Honeywell IFS-2600 installation manual Instructions to Operators, Indicators

Page 24

Page 20

IFS-2600Installation & Programming Manual

INSTRUCTIONS TO OPERATORS

INDICATORS

 

Qty

Descriptor

Colour

Function

Buzzer

 

 

 

 

 

 

1

MAINS ON

Green

Illuminates when there is 200/220/240 VAC supply to

 

 

 

 

 

the panel.

 

1

BATTERY

Yellow

Illuminates if the battery fails a battery test.

Yes

 

 

FAULT

 

Illuminates if batteries are disconnected >30

 

 

 

 

 

seconds.

 

 

 

 

 

Illuminates if batteries are short circuit >30 seconds.

 

1

PSU FAULT

Yellow

Illuminates if the power supply is outside the

Yes

 

 

 

 

manufacturers range.

 

 

1

CHARGER

Yellow

Illuminates if the battery charger is outside the

Yes

 

 

LOW

 

recommended float charge voltage.

 

1

COMMON

Yellow

Illuminates if;

Yes

 

 

FAULT

 

Any un-isolated zone goes into fault.

 

 

 

 

 

ACF output is open or short circuit

 

 

 

 

 

Bell output is open or short circuit

 

 

 

 

 

Warning System output is open or short circuit

 

 

 

 

 

Battery Fault

 

 

 

 

 

Charger Fault

 

 

 

 

 

Power Supply Fault

 

 

 

 

 

MAF Isolate Input is Open Circuit

 

 

 

 

 

Configuration Fault

 

1

ACF ACT

Red

Illuminates if the ACF output has been activated.

 

1

ACF FLT

Yellow

Illuminates if the ancillary circuit is open or short

Yes

 

 

 

 

circuit. The LED will extinguish when the load is

 

 

 

 

 

restored.

 

1

ACF ISO

Yellow

Illuminates if the ancillary output has been manually

 

 

 

 

 

isolated.

 

1

Bell ACT

Red

Illuminates when the bell output has been energised.

 

1

Bell FLT

Yellow

Illuminates if the bell circuit is open or short circuit.

Yes

 

 

 

 

The LED will extinguish when the load is restored.

 

1

Bell ISO

Yellow

Illuminates if the bell output has been manually

 

 

 

 

 

isolated.

 

 

1

Warning

Red

Illuminates if the Warning System output has been

 

 

 

System ACT

 

energised.

 

1

Warning

Yellow

Illuminates if the Warning System circuit is open or

Yes

 

 

System FLT

 

short circuit. The LED will extinguish if the load is

 

 

 

 

 

restored.

 

1

Warning

Yellow

Illuminates if the Warning System has been manually

 

 

 

System ISO

 

isolated.

 

8

ALARM LEDS

Red

This LED will flash if it's corresponding zone goes

Yes

 

 

 

 

into alarm. It will remain flashing until it is

 

 

 

 

 

Acknowledged at which time it will go steady and

 

 

 

 

 

remain on until the alarm is reset. If the zone is

 

 

 

 

 

programmed as a time delay type, a steady LED

 

 

 

 

 

indicates the “pre-alarm” condition. If the zone is

 

 

 

 

 

isolated and in alarm it will also be steady.

 

8

FAULT LEDS

Yellow

This LED illuminates if it's corresponding zone goes

Yes

 

 

 

 

into fault. It will remain on until the fault is removed.

 

8

ISOLATE LEDS

Yellow

This LED illuminates if its corresponding zone is

 

 

 

 

 

isolated. It will remain on until the zone is de-

 

 

 

 

 

isolated.

 

P/N 10069 ECN08-0066

Image 24
Contents IFS-2600 Page Installation Precautions Documentation Feedback Table of Contents Placing Into Operation Instructions to OperatorsProgramming Appendix a Appendix BAppendix C Appendix DAppendix F Appendix GAppendix H AppendixCompatible Detectors Overview Specification ApprovalsEnvironmental Limits VDCAdditional relay outputs Power Supply Ratings and Settings Internal 24 VDC nom 3.0A Main Power SupplyInternal 27.3V DC 1.5A Battery Charger Internal 5VDC 2A Power SupplyBattery Type and Capacities External 27VDC Power SupplyTechnical Description GeneralTransient Suppression Current ConsumptionZone Overload Self Reset AZF DescriptionAZF Supervisory Current Overload ProtectionPrinter Output Cable ConnectionProgramming by Computer DB9 Female DB25 Male DB9 MaleAlignment and Adjustment PCB2006 Power Supply BoardNON Adjustable Test Points PCB2005 Termination BoardAlarm Threshold Comparator TP7 Fault Threshold Comparator TP6Configuration Jumpers Initial Checklist Placing Into OperationEquipment AS Fitted Power UP Checklist Functional TestingFault Record Fault Correction DateTests Satisfactorily Completed Indicators Instructions to OperatorsSuggested Alarm Procedure ResetOperator Instructions Acknowledge ACKBattery Test Batt Test Auto Test ModeBell Isolate EXT Bell Warn SYS IsolateWalk Test Mode ACF ResetACF Isolate Alarm Test ENT Zone FunctionsFault Test Enter Reset Enter Isolate EnterProgramming Global OptionsZone Options Output Relay Options Program Mode Previous →Select → Main Menu RelaysGlobal PrintExit Programming Mode Zone ProgrammingSelect Zone # Zone SelectedRelay Programming Mode Zone Output ConfigurationSelect Relay # Relay SelectedGlobal Programming Relay TypeRelay Mapping Relay #ALL Type GeneralACF Output AVFRelay Global Relay Unity MAP Print Programming Data Time Date & TimeDescription of Alarm Zone Types Appendix aLatching Type NON Latching TypeTime Delay AZF Zone Output Configurations Appendix BAlarm Verification Facility AVF AVF TimeoutAppendix C Global Programmable OptionsAppendix D Ancillary Trip ACFAncillary Trip ACF NON-LATCHING ND Latching ND NON-LATCHING NE LatchingneFault Mapping Appendix ERelay Output Mapping MappingFAULT/ISOLATE Mapping Isolate MappingAppendix F Glossary of TermsAppendix G Summary of Terminations and CautionsBattery Door Holder AC InputOutput Relays Appendix H IFS-2600 Programmed OptionsZone Type Programming 48IFS-2600Installation & Programming Manual Zone Output Programming Indicate IBG Ibga Bell General ACF BR1 BR2 BR1&BR2 Relay Output Mapping Mapping RLY ISO ACF BR1 BR2 FLT Mains GEN Bell Appendix Technical DrawingsMain Keypad and Display Expansion Display Block Connection Diagram 12V BatterySystem Sensor Conventional Detector Connection Diagram Hochiki Conventional Detector Connection Diagram DET aDET B DET C RIP DET a DET B DET CAncillary Connection Diagram Strobe UsedASE Connection Diagram TerminationASE Bracket Auto Changeover Dual Sounder Connection Diagram Changeover from Alert to EvacAuto Change Over Dual Sounder Connection Diagram Manual ChangeoverMimic Connection Diagram ZonesFitted with IFS2600 Mimic Driver MIM/EXT/26Single Fan Connection Diagram FAN Termination Board AUX PowerFront Panel Control Dual Fan Connection Diagram FANExhaust Fan Connection Diagram Stops the FAN From FIPSupply Fan Connection Diagram FAN Termination BoardSmoke Spill Fan Connection Diagram From FIP Front Panel Control10W Evac Connection Diagram Sound10W Evac Slave Connection Diagram From Slave30W Evac Connection Diagram AC230W Evac Slave Connection Diagram Acinput50W Evac Connection Diagram 50W EvacPCB 50W Evac Slave Connection Diagram FAN 50W EvacPage Page Page New South Wales Queensland Victoria Head Office

IFS-2600 specifications

The Honeywell IFS-2600 is a cutting-edge portable data collection device that has gained recognition for its robustness and efficiency in various industrial settings. Designed to enhance productivity in rugged environments, the IFS-2600 is a powerful tool for data acquisition and operational optimization.

One of the key features of the Honeywell IFS-2600 is its advanced scanning technology. It is equipped with a superior imaging engine that provides high-speed scanning capabilities. This makes it ideal for scanning barcodes, even in challenging conditions. The ability to read both 1D and 2D barcodes ensures versatility in applications ranging from inventory management to shipping and receiving.

Another significant characteristic of the IFS-2600 is its rugged design. Built to withstand harsh conditions, this device is compliant with military-grade specifications and offers an impressive drop resistance. It is capable of enduring extreme temperatures, humidity, and dust, making it suitable for use in warehouses, manufacturing plants, and outdoor environments.

The IFS-2600 also boasts a user-friendly interface. Featuring a high-resolution display with touchscreen capabilities, users can easily navigate through applications and access necessary data. The device is designed for efficiency, allowing users to efficiently input information and manage tasks.

Connectivity is another prominent aspect of the Honeywell IFS-2600. With support for multiple communication protocols, including Wi-Fi, Bluetooth, and cellular options, the device ensures seamless integration into existing workflows. This connectivity allows real-time data transmission to central systems, enhancing decision-making capabilities and operational oversight.

Battery life is crucial for a portable device, and the IFS-2600 does not disappoint. It is equipped with a high-capacity battery that supports prolonged usage without frequent recharging. This makes the device perfect for long shifts, ensuring that employees can continue working without interruptions.

In summary, the Honeywell IFS-2600 is a formidable solution for businesses aiming to improve their operational efficiency through advanced data collection. With its robust scanning technology, rugged design, user-friendly interface, versatile connectivity options, and long-lasting battery life, it equips organizations with the tools necessary to thrive in an increasingly competitive market. This makes it an invaluable asset for industries such as logistics, manufacturing, and retail.