Crown Boiler MWC116ELL, MWC Series, MWC116ENL All cuts are square and allow for proper insertion

Page 22

C. Assembly of Crown 60/100mm Concentric Venting

(IMPORTANT - Skip to Section D for 80/125mm Concentric Vent Assembly)

WARNING

Failure to follow the instructions could result in flue gas leakage into the combustion air or indoor air, resulting in unsafe or unreliable operation.

Do not lubricate concentric gaskets with anything other than water.

Do not attempt to cut any piping except as permitted in this section. When cutting these

sections, make sure

all cuts are square and allow for proper insertion.

Do not attempt to try to mix this concentric pipe with other venting systems.

1)Concentric vent components supplied with the boiler are packed in a separate carton and include the following:

a)60/100mm elbow adaptor (Crown PN 340509).

b)60/100mm terminal section (straight section with a terminal and overall length of 27 3/4” (Crown PN 230520).

c)Two (2) Rubber wall grommets (Crown PN 230522).

d)Vent gasket and screws for attachment of vent system to boiler.

The 82mm air inlet orifice required for Vent Option 1 is packed in the boiler carton.

The 60/100 straight adaptor is optional equipment. It is supplied with the same screws and gasket as the 60/100 elbow adaptor.

2)Start by attaching the elbow adaptor (or straight adaptor, if used instead) to the top of the boiler using the gasket and four 4.2mm sheet metal screws provided in the vent kit as shown in Figure 7.20. For Vent Option 1, install the 82mm air inlet orifice as shown.

3)If no additional sections of concentric pipe are required, attach the terminal section to the elbow. In most cases, it will need to be cut before doing so. Use the following procedure to cut the pipe:

a)Measure distance “L” from the outside surface of the exterior wall to the end of the elbow as shown in Figure 7.21.

b)Add 2-1/8” to distance “L”. Carefully mark this length on the pipe as shown in Figure 7.22.

c)Press in the two tabs holding the plastic terminal in the terminal section (Figure 7.22). Carefully pull out the terminal and the inner pipe.

d)Cut the outer pipe only at the point marked in Step (b) using aviation shears, a hacksaw, or an abrasive wheel cutter. Be careful to cut the pipe square. De burr the cut end with a file or emery cloth.

e)Cut the plastic inner pipe so that it will protrude 3/8” beyond the outer pipe when reinstalled in the terminal section (Figure 7.23). Use a fine tooth hacksaw or a PVC saw to cut the plastic pipe and be careful to cut the pipe square. De burr the cut edge of the plastic pipe with a file, razor blade, or fine sandpaper.

f)Reinstall the inner pipe in the terminal section. Slip the outside wall grommet over the terminal section and position so that it covers the joint between the outer pipe and the terminal (Figure 7.24).

g)Make a mark on the terminal section 1” from the cut end of the outer pipe as shown in Figure 7.24.

h)Pass the terminal section through the wall from the outside. Push the remaining wall grommet over the terminal section on the inside of the wall. Push the terminal section into the elbow until the mark made in Step

(g) is no longer visible. If necessary, the brown gasket in the inner pipe may be lubricated with a few drops of water.

i)The terminal section must be attached to the elbow with a single #10 x 1/2” sheet metal screw ( not supplied) at the top of the elbow. Drill a 1/8” hole in the location shown in Figure 7.25. Use a short drill bit or a drill stop to ensure that the drill bit does not penetrate the pipe by more than 3/8”. Install a #10 x 1/2” screw in this hole. Do not use a screw longer than 1/2” long.

j)If not already done, make sure that both wall grommets are firmly against the interior and exterior wall surfaces. Seal any cracks or other openings near the terminal through which exhaust could enter the building.

20

Image 22
Contents MWC Series Page Table of Contents Product Description Key ComponentMWC Boiler Principle Components Maximum Vent Lengths II SpecificationsRatings Other SpecificationsIII Before Installing Clearances To Combustible Or Non-combustible Material Mounting The Boiler Wall Mounting Hole Locations Boiler Mounting VI Air for Ventilation Page VII Venting Vent System DesignPage Horizontal Concentric Venting Vent Options 3a Crown Concentric 60/100 Vent Components Vent Options 1,2 3b Crown Concentric 80/125 Vent Components Vent Options 3,54c Positioning Vent Terminal Under Overhangs Vent/ Air Intake Fitting Equivalent Length Vertical Concentric Vent System Vent Option Removing an Existing Boiler From a Common Chimney All cuts are square and allow for proper insertion 21 Dimension L 22 Cutting Outer Pipe 25 Attaching 60/100mm Terminal Section 30 Installation Of 80/125 Adaptor On Boiler 31a Cuttable Straight Section 32 Cutting Straight Pipe 33a Joining Cuttable Pipe 34a Dimension L, 80/125mm Horizontal Terminal 34c Cutting Inner Pipe Of 80/125mm Horizontal Terminal 35a Dimension H 35b Cutting Vertical Terminal 36 Chimney Chase Installation Condensate Trap and Drain Line 40 Condensate Piping ArrangementViii Gas Piping Gas Connection To Boiler IX System Piping Standard PipingBasic Piping Relief Valve Installation Piping for Special Situations Internal Boiler PipingPrimary-Secondary Piping MWC116E*T Combi Internal Boiler-Side Piping Schematic MWC116E*L Heat-Only Internal Piping Schematic Domestic Water Piping DHW Piping MWC116E*T Combi Internal DHW-Side Piping Schematic XI Wiring Field Supplied Box End Boiler End Location of Terminal Blocks and 7/8 Hole for Whip Field Wiring 120VAC Thermostat Internal Boiler Wiring XII Start-up and Checkout Location of Automatic Air Vent CapLocation of Circulator Shaft Cover Control Panel Page Inner Cover Removal For Your Safety Read Before Operating MWC Series Lighting and Operating InstructionsHigh Fire Combustion Readings Xiii Operation DHWHeating System Knob Sequence of Operation Also Refer to Figures 9.7, 9.8, 10.3 See Part XV for Error Codes Flash Codes During Normal OperationXIV. Service and Maintenance Removing Combustion Chamber Cover Service Notes InducerCondensate Trap Removal XV. Troubleshooting No Error Code DisplayedError Codes Lamp Number Flame Meaning Corrective ActionFlow Chart for Isolating Limit and APS Errors See Table XVI Parts Flow group and three way diverter valve Model combi Flow and return groups Model c.h. only Pump and main circuit assembly Model combi Pump and main circuit assembly Model c.h. only Gas assembly Connection pipes Control panel and ignition device Model combi Control panel and ignition device Model c.h. only Wiring Model combi Wiring Model c.h. only Fan, combustion chamber and case panels Description Spare part code Description Spare part code Description Spare part code Installation of Carbon Monoxide Detectors Approved Carbon Monoxide Detectors 11/07

MWC116ENL, MWC116ELL, MWC116ELT, MWC116ENT, MWC Series specifications

Crown Boiler's MWC Series represents a commendable choice in the realm of residential and light commercial heating solutions. Specifically, models like the MWC116ENT, MWC116ELT, MWC116ELL, and MWC116ENL stand out due to their exceptional performance, reliability, and innovative features.

At the core of the MWC Series lies a robust cast iron boiler construction designed to withstand the test of time. This material not only provides durability but also enhances heat retention, thereby increasing the system's efficiency. Each model in this series is designed for natural gas or propane fuel types, ensuring flexibility based on availability and user preference.

A notable feature of the MWC116 models is the efficient heat exchanger, which enables rapid heating of water for both space heating and domestic hot water applications. With a heating capacity of 116,000 BTUs, these boilers deliver ample warmth for mid-sized homes or light commercial settings, making them a versatile option for various applications.

The MWC116ENT model is equipped with an energy-efficient electronic ignition system, which enhances reliability and efficiency. This technology reduces energy consumption, providing users with cost savings on their utility bills. Similarly, the MWC116ELT model boasts an integrated aquastat that regulates water temperature, ensuring optimal performance and comfort.

For those requiring increased venting options, the MWC116ELL model includes advanced horizontal venting capabilities, allowing for flexible installation in various environments. This feature aids in overcoming space limitations and facilitating optimal combustion conditions. The MWC116ENL, on the other hand, features a low NOx emissions configuration, making it an environmentally conscious choice for users concerned about their carbon footprint.

User-friendly controls are a characteristic hallmark of the MWC Series, enabling straightforward operation and easy adjustments. The boilers come equipped with a digital display that provides critical system information and diagnostics, streamlining maintenance efforts.

Overall, the Crown Boiler MWC Series, particularly models like the MWC116ENT, MWC116ELT, MWC116ELL, and MWC116ENL, offer an impressive blend of efficiency, flexibility, and advanced technology. These units are designed to meet contemporary heating demands while ensuring sustainable operation, making them a wise investment for comfort and performance in residential and light commercial applications alike. With reliable construction and innovative features, the MWC Series remains a top choice for those seeking effective heating solutions.