field Supplied Box End Boiler End Location of Terminal Blocks and 7/8 Hole for Whip Field Wiring 120VAC Thermostat Internal Boiler Wiring XII Start-up and Checkout Location of Automatic Air Vent CapLocation of Circulator Shaft Cover Control Panel Page Inner Cover Removal For Your Safety Read Before Operating MWC Series Lighting and Operating InstructionsHigh Fire Combustion Readings Xiii Operation DHWHeating System Knob Sequence of Operation Also Refer to Figures 9.7, 9.8, 10.3 See Part XV for Error Codes Flash Codes During Normal OperationXIV. Service and Maintenance Removing Combustion Chamber Cover Service Notes InducerCondensate Trap Removal XV. Troubleshooting No Error Code DisplayedError Codes Lamp Number Flame Meaning Corrective ActionFlow Chart for Isolating Limit and APS Errors See Table XVI Parts Flow group and three way diverter valve Model combi Flow and return groups Model c.h. only Pump and main circuit assembly Model combi Pump and main circuit assembly Model c.h. only Gas assembly Connection pipes Control panel and ignition device Model combi Control panel and ignition device Model c.h. only Wiring Model combi Wiring Model c.h. only Fan, combustion chamber and case panels Description Spare part code Description Spare part code Description Spare part code Installation of Carbon Monoxide Detectors Approved Carbon Monoxide Detectors 11/07

MWC116ENL, MWC116ELL, MWC116ELT, MWC116ENT, MWC Series specifications

Crown Boiler's MWC Series represents a commendable choice in the realm of residential and light commercial heating solutions. Specifically, models like the MWC116ENT, MWC116ELT, MWC116ELL, and MWC116ENL stand out due to their exceptional performance, reliability, and innovative features.

At the core of the MWC Series lies a robust cast iron boiler construction designed to withstand the test of time. This material not only provides durability but also enhances heat retention, thereby increasing the system's efficiency. Each model in this series is designed for natural gas or propane fuel types, ensuring flexibility based on availability and user preference.

A notable feature of the MWC116 models is the efficient heat exchanger, which enables rapid heating of water for both space heating and domestic hot water applications. With a heating capacity of 116,000 BTUs, these boilers deliver ample warmth for mid-sized homes or light commercial settings, making them a versatile option for various applications.

The MWC116ENT model is equipped with an energy-efficient electronic ignition system, which enhances reliability and efficiency. This technology reduces energy consumption, providing users with cost savings on their utility bills. Similarly, the MWC116ELT model boasts an integrated aquastat that regulates water temperature, ensuring optimal performance and comfort.

For those requiring increased venting options, the MWC116ELL model includes advanced horizontal venting capabilities, allowing for flexible installation in various environments. This feature aids in overcoming space limitations and facilitating optimal combustion conditions. The MWC116ENL, on the other hand, features a low NOx emissions configuration, making it an environmentally conscious choice for users concerned about their carbon footprint.

User-friendly controls are a characteristic hallmark of the MWC Series, enabling straightforward operation and easy adjustments. The boilers come equipped with a digital display that provides critical system information and diagnostics, streamlining maintenance efforts.

Overall, the Crown Boiler MWC Series, particularly models like the MWC116ENT, MWC116ELT, MWC116ELL, and MWC116ENL, offer an impressive blend of efficiency, flexibility, and advanced technology. These units are designed to meet contemporary heating demands while ensuring sustainable operation, making them a wise investment for comfort and performance in residential and light commercial applications alike. With reliable construction and innovative features, the MWC Series remains a top choice for those seeking effective heating solutions.