Honeywell IFS-2600 installation manual Installation Precautions

Page 3

Installation Precautions

Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.

Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.

Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.

Do not over tighten screw terminals. Over tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.

This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.

Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.

This equipment must be correctly programmed and installed to suit the specific application. Please ensure correct operational parameters are set prior to commissioning. If further details on programming options are required, please consult the programming manual or contact our helpful technical support personnel.

EMC WARNING:

This equipment may radiate radio frequency energy. It may also be affected by radio frequency energy and, if

not installed and operated in accordance with the manufacturers instructions, may cause interference to radio

communications. It has been tested and found to comply with the Class A radiated and conducted EMI

requirements of AS/NZ 3548:1995 (including Amendments 1 & 2) as well as the EMI susceptibility

requirements of Clause C3.5 in AS4428.0:1997.

Radio communication devices should not be used in the vicinity of fire panels or associated ancillary devices

and systems.

Image 3
Contents IFS-2600 Page Installation Precautions Documentation Feedback Table of Contents Placing Into Operation Instructions to OperatorsProgramming Appendix D Appendix aAppendix B Appendix CAppendix Appendix FAppendix G Appendix HCompatible Detectors Overview VDC SpecificationApprovals Environmental LimitsAdditional relay outputs Internal 5VDC 2A Power Supply Power Supply Ratings and SettingsInternal 24 VDC nom 3.0A Main Power Supply Internal 27.3V DC 1.5A Battery ChargerExternal 27VDC Power Supply Battery Type and CapacitiesCurrent Consumption Technical DescriptionGeneral Transient SuppressionOverload Protection Zone Overload Self ResetAZF Description AZF Supervisory CurrentDB9 Female DB25 Male DB9 Male Printer OutputCable Connection Programming by ComputerPCB2005 Termination Board Alignment and AdjustmentPCB2006 Power Supply Board NON Adjustable Test PointsFault Threshold Comparator TP6 Alarm Threshold Comparator TP7Configuration Jumpers Initial Checklist Placing Into OperationEquipment AS Fitted Functional Testing Power UP ChecklistFault Record Fault Correction DateTests Satisfactorily Completed Instructions to Operators IndicatorsAcknowledge ACK Suggested Alarm ProcedureReset Operator InstructionsWarn SYS Isolate Battery Test Batt TestAuto Test Mode Bell Isolate EXT BellWalk Test Mode ACF ResetACF Isolate Zone Functions Alarm Test ENTFault Test Enter Isolate Enter Reset EnterProgramming Global OptionsZone Options Output Relay Options Program Mode Previous →Select → Print Main MenuRelays GlobalZone Selected Exit Programming ModeZone Programming Select Zone #Relay Selected Relay Programming ModeZone Output Configuration Select Relay #Relay #ALL Type General Global ProgrammingRelay Type Relay MappingACF Output AVFRelay Global Relay Unity MAP Time Date & Time Print Programming DataNON Latching Type Description of Alarm Zone TypesAppendix a Latching TypeTime Delay AZF Appendix B Zone Output ConfigurationsGlobal Programmable Options Alarm Verification Facility AVFAVF Timeout Appendix CNON-LATCHING ND Latching ND NON-LATCHING NE Latchingne Appendix DAncillary Trip ACF Ancillary Trip ACFMapping Fault MappingAppendix E Relay Output MappingIsolate Mapping FAULT/ISOLATE MappingGlossary of Terms Appendix FSummary of Terminations and Cautions Appendix GBattery Door Holder AC InputOutput Relays IFS-2600 Programmed Options Appendix HZone Type Programming 48IFS-2600Installation & Programming Manual Zone Output Programming Indicate IBG Ibga Bell General ACF BR1 BR2 BR1&BR2 Relay Output Mapping Mapping RLY ISO ACF BR1 BR2 FLT Mains GEN Bell Appendix Technical DrawingsMain Keypad and Display Expansion Display 12V Battery Block Connection DiagramSystem Sensor Conventional Detector Connection Diagram DET a DET B DET C Hochiki Conventional Detector Connection DiagramDET a DET B DET C RIPStrobe Used Ancillary Connection DiagramASE Connection Diagram TerminationASE Bracket Changeover from Alert to Evac Auto Changeover Dual Sounder Connection DiagramManual Changeover Auto Change Over Dual Sounder Connection DiagramMIM/EXT/26 Mimic Connection DiagramZones Fitted with IFS2600 Mimic DriverSingle Fan Connection Diagram FAN Termination Board AUX PowerFront Panel Control FAN Dual Fan Connection DiagramStops the FAN From FIP Exhaust Fan Connection DiagramFAN Termination Board Supply Fan Connection DiagramFrom FIP Front Panel Control Smoke Spill Fan Connection DiagramSound 10W Evac Connection DiagramFrom Slave 10W Evac Slave Connection DiagramAC2 30W Evac Connection DiagramAcinput 30W Evac Slave Connection Diagram50W Evac Connection Diagram 50W EvacPCB FAN 50W Evac 50W Evac Slave Connection DiagramPage Page Page New South Wales Queensland Victoria Head Office

IFS-2600 specifications

The Honeywell IFS-2600 is a cutting-edge portable data collection device that has gained recognition for its robustness and efficiency in various industrial settings. Designed to enhance productivity in rugged environments, the IFS-2600 is a powerful tool for data acquisition and operational optimization.

One of the key features of the Honeywell IFS-2600 is its advanced scanning technology. It is equipped with a superior imaging engine that provides high-speed scanning capabilities. This makes it ideal for scanning barcodes, even in challenging conditions. The ability to read both 1D and 2D barcodes ensures versatility in applications ranging from inventory management to shipping and receiving.

Another significant characteristic of the IFS-2600 is its rugged design. Built to withstand harsh conditions, this device is compliant with military-grade specifications and offers an impressive drop resistance. It is capable of enduring extreme temperatures, humidity, and dust, making it suitable for use in warehouses, manufacturing plants, and outdoor environments.

The IFS-2600 also boasts a user-friendly interface. Featuring a high-resolution display with touchscreen capabilities, users can easily navigate through applications and access necessary data. The device is designed for efficiency, allowing users to efficiently input information and manage tasks.

Connectivity is another prominent aspect of the Honeywell IFS-2600. With support for multiple communication protocols, including Wi-Fi, Bluetooth, and cellular options, the device ensures seamless integration into existing workflows. This connectivity allows real-time data transmission to central systems, enhancing decision-making capabilities and operational oversight.

Battery life is crucial for a portable device, and the IFS-2600 does not disappoint. It is equipped with a high-capacity battery that supports prolonged usage without frequent recharging. This makes the device perfect for long shifts, ensuring that employees can continue working without interruptions.

In summary, the Honeywell IFS-2600 is a formidable solution for businesses aiming to improve their operational efficiency through advanced data collection. With its robust scanning technology, rugged design, user-friendly interface, versatile connectivity options, and long-lasting battery life, it equips organizations with the tools necessary to thrive in an increasingly competitive market. This makes it an invaluable asset for industries such as logistics, manufacturing, and retail.