Crown Boiler MWC116ELL, MWC Series Sequence of Operation Also Refer to Figures 9.7, 9.8, 10.3

Page 62

Sequence of Operation (Also Refer to Figures 9.7, 9.8, 10.3, 11.7)

1)Upon a call for heat from the room thermostat, the circulator is started.

2)If the differential pressure switch connected between the supply and return sees a pressure in excess of 5.1 ft w.c., it closes, allowing the start sequence to continue. If the switch does not see 5.1ft w.c. after 180seconds, the boiler goes into lockout.

3)If the common and normally closed contacts on the air pressure switch are made, the inducer starts.

4)The air pressure switch measures the difference between the combustion air pressure in the cabinet and the negative pressure generated at a venturi located in the inducer discharge. In this way it measures the air flow through the boiler. If the pressure across the air pressure switch exceeds approximately 0.64” w.c., the switch will close. If the air pressure does not close after 4 minutes of inducer operation, the boiler will go into lockout.

5)After the air pressure switch closes, current can pass through the normally closed supply water and flue gas safety limits to the ignition module, initiating a call for burner operation.

6)The ignition module generates an ignition spark and opens the valve. The presence of flame is detected through a separate flame rod. If no flame is detected after 10 seconds, the boiler will go into lockout. If the flame is proven and this proof is subsequently lost at any point during the burner cycle, the boiler will attempt to re-light once, then go into lockout.

7)When responding to a call for heat, the boiler will attempt to maintain the target supply temperature selected by the Heating System Knob. The boiler does this by monitoring the supply temperature sensor shown in Figure 9.7/9.8 and modulating the input based on the difference between the current supply temperature and the target supply temperature. Modulation is achieved by varying a 0-24VDC voltage across a coil on the gas valve regulator (0V=minimum input).

8)If the supply water temperature exceeds the target supply temperature while the call for heat is present, the burner will shut down and the circulator will continue to run. The burner will relight when the supply temperature drops below the target temperature.

9)If the supply temperature exceeds 221F (which should never happen unless there is a problem with the supply sensor), the manual reset supply water high limit will open.

10)If the condensate trap becomes blocked, the condensate level will rise to the point where it covers two electrical contacts: a contact connected to ground, and a contact in the flame rod lead. The condensate will complete an electrical circuit between these two contacts, grounding out the unrectified flame signal. This will be detected by the ignition module as a loss of flame and result in a lockout.

11)If the flue temperature exceeds 248F, the manual reset supply water high limit will open. This protects the PPs venting from excessive temperatures.

12)When responding to a call for heat, combi boilers use exactly the same sequence of operation as heat-only models. When a combi boiler receives a call for domestic hot water (DHW), it responds as follows:

a)The flow switch shown in Figure 11.7 detects a call for DHW draw when a hot water fixture is opened having a flow rate in excess of approximately 0.5 GPM.

b)The main control drives the 3-way diverting valve so that all boiler water flow is directed though the plate heat exchanger.

c)If not already running, the circulator starts

d)The boiler fires after going through the same start sequence described in steps (3-6) above.

e)The boiler monitors the exiting DHW temperature using the sensor shown in Figure 11.7. The boiler’s microprocessor control determines the target boiler supply temperature that is needed to meet the DHW demand and modulates the input accordingly.

60

Image 62
Contents MWC Series Page Table of Contents Product Description Key ComponentMWC Boiler Principle Components Maximum Vent Lengths II SpecificationsRatings Other SpecificationsIII Before Installing Clearances To Combustible Or Non-combustible Material Mounting The Boiler Wall Mounting Hole Locations Boiler Mounting VI Air for Ventilation Page VII Venting Vent System DesignPage Horizontal Concentric Venting Vent Options 3a Crown Concentric 60/100 Vent Components Vent Options 1,2 3b Crown Concentric 80/125 Vent Components Vent Options 3,54c Positioning Vent Terminal Under Overhangs Vent/ Air Intake Fitting Equivalent Length Vertical Concentric Vent System Vent Option Removing an Existing Boiler From a Common Chimney All cuts are square and allow for proper insertion 21 Dimension L 22 Cutting Outer Pipe 25 Attaching 60/100mm Terminal Section 30 Installation Of 80/125 Adaptor On Boiler 31a Cuttable Straight Section 32 Cutting Straight Pipe 33a Joining Cuttable Pipe 34a Dimension L, 80/125mm Horizontal Terminal 34c Cutting Inner Pipe Of 80/125mm Horizontal Terminal 35a Dimension H 35b Cutting Vertical Terminal 36 Chimney Chase Installation Condensate Trap and Drain Line 40 Condensate Piping ArrangementViii Gas Piping Gas Connection To Boiler IX System Piping Standard PipingBasic Piping Relief Valve Installation Piping for Special Situations Internal Boiler PipingPrimary-Secondary Piping MWC116E*T Combi Internal Boiler-Side Piping Schematic MWC116E*L Heat-Only Internal Piping Schematic Domestic Water Piping DHW Piping MWC116E*T Combi Internal DHW-Side Piping Schematic XI Wiring Field Supplied Box End Boiler End Location of Terminal Blocks and 7/8 Hole for Whip Field Wiring 120VAC Thermostat Internal Boiler Wiring XII Start-up and Checkout Location of Automatic Air Vent CapLocation of Circulator Shaft Cover Control Panel Page Inner Cover Removal For Your Safety Read Before Operating MWC Series Lighting and Operating InstructionsHigh Fire Combustion Readings Xiii Operation DHWHeating System Knob Sequence of Operation Also Refer to Figures 9.7, 9.8, 10.3 See Part XV for Error Codes Flash Codes During Normal OperationXIV. Service and Maintenance Removing Combustion Chamber Cover Service Notes InducerCondensate Trap Removal XV. Troubleshooting No Error Code DisplayedError Codes Lamp Number Flame Meaning Corrective ActionFlow Chart for Isolating Limit and APS Errors See Table XVI Parts Flow group and three way diverter valve Model combi Flow and return groups Model c.h. only Pump and main circuit assembly Model combi Pump and main circuit assembly Model c.h. only Gas assembly Connection pipes Control panel and ignition device Model combi Control panel and ignition device Model c.h. only Wiring Model combi Wiring Model c.h. only Fan, combustion chamber and case panels Description Spare part code Description Spare part code Description Spare part code Installation of Carbon Monoxide Detectors Approved Carbon Monoxide Detectors 11/07

MWC116ENL, MWC116ELL, MWC116ELT, MWC116ENT, MWC Series specifications

Crown Boiler's MWC Series represents a commendable choice in the realm of residential and light commercial heating solutions. Specifically, models like the MWC116ENT, MWC116ELT, MWC116ELL, and MWC116ENL stand out due to their exceptional performance, reliability, and innovative features.

At the core of the MWC Series lies a robust cast iron boiler construction designed to withstand the test of time. This material not only provides durability but also enhances heat retention, thereby increasing the system's efficiency. Each model in this series is designed for natural gas or propane fuel types, ensuring flexibility based on availability and user preference.

A notable feature of the MWC116 models is the efficient heat exchanger, which enables rapid heating of water for both space heating and domestic hot water applications. With a heating capacity of 116,000 BTUs, these boilers deliver ample warmth for mid-sized homes or light commercial settings, making them a versatile option for various applications.

The MWC116ENT model is equipped with an energy-efficient electronic ignition system, which enhances reliability and efficiency. This technology reduces energy consumption, providing users with cost savings on their utility bills. Similarly, the MWC116ELT model boasts an integrated aquastat that regulates water temperature, ensuring optimal performance and comfort.

For those requiring increased venting options, the MWC116ELL model includes advanced horizontal venting capabilities, allowing for flexible installation in various environments. This feature aids in overcoming space limitations and facilitating optimal combustion conditions. The MWC116ENL, on the other hand, features a low NOx emissions configuration, making it an environmentally conscious choice for users concerned about their carbon footprint.

User-friendly controls are a characteristic hallmark of the MWC Series, enabling straightforward operation and easy adjustments. The boilers come equipped with a digital display that provides critical system information and diagnostics, streamlining maintenance efforts.

Overall, the Crown Boiler MWC Series, particularly models like the MWC116ENT, MWC116ELT, MWC116ELL, and MWC116ENL, offer an impressive blend of efficiency, flexibility, and advanced technology. These units are designed to meet contemporary heating demands while ensuring sustainable operation, making them a wise investment for comfort and performance in residential and light commercial applications alike. With reliable construction and innovative features, the MWC Series remains a top choice for those seeking effective heating solutions.