Honeywell IFS-2600 Mimic Connection Diagram, Zones, Fitted with IFS2600 Mimic Driver, MIM/EXT/26

Page 65

IFS-2600Installation & Programming Manual

Page 61

MIMIC Connection Diagram

A

B

C

D

 

1

 

 

 

2

 

 

 

3

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

PCB812

PCB812

 

 

 

 

PCB812

 

 

 

 

 

 

 

 

 

ZONES 1-8

 

ZONES 9-16

 

 

 

 

ZONES 17-24

 

IFS2600

 

 

 

 

PCB810

 

 

 

 

 

 

 

 

 

 

 

TERMINATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOARD

 

 

 

 

FITTED WITH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IFS2600 MIMIC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRIVER

 

 

 

 

 

 

 

 

 

 

 

 

N/O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARN

+24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BELL

+24

 

 

 

33-40

 

 

 

1-8

 

 

 

 

 

 

 

0V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41-48

 

 

 

9-16

 

 

 

 

 

 

 

 

+24

 

 

 

 

 

 

 

 

 

 

 

 

 

ACF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0V

 

 

 

49-56

 

 

 

17-24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX

+24

 

 

 

57-64

+24

CLK

DATA

25-32

 

 

 

 

 

 

 

0V

 

 

 

0V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TP 0V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAF ISO

 

 

 

Max 120 Meters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4/0.75mm cable

 

 

 

 

 

 

 

 

 

 

 

 

 

CLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MIMIC

 

POWER AND SIGNAL RETURN

 

 

 

 

 

 

 

 

 

 

 

 

DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOOR HOLD

-

 

 

SERIAL BUS

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

MIM/EXT/26

 

 

 

MIM/EXT/26

 

 

 

 

 

 

 

 

 

 

 

 

DOOR HOLD INPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MIM/26/KIT

 

 

 

 

 

FOR EXTRA ZONES

 

 

 

 

 

 

 

 

FOR 8 ZONES

 

 

 

 

STANDARD SIZES 8, 24 AND 64 ZONES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PCB811

 

 

 

 

 

 

 

 

 

 

 

 

Copyright

 

 

 

 

7 Columbia Court,

Sheet: 1 Of: 1

 

Title

 

 

 

 

 

 

 

This document is & shall

OC

 

 

 

Norwest Business Park

G.W.

 

MIM/26/KIT

 

 

 

 

 

Notifier Inertia Fire Systems

 

 

 

 

Traced 2/2/04

Design

 

 

 

 

 

 

remain the property of

 

 

 

 

Baulkham Hills NSW 2153

Drawn/

Engineer

 

 

 

 

 

 

 

 

 

Unauthorised use of this

 

 

 

 

AUSTRALIA

 

 

 

 

 

 

 

 

 

 

 

document in any way is

Drawing File No.

 

 

 

Tel 61 2 9894 1444

Approved

 

 

Size

Drg.

26-MIM-CON

Rev

No. Revision - revise on CAD. Do not amend by hand

Eng.

App.

prohibited.

 

 

 

Fax 61 2 9899 4156

This Drawing must not be used for Construction

Date =DocumentFullPathAndName

 

 

 

Email: support@inertia.com.au unless signed as approved

 

A4

No.

 

A

 

1

 

 

 

2

 

 

 

3

 

 

 

 

 

4

 

A

B

C

D

P/N 10069 ECN08-0066

Image 65
Contents IFS-2600 Page Installation Precautions Documentation Feedback Table of Contents Programming Placing Into OperationInstructions to Operators Appendix B Appendix aAppendix C Appendix DAppendix G Appendix FAppendix H AppendixCompatible Detectors Overview Approvals SpecificationEnvironmental Limits VDCAdditional relay outputs Internal 24 VDC nom 3.0A Main Power Supply Power Supply Ratings and SettingsInternal 27.3V DC 1.5A Battery Charger Internal 5VDC 2A Power SupplyExternal 27VDC Power Supply Battery Type and CapacitiesGeneral Technical DescriptionTransient Suppression Current ConsumptionAZF Description Zone Overload Self ResetAZF Supervisory Current Overload ProtectionCable Connection Printer OutputProgramming by Computer DB9 Female DB25 Male DB9 MalePCB2006 Power Supply Board Alignment and AdjustmentNON Adjustable Test Points PCB2005 Termination BoardFault Threshold Comparator TP6 Alarm Threshold Comparator TP7Configuration Jumpers Equipment AS Fitted Initial ChecklistPlacing Into Operation Functional Testing Power UP ChecklistTests Satisfactorily Completed Fault RecordFault Correction Date Instructions to Operators IndicatorsReset Suggested Alarm ProcedureOperator Instructions Acknowledge ACKAuto Test Mode Battery Test Batt TestBell Isolate EXT Bell Warn SYS IsolateACF Isolate Walk Test ModeACF Reset Zone Functions Alarm Test ENTFault Test Enter Isolate Enter Reset EnterZone Options ProgrammingGlobal Options Output Relay Options Select → Program ModePrevious → Relays Main MenuGlobal PrintZone Programming Exit Programming ModeSelect Zone # Zone SelectedZone Output Configuration Relay Programming ModeSelect Relay # Relay SelectedRelay Type Global ProgrammingRelay Mapping Relay #ALL Type GeneralRelay Global Relay Unity MAP ACF OutputAVF Time Date & Time Print Programming DataAppendix a Description of Alarm Zone TypesLatching Type NON Latching TypeTime Delay AZF Appendix B Zone Output ConfigurationsAVF Timeout Alarm Verification Facility AVFAppendix C Global Programmable OptionsAncillary Trip ACF Appendix DAncillary Trip ACF NON-LATCHING ND Latching ND NON-LATCHING NE LatchingneAppendix E Fault MappingRelay Output Mapping MappingIsolate Mapping FAULT/ISOLATE MappingGlossary of Terms Appendix FSummary of Terminations and Cautions Appendix GOutput Relays BatteryDoor Holder AC Input IFS-2600 Programmed Options Appendix HZone Type Programming 48IFS-2600Installation & Programming Manual Zone Output Programming Indicate IBG Ibga Bell General ACF BR1 BR2 BR1&BR2 Relay Output Mapping Mapping RLY ISO ACF BR1 BR2 FLT Mains GEN Bell Main Keypad and Display Expansion Display AppendixTechnical Drawings 12V Battery Block Connection DiagramSystem Sensor Conventional Detector Connection Diagram DET a Hochiki Conventional Detector Connection DiagramDET B DET C RIP DET a DET B DET CStrobe Used Ancillary Connection DiagramASE Bracket ASE Connection DiagramTermination Changeover from Alert to Evac Auto Changeover Dual Sounder Connection DiagramManual Changeover Auto Change Over Dual Sounder Connection DiagramZones Mimic Connection DiagramFitted with IFS2600 Mimic Driver MIM/EXT/26Front Panel Control Single Fan Connection DiagramFAN Termination Board AUX Power FAN Dual Fan Connection DiagramStops the FAN From FIP Exhaust Fan Connection DiagramFAN Termination Board Supply Fan Connection DiagramFrom FIP Front Panel Control Smoke Spill Fan Connection DiagramSound 10W Evac Connection DiagramFrom Slave 10W Evac Slave Connection DiagramAC2 30W Evac Connection DiagramAcinput 30W Evac Slave Connection DiagramPCB 50W Evac Connection Diagram50W Evac FAN 50W Evac 50W Evac Slave Connection DiagramPage Page Page New South Wales Queensland Victoria Head Office

IFS-2600 specifications

The Honeywell IFS-2600 is a cutting-edge portable data collection device that has gained recognition for its robustness and efficiency in various industrial settings. Designed to enhance productivity in rugged environments, the IFS-2600 is a powerful tool for data acquisition and operational optimization.

One of the key features of the Honeywell IFS-2600 is its advanced scanning technology. It is equipped with a superior imaging engine that provides high-speed scanning capabilities. This makes it ideal for scanning barcodes, even in challenging conditions. The ability to read both 1D and 2D barcodes ensures versatility in applications ranging from inventory management to shipping and receiving.

Another significant characteristic of the IFS-2600 is its rugged design. Built to withstand harsh conditions, this device is compliant with military-grade specifications and offers an impressive drop resistance. It is capable of enduring extreme temperatures, humidity, and dust, making it suitable for use in warehouses, manufacturing plants, and outdoor environments.

The IFS-2600 also boasts a user-friendly interface. Featuring a high-resolution display with touchscreen capabilities, users can easily navigate through applications and access necessary data. The device is designed for efficiency, allowing users to efficiently input information and manage tasks.

Connectivity is another prominent aspect of the Honeywell IFS-2600. With support for multiple communication protocols, including Wi-Fi, Bluetooth, and cellular options, the device ensures seamless integration into existing workflows. This connectivity allows real-time data transmission to central systems, enhancing decision-making capabilities and operational oversight.

Battery life is crucial for a portable device, and the IFS-2600 does not disappoint. It is equipped with a high-capacity battery that supports prolonged usage without frequent recharging. This makes the device perfect for long shifts, ensuring that employees can continue working without interruptions.

In summary, the Honeywell IFS-2600 is a formidable solution for businesses aiming to improve their operational efficiency through advanced data collection. With its robust scanning technology, rugged design, user-friendly interface, versatile connectivity options, and long-lasting battery life, it equips organizations with the tools necessary to thrive in an increasingly competitive market. This makes it an invaluable asset for industries such as logistics, manufacturing, and retail.