Crown Boiler MWC Series, MWC116ENL, MWC116ELL, MWC116ENT, MWC116ELT manual Control Panel

Page 55

Lamp 1

DHW

Heating System Knob

 

 

Flame Reset Button

Lamp 2

Thermostat

Lamp 3

(Combi Only)

Flame Lockout Lamp

 

 

 

Figure 12.3: Control Panel

The burner may not light on the first try. The most likely cause of this problem on a new installation is a gas line that has not been completely purged. Other possibilities include inadequate inlet gas pressure or a boiler that is configured for the wrong fuel. If the boiler does not light on the first try, it will go into a lockout condition. When this happens, the Flame Lockout Lamp (Figure 12.3) will be illuminated. In addition, Lamps 1 and 3 will flash and Lamp 2 will be on continuously. To reset the boiler, push the Flame Reset Button shown in Figure 12.3 AND rotate the Heating System Knob back to “0” for a few seconds.

7)Inspect the flame visible through the window. The flame should be stable and mostly blue (Fig.12.4). No yellow tipping should be present; however, intermittent flecks of yellow and orange in the flame are normal.

8)Check the inlet and manifold pressures. To do this, use the following procedure:

a)Remove the inner cover (figure 12.5). Note: this is necessary in order to read the manifold pressure accurately because the gas valve regulator is referenced to the burner area.

Figure 12.4: Main Burner Flame

53

Image 55
Contents MWC Series Page Table of Contents Key Component Product DescriptionMWC Boiler Principle Components Other Specifications II SpecificationsRatings Maximum Vent LengthsIII Before Installing Clearances To Combustible Or Non-combustible Material Mounting The Boiler Wall Mounting Hole Locations Boiler Mounting VI Air for Ventilation Page Vent System Design VII VentingPage Horizontal Concentric Venting Vent Options 3b Crown Concentric 80/125 Vent Components Vent Options 3,5 3a Crown Concentric 60/100 Vent Components Vent Options 1,24c Positioning Vent Terminal Under Overhangs Vent/ Air Intake Fitting Equivalent Length Vertical Concentric Vent System Vent Option Removing an Existing Boiler From a Common Chimney All cuts are square and allow for proper insertion 21 Dimension L 22 Cutting Outer Pipe 25 Attaching 60/100mm Terminal Section 30 Installation Of 80/125 Adaptor On Boiler 31a Cuttable Straight Section 32 Cutting Straight Pipe 33a Joining Cuttable Pipe 34a Dimension L, 80/125mm Horizontal Terminal 34c Cutting Inner Pipe Of 80/125mm Horizontal Terminal 35a Dimension H 35b Cutting Vertical Terminal 36 Chimney Chase Installation 40 Condensate Piping Arrangement Condensate Trap and Drain LineViii Gas Piping Gas Connection To Boiler Standard Piping IX System PipingBasic Piping Relief Valve Installation Internal Boiler Piping Piping for Special SituationsPrimary-Secondary Piping MWC116E*T Combi Internal Boiler-Side Piping Schematic MWC116E*L Heat-Only Internal Piping Schematic Domestic Water Piping DHW Piping MWC116E*T Combi Internal DHW-Side Piping Schematic XI Wiring Field Supplied Box End Boiler End Location of Terminal Blocks and 7/8 Hole for Whip Field Wiring 120VAC Thermostat Internal Boiler Wiring Location of Automatic Air Vent Cap XII Start-up and CheckoutLocation of Circulator Shaft Cover Control Panel Page Inner Cover Removal MWC Series Lighting and Operating Instructions For Your Safety Read Before OperatingHigh Fire Combustion Readings DHW Xiii OperationHeating System Knob Sequence of Operation Also Refer to Figures 9.7, 9.8, 10.3 Flash Codes During Normal Operation See Part XV for Error CodesXIV. Service and Maintenance Removing Combustion Chamber Cover Inducer Service NotesCondensate Trap Removal No Error Code Displayed XV. TroubleshootingLamp Number Flame Meaning Corrective Action Error CodesFlow Chart for Isolating Limit and APS Errors See Table XVI Parts Flow group and three way diverter valve Model combi Flow and return groups Model c.h. only Pump and main circuit assembly Model combi Pump and main circuit assembly Model c.h. only Gas assembly Connection pipes Control panel and ignition device Model combi Control panel and ignition device Model c.h. only Wiring Model combi Wiring Model c.h. only Fan, combustion chamber and case panels Description Spare part code Description Spare part code Description Spare part code Installation of Carbon Monoxide Detectors Approved Carbon Monoxide Detectors 11/07

MWC116ENL, MWC116ELL, MWC116ELT, MWC116ENT, MWC Series specifications

Crown Boiler's MWC Series represents a commendable choice in the realm of residential and light commercial heating solutions. Specifically, models like the MWC116ENT, MWC116ELT, MWC116ELL, and MWC116ENL stand out due to their exceptional performance, reliability, and innovative features.

At the core of the MWC Series lies a robust cast iron boiler construction designed to withstand the test of time. This material not only provides durability but also enhances heat retention, thereby increasing the system's efficiency. Each model in this series is designed for natural gas or propane fuel types, ensuring flexibility based on availability and user preference.

A notable feature of the MWC116 models is the efficient heat exchanger, which enables rapid heating of water for both space heating and domestic hot water applications. With a heating capacity of 116,000 BTUs, these boilers deliver ample warmth for mid-sized homes or light commercial settings, making them a versatile option for various applications.

The MWC116ENT model is equipped with an energy-efficient electronic ignition system, which enhances reliability and efficiency. This technology reduces energy consumption, providing users with cost savings on their utility bills. Similarly, the MWC116ELT model boasts an integrated aquastat that regulates water temperature, ensuring optimal performance and comfort.

For those requiring increased venting options, the MWC116ELL model includes advanced horizontal venting capabilities, allowing for flexible installation in various environments. This feature aids in overcoming space limitations and facilitating optimal combustion conditions. The MWC116ENL, on the other hand, features a low NOx emissions configuration, making it an environmentally conscious choice for users concerned about their carbon footprint.

User-friendly controls are a characteristic hallmark of the MWC Series, enabling straightforward operation and easy adjustments. The boilers come equipped with a digital display that provides critical system information and diagnostics, streamlining maintenance efforts.

Overall, the Crown Boiler MWC Series, particularly models like the MWC116ENT, MWC116ELT, MWC116ELL, and MWC116ENL, offer an impressive blend of efficiency, flexibility, and advanced technology. These units are designed to meet contemporary heating demands while ensuring sustainable operation, making them a wise investment for comfort and performance in residential and light commercial applications alike. With reliable construction and innovative features, the MWC Series remains a top choice for those seeking effective heating solutions.