Crown Boiler MWC116ENT, MWC Series, MWC116ENL, MWC116ELL manual IX System Piping, Standard Piping

Page 38

IX System Piping

CAUTION

Install boiler so that the gas ignition system components are protected from water (dripping, spraying, rain, etc) during appliance operation and service (circulator replacement, etc).

Operation of this boiler with continuous return temperatures below 86F can cause severe heat exchanger corrosion damage.

Operation of this boiler in a system having frequent additions of make-up water can cause severe heat exchanger damage.

Do not use toxic additives, such as automotive antifreeze, in a hydronic system.

Before connecting boiler, make sure that the system is free of sediment, flux and any residual boiler water additives. Flush the system if necessary to ensure that these contaminates are removed.

A. Standard Piping

Figure 9.1 shows typical boiler system connections on a single zone system. Additional information on hydronic system design may be found in Installation of Residential Hydronic Systems (Pub. #200) published by the Hydronics Institute in Berkeley Heights, NJ. The components in this system and their purposes are as follows:

1)Relief valve (Included & Required) – Install the relief valve in the 3/4” connections on the top of the boiler as shown in Figure 9.3. The relief valve shipped with the boiler is set to open at 30 psi. This valve may be replaced with one having a setting at or below the Maximum Allowable Working Pressure (MAWP) shown on the ASME plate attached to the heat exchanger. If the valve is replaced, the replacement must have a relief capacity in excess of the Minimum Relief Valve Capacity shown on the rating plate.

Pipe the discharge of the relief valve to a location where water or steam will not create a hazard or cause property damage if the valve opens. The end of the discharge pipe must terminate in an unthreaded pipe. If the relief valve discharge is not piped to a drain, it must terminate at least 6 inches above the floor. Do not run relief valve discharge piping through an area that is prone to freezing. The termination of the relief valve discharge piping must be in an area where it is not likely to become plugged by debris.

DANGER

Pipe relief valve discharge to a safe location.

Do not install a valve in the relief valve discharge line.

Do not move relief valve from factory specified location.

Do not plug relief valve discharge.

2)Circulator (Included & Required) – This boiler is equipped with a factory piped circulator, which is often the only circulator required. Figure 9.2 is a performance curve for this circulator. Note that this curve is has been adjusted to take into the account of all internal boiler piping. This performance curve therefore shows the amount of flow that can be achieved at various heating system pressure drops.

3)Throttling Valve or Flow Restrictor - This boiler is equipped with a differential pressure switch to prove that there is flow through the boiler before allowing it to fire. Reliable operation of this switch requires that there be a head loss across the heating system of at least 5.1ft wc. In order to assure that this head loss will always be present, either a throttling valve must be installed as shown in Figure 9.1 or the flow restrictor shown in Figure 9.4 must be installed. Use the following guidelines to determine which device to use:

If the boiler is installed an a single zone system, or one having zone valves, install the throttling valve. At start- up, start with this valve fully open and then close it just enough to obtain reliable operation of the pressure switch.

If the boiler is connected to a primary-secondary system (Figure 9.5), install the orifice in the supply tailpiece as shown in Figure 9.4.

If the boiler is connected to a circulator zone system, primary-secondary piping must be used. Install the orifice as shown in Figure 9.4.

36

Image 38
Contents MWC Series Page Table of Contents Product Description Key ComponentMWC Boiler Principle Components Maximum Vent Lengths II SpecificationsRatings Other SpecificationsIII Before Installing Clearances To Combustible Or Non-combustible Material Mounting The Boiler Wall Mounting Hole Locations Boiler Mounting VI Air for Ventilation Page VII Venting Vent System DesignPage Horizontal Concentric Venting Vent Options 3a Crown Concentric 60/100 Vent Components Vent Options 1,2 3b Crown Concentric 80/125 Vent Components Vent Options 3,54c Positioning Vent Terminal Under Overhangs Vent/ Air Intake Fitting Equivalent Length Vertical Concentric Vent System Vent Option Removing an Existing Boiler From a Common Chimney All cuts are square and allow for proper insertion 21 Dimension L 22 Cutting Outer Pipe 25 Attaching 60/100mm Terminal Section 30 Installation Of 80/125 Adaptor On Boiler 31a Cuttable Straight Section 32 Cutting Straight Pipe 33a Joining Cuttable Pipe 34a Dimension L, 80/125mm Horizontal Terminal 34c Cutting Inner Pipe Of 80/125mm Horizontal Terminal 35a Dimension H 35b Cutting Vertical Terminal 36 Chimney Chase Installation Condensate Trap and Drain Line 40 Condensate Piping ArrangementViii Gas Piping Gas Connection To Boiler IX System Piping Standard PipingBasic Piping Relief Valve Installation Piping for Special Situations Internal Boiler PipingPrimary-Secondary Piping MWC116E*T Combi Internal Boiler-Side Piping Schematic MWC116E*L Heat-Only Internal Piping Schematic Domestic Water Piping DHW Piping MWC116E*T Combi Internal DHW-Side Piping Schematic XI Wiring Field Supplied Box End Boiler End Location of Terminal Blocks and 7/8 Hole for Whip Field Wiring 120VAC Thermostat Internal Boiler Wiring XII Start-up and Checkout Location of Automatic Air Vent CapLocation of Circulator Shaft Cover Control Panel Page Inner Cover Removal For Your Safety Read Before Operating MWC Series Lighting and Operating InstructionsHigh Fire Combustion Readings Xiii Operation DHWHeating System Knob Sequence of Operation Also Refer to Figures 9.7, 9.8, 10.3 See Part XV for Error Codes Flash Codes During Normal OperationXIV. Service and Maintenance Removing Combustion Chamber Cover Service Notes InducerCondensate Trap Removal XV. Troubleshooting No Error Code DisplayedError Codes Lamp Number Flame Meaning Corrective ActionFlow Chart for Isolating Limit and APS Errors See Table XVI Parts Flow group and three way diverter valve Model combi Flow and return groups Model c.h. only Pump and main circuit assembly Model combi Pump and main circuit assembly Model c.h. only Gas assembly Connection pipes Control panel and ignition device Model combi Control panel and ignition device Model c.h. only Wiring Model combi Wiring Model c.h. only Fan, combustion chamber and case panels Description Spare part code Description Spare part code Description Spare part code Installation of Carbon Monoxide Detectors Approved Carbon Monoxide Detectors 11/07