A.O. Smith VB/VW- 1000, VB/VW- 750 instruction manual Termination Clearances Sidewall Power Vent

Page 14

Termination Clearances Sidewall Power Vent

 

 

 

 

 

 

POWER VENT

 

 

 

 

 

 

 

 

(using room air for combustion)

 

 

 

 

EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V

 

 

 

 

 

 

 

 

D

 

 

 

 

 

A

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

vE

 

 

 

 

 

 

 

 

 

 

 

 

 

L

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

v

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

C

 

B

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

FIXED

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

V

FIXED

 

V

 

OPERABL

CLOSED

 

M

 

X

 

 

 

 

 

 

 

 

 

 

 

CLOSED

 

 

 

 

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPERABL

E

 

 

 

 

X

 

 

 

 

 

 

V

B

 

V

 

 

 

 

 

 

 

F

 

 

 

 

 

 

 

 

 

 

 

 

B

 

J

 

 

 

K

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

V

VENT TERMINAL

X AIR SUPPLY INLET

 

AREA WHERE TERMINAL IS NOT PERMITTED

Figure 9F.

Vent terminal clearances for “Power Vent” installations. Power Vent configurations use room air for combustion.

 

 

Canadian Installations 1

US Installations 2

 

 

Canadian Installations 1

US Installations 2

 

Clearance above grade,

 

 

 

Clearance to each side

3 feet (91 cm) within a height 15 feet

3 feet (91 cm) within a

A

 

 

H

of center line extended

height 15 feet (4.5 m)

veranda, porch, deck or

12 inches (30 cm)

12 inches (30 cm)

(4.5 m) above the meter/

above meter/regulator

above the meter/regulator

 

balcony

 

 

 

assembly

regulator assembly

assembly*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 inches (15 cm) for appliances up to

 

 

 

 

 

 

Clearance to window

10,000 Btu/hr (3 kW), 12 inches (30

4 feet (1.2 m) below

 

Clearance to service

 

 

B

cm) for appliances between 10,000

or to side of opening;

I

 

 

or door that may be

regulator vent outlet

3 feet (91 cm)

3 feet (91 cm)*

Btu/hr (3 kW) and 100,000 Btu/hr (30

1 foot (30 cm) above

 

opened

kW), 36 inches (91 cm) for appliances

opening

 

 

 

 

 

 

above 100,000 Btu/hr (30 kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 inches (15 cm) for appliances up

 

 

Clearance to

 

 

 

Clearance to a non

to 10,000 Btu/hr (3 kW), 12 inches

4 feet (1.2 m) below or to

 

 

 

 

mechanical air supply

(30 cm) for appliances between

C

 

 

J

side of opening; 1 foot

permanently closed

12 inches (30 cm)*

12 inches (30 cm)*

inlet into building or

10,000 Btu/hr (3 kW) and 100,000

(30 cm) above opening.

 

window

 

 

 

combustion air inlet to

Btu/hr (30kW), 36 inches (91cm)

 

 

 

 

 

 

any other appliance

for appliances above 100,000 Btu/

 

 

 

 

 

 

 

hr (30 kW)

 

 

 

 

 

 

 

 

 

 

Vertical clearance to

 

 

 

 

 

 

 

ventilated soffit located

 

 

 

 

 

3 feet (91 cm) above if

 

above the terminal

 

 

 

Clearance to a

 

D

 

 

K

 

within

within a horizontal

12 inches (30 cm)*

12 inches (30 cm)*

mechanical air supply

6 feet (1.83 m)

10 feet (3 m) horizontally

 

distance of 2 feet (61

 

 

 

inlet

 

 

 

cm) from the center line

 

 

 

 

 

 

 

of the terminal

 

 

 

 

 

 

 

 

 

 

 

Clearance above paved

 

 

E

Clearance to

12 inches (30 cm)*

12 inches (30 cm)*

L

sidewalk or paved

7 feet (2.13 m)†

7 feet (2.13 m)

unventilated soffit

driveway located on

 

 

 

 

 

 

public property

 

 

F

cornerClearance to outside

 

 

M

Clearance under

 

 

2 feet (60 cm)*

2 feet (60 cm)*

veranda, porch, deck, or

12 inches (30 cm) ‡

12 inches (30 cm) ‡

 

 

 

 

 

balcony

 

 

G

cornerClearance to inside

8 ft. (2.44 m)*

8 ft. (2.44 m)*

 

 

 

 

1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code. 2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.

A vent should not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.

14

Image 14
Contents Models Safe INSTALLATION, USE and Service General Safety Dimension and capacity data GAS and Electrical CharacteristicsRecovery Capacities Capacity and Flow dataContents IntroductionField Installed Components PrecautionsHigh Altitude Installations Grounding InstructionsControl Components Temperature Probes Water Temperature Limit ControlsON/OFF Switch Circulating PumpPanels and Covers Required AbilityLocation VB HOT Water Heating BOILERS, are shipped with a 50 psi Leveling Installtion Clearances Chemical Vapor Corrosion Air Requirements Breathing Hazard Carbon Monoxide GasOutdoorAir Through Two HorizontalDucts Outdoor Air Through Two OpeningsOutdoor Air Through One Opening Outdoor Air Through Two Vertical DuctsAir From Other Indoor Spaces Termination Clearances Sidewall Power Vent Power VentTermination Clearances Sidewall Direct Vent Direct VentConnecting Vent to Boiler Special Installation ConsiderationsVenting System Using AL 29-4C Venting Supports Vertical Installation RequirementsHorizontal Installtion Requirements Vertical Termination Direct Vent Installation Requirements BELOW. Keep Clear of ALL ObstructionsDirect Vent Horizontal Direct Vent Using TWT with Vertical Intake Hot Water Heating Hydronic Equipment System installationGeneral Hard Water Conditions Remote Probe Installation ProcedureInternal Contaminants Thermal Expansion Closed SystemGas Connections Gas Supply Line SizingTypical PRIMARY, Secondary Piping ONE VF Model VW HOT Water Supply Boiler with Vertical Tank ONE VF Model VW HOT Water Supply Boiler with Horizontal Tank Wiring Suggested Pipe Size For Multiple Gas Appliances Natural Gas Suggested Pipe Size For Multiple Gas Appliances Propane GasWiring Diagram Connection DiagramPage VB/VW-500, 750 & 1000 Schematic Diagram Operation Filling and Purging of Heating Boiler InstallationFilling Hot Water Supply Boiler Installation Purging Gas LineWater Temperature Regulation Risk of ScaldsMCB Three position Dipswitch MCB Ten Position DipswitchMCB/FCB Dipswitches Lighting & Operation Instructions for Models VB/VW 500, 750 High Fire Setting Natural GAS AdjustmentSetting of the Test Mode PropaneInputs to MCB Temperature Setpoints System Control Algorithm Operating SequenceUIM Operating Procedures OperatingSetpointAdjustmentProcedure Description of FCB control statesHighLimitDifferentialSetpointAdjustment Procedure Fault Messages and Troubleshooting Guide UIM LED’sTroubleshooting Ignition System Fault Displayed Description Red LED LockoutMain Burner Preventative maintenanceTroubleshooting Gas Valve Combustion Air Filter Burner MaintenanceRelief Valve Blower CompartmentTube Cleaning Procedure Mechanical Removal of Deposits Venting MaintenanceHeatExchangerPreventativeMaintenance Replacement PartsPage Page Page Limited Warranty Tennessee Waltz Parkway, Ashland City, TN Phone