A.O. Smith VB/VW- 750, VB/VW- 1000 instruction manual Air From Other Indoor Spaces

Page 13

Air From Other Indoor Spaces

The confined space should be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 9E.

Each opening should communicate directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an Unconfined Space.

Each opening should have a minimum free area of 1 square inch per 1,000 Btu/hr (1100 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening should not be less than 100 square inches (645 cm2).

FIGURE 9E.

13

Image 13
Contents Models Safe INSTALLATION, USE and Service General Safety GAS and Electrical Characteristics Dimension and capacity dataCapacity and Flow data Recovery CapacitiesIntroduction ContentsHigh Altitude Installations PrecautionsField Installed Components Grounding InstructionsControl Components ON/OFF Switch Water Temperature Limit ControlsTemperature Probes Circulating PumpLocation Required AbilityPanels and Covers VB HOT Water Heating BOILERS, are shipped with a 50 psiChemical Vapor Corrosion Installtion ClearancesLeveling Air Requirements Breathing Hazard Carbon Monoxide GasOutdoor Air Through One Opening Outdoor Air Through Two OpeningsOutdoorAir Through Two HorizontalDucts Outdoor Air Through Two Vertical DuctsAir From Other Indoor Spaces Power Vent Termination Clearances Sidewall Power VentDirect Vent Termination Clearances Sidewall Direct VentVenting System Using AL 29-4C Special Installation ConsiderationsConnecting Vent to Boiler Horizontal Installtion Requirements Vertical Installation RequirementsVenting Supports Vertical Termination BELOW. Keep Clear of ALL Obstructions Direct Vent Installation RequirementsDirect Vent Horizontal Direct Vent Using TWT with Vertical Intake General System installationHot Water Heating Hydronic Equipment Internal Contaminants Remote Probe Installation ProcedureHard Water Conditions Thermal Expansion Closed SystemGas Supply Line Sizing Gas ConnectionsTypical PRIMARY, Secondary Piping ONE VF Model VW HOT Water Supply Boiler with Vertical Tank ONE VF Model VW HOT Water Supply Boiler with Horizontal Tank Wiring Suggested Pipe Size For Multiple Gas Appliances Propane Gas Suggested Pipe Size For Multiple Gas Appliances Natural GasConnection Diagram Wiring DiagramPage VB/VW-500, 750 & 1000 Schematic Diagram Filling Hot Water Supply Boiler Installation Filling and Purging of Heating Boiler InstallationOperation Purging Gas LineRisk of Scalds Water Temperature RegulationMCB/FCB Dipswitches MCB Ten Position DipswitchMCB Three position Dipswitch Lighting & Operation Instructions for Models VB/VW 500, 750 Setting of the Test Mode AdjustmentHigh Fire Setting Natural GAS PropaneInputs to MCB Operating Sequence Temperature Setpoints System Control AlgorithmUIM Operating Procedures Description of FCB control states OperatingSetpointAdjustmentProcedureHighLimitDifferentialSetpointAdjustment Procedure UIM LED’s Fault Messages and Troubleshooting GuideFault Displayed Description Red LED Lockout Troubleshooting Ignition SystemTroubleshooting Gas Valve Preventative maintenanceMain Burner Relief Valve Burner MaintenanceCombustion Air Filter Blower CompartmentHeatExchangerPreventativeMaintenance Venting MaintenanceTube Cleaning Procedure Mechanical Removal of Deposits Replacement PartsPage Page Page Limited Warranty Tennessee Waltz Parkway, Ashland City, TN Phone

VB/VW- 1000, VB/VW- 750 specifications

A.O. Smith is a renowned name in the water heating industry, and their VB/VW-750 and VB/VW-1000 models reflect the cutting-edge advancements in both design and functionality. These commercial water heaters stand out due to their innovative features and robust characteristics, making them ideal solutions for various applications in commercial settings.

The VB/VW-750 and VB/VW-1000 models are designed with high efficiency in mind. They utilize advanced heat transfer technology that maximizes energy use, translating to significant savings on utility bills. These units are engineered to deliver consistent hot water supply, essential for businesses such as restaurants, hotels, and manufacturing facilities where extensive hot water demands are necessary.

One of the standout features of the VB/VW models is their high recovery rate. This means they can produce a large volume of hot water within a short period, catering to peak demand times without compromising performance. Additionally, the units come equipped with a durable tank made from high-quality materials to resist corrosion, which ensures a long lifespan and reliability in service.

The VB/VW-750 and VB/VW-1000 are also equipped with advanced control systems. These systems provide precise temperature regulation, improving safety and energy efficiency. The smart pumping system further enhances performance by optimizing water flow and reducing energy consumption during operation.

Maintenance and serviceability are key characteristics of these models. They feature easy access to critical components, allowing for quick inspections and repairs. This design consideration minimizes downtime, which is crucial for any business reliant on continuous hot water supply.

Both models are compliant with various industry standards, including energy efficiency regulations. A.O. Smith has focused on ensuring these water heaters not only meet but exceed these requirements, contributing to sustainability efforts.

In summary, the A.O. Smith VB/VW-750 and VB/VW-1000 models combine efficiency, reliability, and ease of maintenance. Their advanced features and cutting-edge technologies make them a top choice for commercial hot water applications, positioning A.O. Smith as a leader in the water heating industry. With their strong performance and durability, these models are designed to meet the demands of modern businesses while providing peace of mind regarding hot water availability.