A.O. Smith VB/VW- 1000, VB/VW- 750 instruction manual Gas Connections, Gas Supply Line Sizing

Page 24

This is accomplished by changing two dipswitch settings on the MCB. First, dipswitch “4” must be set to the “ON” position to designate the remote probe as the controlling probe. Second, dipswitch “1” must be set to the “OFF” position to limit the maximum remote probe temperature for VW applications. Also, make sure dipswitch “1” is set to the “OFF” position, which sets the outlet temperature for VW applications. Failure to do this will void the warranty. If the remote probe is not designated as the controlling probe, the unit will be controlled by the inlet probe and will not use the desired tank temperature as its base.

Refer to Connection Diagram, Figure 17, in order to connect the remote probe to the boiler, see Tables 9, 10, 13 and 14 for Dipswitch positions.

Gas Connections

Make sure the gas on which the boiler is to operate is the same as that specified on the rating plate. Do not install the boiler if equipped for a different type of gas. Consult your gas supplier.

This boiler is not intended to operate at gas supply pressure other than shown on the rating plate. A lock-up or positive shut-off type regulator must be installed in the gas supply line. Exposure to higher gas supply pressure may cause damage to gas valves which can result in fire or explosion. If overpressure has occurred such as through improper testing of gas lines or emergency malfunction of the supply system, the gas valves must be checked for safe operation. Make sure that the outside vents on the supply regulators and the safety vent valves are protected against blockage. These are parts of the gas supply system, not the boiler. Vent blockage may occur during ice build-up or snowstorms.

The boiler must be isolated from the gas supply piping system by closing its main manual gas shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.

Disconnect the boiler and its main manual gas shut-off valve from the gas supply piping during any pressure testing of the gas supply system over 1/2 psig. The gas supply line must be capped when not connected to the boiler.

It is important to guard against gas valve fouling from contaminants in the gas ways. Such fouling may cause improper operation, fire or explosion. If copper supply lines are used they must be approved for gas service.

When local codes require a main manual shut-off valve outside the boiler jacket, a suitable main manual shut-off valve must be installed in a location complying with those codes.

Before attaching the gas line be sure that all gas pipe is clean on the inside.

To trap any dirt or foreign material in the gas supply line, a drip leg (sediment trap) must be incorporated in the piping. The drip leg must be readily accessible and not subject to freezing conditions. Install in accordance with recommendations of serving gas supplier. Refer to the current edition of the national fuel gas code, ANSI Z223.1 or CAN/CSA – B149.1, and current addenda.

Size of gas supply piping may be larger than heater connection on installations where a significant run of piping is required.

To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to boiler gas inlet.

Fittings and unions in the gas line must be of the metal to metal type.

Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compound to the first two threads. Use compounds resistant to the action of liquefied petroleum gases.

Gas Supply Line Sizing

The gas piping installation must be capable of supplying the maximum probable gas demand without excessive pressure loss. Depending on local practices, the ALLOWABLE PRESSURE LOSS between the gas meter, or service regulator and each appliance is generally 0.3 or 0.5 inches of water column (0.075 or 0.124kPa).

For single boiler installation, refer to Table 5 for appropriate pipe length for the appliance maximum rate.

For multiple boilers refer to Table 6 for natural gas and Table 7 for propane. Maximum pressure drop is 0.5 for these charts.

Reference tables are from ANSI Z223.1 National Fuel Gas Code or CAN/CSA-B149.1-00 (and current addenda):

Natural gas is 1000 BTU/ft^3 @ 0.6 specific gravity Propane gas is 2500 BTU/ft^3 @ 1.5 specific gravity

< pipe length longer than 200 feet consult applicable codes

No additional allowance is necessary for an ordinary number of fittings. Where it is necessary to use more than the average number of fittings (i.e., elbows, tees and valves in gas supply line) use a pipe larger than specified to compensate for increased pressure drop.

TABLE 5.

SINGLE UNIT INSTALLATION, SUGGESTED GAS PIPE SIZING.

MAXIMUM EQUIVALENT PIPE LENGTH (IN FEET).

Nom. Pipe

 

 

 

 

0.3 in w.c. drop

 

 

 

 

 

1”

1.25”

1.5”

 

2”

BTU input

Nat

 

Prop

Nat

Prop

Nat

 

Prop

Nat

 

Prop

500,000

10

 

25

40

90

80

 

200

200

 

 

750,000

 

 

10

10

40

40

 

90

125

 

<

1,000,000

 

 

 

10

20

20

 

50

70

 

175

Nom. Pipe

 

 

 

 

0.5 in w.c. drop

 

 

 

 

 

1”

1.25”

1.5”

 

2”

BTU input

Nat

 

Prop

Nat

Prop

Nat

 

Prop

Nat

 

Prop

500,000

10

 

40

60

150

150

 

200

<

 

 

750,000

 

 

10

30

70

70

 

150

200

 

 

1,000,000

 

 

10

10

40

30

 

90

125

 

<

24

Image 24
Contents Models Safe INSTALLATION, USE and Service General Safety Dimension and capacity data GAS and Electrical CharacteristicsRecovery Capacities Capacity and Flow dataContents IntroductionPrecautions High Altitude InstallationsField Installed Components Grounding InstructionsControl Components Water Temperature Limit Controls ON/OFF SwitchTemperature Probes Circulating PumpRequired Ability LocationPanels and Covers VB HOT Water Heating BOILERS, are shipped with a 50 psiInstalltion Clearances Chemical Vapor CorrosionLeveling Air Requirements Breathing Hazard Carbon Monoxide GasOutdoor Air Through Two Openings Outdoor Air Through One OpeningOutdoorAir Through Two HorizontalDucts Outdoor Air Through Two Vertical DuctsAir From Other Indoor Spaces Termination Clearances Sidewall Power Vent Power VentTermination Clearances Sidewall Direct Vent Direct VentSpecial Installation Considerations Venting System Using AL 29-4CConnecting Vent to Boiler Vertical Installation Requirements Horizontal Installtion RequirementsVenting Supports Vertical Termination Direct Vent Installation Requirements BELOW. Keep Clear of ALL ObstructionsDirect Vent Horizontal Direct Vent Using TWT with Vertical Intake System installation GeneralHot Water Heating Hydronic Equipment Remote Probe Installation Procedure Internal ContaminantsHard Water Conditions Thermal Expansion Closed SystemGas Connections Gas Supply Line SizingTypical PRIMARY, Secondary Piping ONE VF Model VW HOT Water Supply Boiler with Vertical Tank ONE VF Model VW HOT Water Supply Boiler with Horizontal Tank Wiring Suggested Pipe Size For Multiple Gas Appliances Natural Gas Suggested Pipe Size For Multiple Gas Appliances Propane GasWiring Diagram Connection DiagramPage VB/VW-500, 750 & 1000 Schematic Diagram Filling and Purging of Heating Boiler Installation Filling Hot Water Supply Boiler InstallationOperation Purging Gas LineWater Temperature Regulation Risk of ScaldsMCB Ten Position Dipswitch MCB/FCB DipswitchesMCB Three position Dipswitch Lighting & Operation Instructions for Models VB/VW 500, 750 Adjustment Setting of the Test ModeHigh Fire Setting Natural GAS PropaneInputs to MCB Temperature Setpoints System Control Algorithm Operating SequenceUIM Operating Procedures OperatingSetpointAdjustmentProcedure Description of FCB control statesHighLimitDifferentialSetpointAdjustment Procedure Fault Messages and Troubleshooting Guide UIM LED’sTroubleshooting Ignition System Fault Displayed Description Red LED LockoutPreventative maintenance Troubleshooting Gas ValveMain Burner Burner Maintenance Relief ValveCombustion Air Filter Blower CompartmentVenting Maintenance HeatExchangerPreventativeMaintenanceTube Cleaning Procedure Mechanical Removal of Deposits Replacement PartsPage Page Page Limited Warranty Tennessee Waltz Parkway, Ashland City, TN Phone

VB/VW- 1000, VB/VW- 750 specifications

A.O. Smith is a renowned name in the water heating industry, and their VB/VW-750 and VB/VW-1000 models reflect the cutting-edge advancements in both design and functionality. These commercial water heaters stand out due to their innovative features and robust characteristics, making them ideal solutions for various applications in commercial settings.

The VB/VW-750 and VB/VW-1000 models are designed with high efficiency in mind. They utilize advanced heat transfer technology that maximizes energy use, translating to significant savings on utility bills. These units are engineered to deliver consistent hot water supply, essential for businesses such as restaurants, hotels, and manufacturing facilities where extensive hot water demands are necessary.

One of the standout features of the VB/VW models is their high recovery rate. This means they can produce a large volume of hot water within a short period, catering to peak demand times without compromising performance. Additionally, the units come equipped with a durable tank made from high-quality materials to resist corrosion, which ensures a long lifespan and reliability in service.

The VB/VW-750 and VB/VW-1000 are also equipped with advanced control systems. These systems provide precise temperature regulation, improving safety and energy efficiency. The smart pumping system further enhances performance by optimizing water flow and reducing energy consumption during operation.

Maintenance and serviceability are key characteristics of these models. They feature easy access to critical components, allowing for quick inspections and repairs. This design consideration minimizes downtime, which is crucial for any business reliant on continuous hot water supply.

Both models are compliant with various industry standards, including energy efficiency regulations. A.O. Smith has focused on ensuring these water heaters not only meet but exceed these requirements, contributing to sustainability efforts.

In summary, the A.O. Smith VB/VW-750 and VB/VW-1000 models combine efficiency, reliability, and ease of maintenance. Their advanced features and cutting-edge technologies make them a top choice for commercial hot water applications, positioning A.O. Smith as a leader in the water heating industry. With their strong performance and durability, these models are designed to meet the demands of modern businesses while providing peace of mind regarding hot water availability.