Honeywell IFS-2600 installation manual 10W Evac Slave Connection Diagram, From Slave

Page 72

Page 68

IFS-2600Installation & Programming Manual

10W EVAC Slave Connection Diagram

1

2

3

4

A

B

C

IFS2600

TERMINATION

BOARD

AC INPUT

REMOTE

OUTPUT

REMOTE

INPUT

 

BATT

 

 

 

 

 

 

 

 

+24V

0V

+24V

0V

+24V

0V

 

 

 

 

 

 

 

EXTERNAL POWER JP1 MONITOR AUXWARN

+24

0V

+24

0V

LINK JP1

FRONT

PANEL

EVAC CONTROL

VOL

10W EVAC

 

PCB 908

 

 

 

 

 

 

 

 

 

 

 

PA

 

 

 

 

+24V COM

FAULT ALERT OUT EVAC OUT ALARM

BGM EN

EVAC IN

ALERT IN

PTT

0V

PA+

PA -

BGM + BGM -

JP1 JP2

SOUND

+24 GND

COM

LINE +

 

 

4K7 5%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPEAKERS WITH

EOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

47K 5%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100V LINE TRANSFORMERS

 

CONNECT TO

 

 

 

 

 

 

 

 

 

 

 

 

AND ISOLATION CAPACITORS

 

FAULT OUT

 

 

 

 

 

 

 

 

 

 

WHITE

 

 

 

 

FROM SLAVE

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK/SHIELD

MICROPHONE

 

 

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

 

 

 

 

 

 

SHIELDED

 

 

WITH PTT

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO SLAVE TWO AMPLIFIERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TOGETHER, REMOVE THE IFS903

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOARD FROM THE SLAVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AMPLIFIER AND CONNECT JP1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON THE MASTER TO JP2 ON THE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLAVE.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THE MICROPHONE AND BGM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUST ONLY BE CONNECTED TO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THE MASTER AMPLIFIER.

 

 

BGM ENABLE

 

 

 

 

 

 

 

 

 

 

 

 

CONNECT FAULT OUTPUTS

 

 

( ENABLED ON

 

 

 

 

 

 

 

 

SHIELDED

 

 

TOGETHER AND MOVE THE

 

 

CLOSURE )

 

 

 

 

 

 

 

 

 

 

 

 

LAST WRE ON I/O PCB TO THE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT TERMINAL ON THE

 

 

 

 

 

 

 

 

 

BGM INPUT

 

 

 

MASTER AMPLIFIER.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1V P-P

 

 

 

 

CONNECT PIN 4, P12 ON MASTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO PIN4 P12 ON SLAVE.

 

A

B

C

D

 

 

 

 

 

Copyright

 

 

 

7 Columbia Court,

Sheet:

1 Of: 1

 

 

 

Title

IFS-2600

 

 

 

 

 

 

 

This document is & shall

 

 

 

Norwest Business Park

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remain the property of

 

 

 

Baulkham Hills NSW 2153

Drawn/

I PERRY

Engineer

I PERRY

 

10 WATT SLAVE

 

 

 

 

 

 

Notifier Inertia Fire Systems

C

 

 

Traced

Design

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unauthorised use of this

O

 

 

AUSTRALIA

 

 

 

 

 

 

CONNECTION DIAGRAM

 

 

 

 

 

 

 

I PERRY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

document in any way is

Drawing File No.

 

 

Tel 61 2 9894 1444

Approved

 

Size

 

Drg.

 

Rev

 

 

 

 

 

prohibited.

 

 

Fax 61 2 9899 4156

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A4

2600-10W SLAVE

 

 

 

 

 

 

 

 

 

 

 

This Drawing must not be used for Construction

No.

A

No.

Revision - revise on CAD. Do not amend by hand

Eng.

App.

Date

=DocumentFullPathAndName

 

 

Email: support@inertia.com.au

unless signed as approved

 

1

 

 

 

 

2

 

3

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

P/N 10069 ECN08-0066

Image 72
Contents IFS-2600 Page Installation Precautions Documentation Feedback Table of Contents Placing Into Operation Instructions to OperatorsProgramming Appendix a Appendix BAppendix C Appendix DAppendix F Appendix GAppendix H AppendixCompatible Detectors Overview Specification ApprovalsEnvironmental Limits VDCAdditional relay outputs Power Supply Ratings and Settings Internal 24 VDC nom 3.0A Main Power SupplyInternal 27.3V DC 1.5A Battery Charger Internal 5VDC 2A Power SupplyBattery Type and Capacities External 27VDC Power SupplyTechnical Description GeneralTransient Suppression Current ConsumptionZone Overload Self Reset AZF DescriptionAZF Supervisory Current Overload ProtectionPrinter Output Cable ConnectionProgramming by Computer DB9 Female DB25 Male DB9 MaleAlignment and Adjustment PCB2006 Power Supply BoardNON Adjustable Test Points PCB2005 Termination BoardAlarm Threshold Comparator TP7 Fault Threshold Comparator TP6Configuration Jumpers Initial Checklist Placing Into OperationEquipment AS Fitted Power UP Checklist Functional TestingFault Record Fault Correction DateTests Satisfactorily Completed Indicators Instructions to OperatorsSuggested Alarm Procedure ResetOperator Instructions Acknowledge ACKBattery Test Batt Test Auto Test ModeBell Isolate EXT Bell Warn SYS IsolateWalk Test Mode ACF ResetACF Isolate Alarm Test ENT Zone FunctionsFault Test Enter Reset Enter Isolate EnterProgramming Global OptionsZone Options Output Relay Options Program Mode Previous →Select → Main Menu RelaysGlobal PrintExit Programming Mode Zone ProgrammingSelect Zone # Zone SelectedRelay Programming Mode Zone Output ConfigurationSelect Relay # Relay SelectedGlobal Programming Relay TypeRelay Mapping Relay #ALL Type GeneralACF Output AVFRelay Global Relay Unity MAP Print Programming Data Time Date & TimeDescription of Alarm Zone Types Appendix aLatching Type NON Latching TypeTime Delay AZF Zone Output Configurations Appendix BAlarm Verification Facility AVF AVF TimeoutAppendix C Global Programmable OptionsAppendix D Ancillary Trip ACFAncillary Trip ACF NON-LATCHING ND Latching ND NON-LATCHING NE LatchingneFault Mapping Appendix ERelay Output Mapping MappingFAULT/ISOLATE Mapping Isolate MappingAppendix F Glossary of TermsAppendix G Summary of Terminations and CautionsBattery Door Holder AC InputOutput Relays Appendix H IFS-2600 Programmed OptionsZone Type Programming 48IFS-2600Installation & Programming Manual Zone Output Programming Indicate IBG Ibga Bell General ACF BR1 BR2 BR1&BR2 Relay Output Mapping Mapping RLY ISO ACF BR1 BR2 FLT Mains GEN Bell Appendix Technical DrawingsMain Keypad and Display Expansion Display Block Connection Diagram 12V BatterySystem Sensor Conventional Detector Connection Diagram Hochiki Conventional Detector Connection Diagram DET aDET B DET C RIP DET a DET B DET CAncillary Connection Diagram Strobe UsedASE Connection Diagram TerminationASE Bracket Auto Changeover Dual Sounder Connection Diagram Changeover from Alert to EvacAuto Change Over Dual Sounder Connection Diagram Manual ChangeoverMimic Connection Diagram ZonesFitted with IFS2600 Mimic Driver MIM/EXT/26Single Fan Connection Diagram FAN Termination Board AUX PowerFront Panel Control Dual Fan Connection Diagram FANExhaust Fan Connection Diagram Stops the FAN From FIPSupply Fan Connection Diagram FAN Termination BoardSmoke Spill Fan Connection Diagram From FIP Front Panel Control10W Evac Connection Diagram Sound10W Evac Slave Connection Diagram From Slave30W Evac Connection Diagram AC230W Evac Slave Connection Diagram Acinput50W Evac Connection Diagram 50W EvacPCB 50W Evac Slave Connection Diagram FAN 50W EvacPage Page Page New South Wales Queensland Victoria Head Office

IFS-2600 specifications

The Honeywell IFS-2600 is a cutting-edge portable data collection device that has gained recognition for its robustness and efficiency in various industrial settings. Designed to enhance productivity in rugged environments, the IFS-2600 is a powerful tool for data acquisition and operational optimization.

One of the key features of the Honeywell IFS-2600 is its advanced scanning technology. It is equipped with a superior imaging engine that provides high-speed scanning capabilities. This makes it ideal for scanning barcodes, even in challenging conditions. The ability to read both 1D and 2D barcodes ensures versatility in applications ranging from inventory management to shipping and receiving.

Another significant characteristic of the IFS-2600 is its rugged design. Built to withstand harsh conditions, this device is compliant with military-grade specifications and offers an impressive drop resistance. It is capable of enduring extreme temperatures, humidity, and dust, making it suitable for use in warehouses, manufacturing plants, and outdoor environments.

The IFS-2600 also boasts a user-friendly interface. Featuring a high-resolution display with touchscreen capabilities, users can easily navigate through applications and access necessary data. The device is designed for efficiency, allowing users to efficiently input information and manage tasks.

Connectivity is another prominent aspect of the Honeywell IFS-2600. With support for multiple communication protocols, including Wi-Fi, Bluetooth, and cellular options, the device ensures seamless integration into existing workflows. This connectivity allows real-time data transmission to central systems, enhancing decision-making capabilities and operational oversight.

Battery life is crucial for a portable device, and the IFS-2600 does not disappoint. It is equipped with a high-capacity battery that supports prolonged usage without frequent recharging. This makes the device perfect for long shifts, ensuring that employees can continue working without interruptions.

In summary, the Honeywell IFS-2600 is a formidable solution for businesses aiming to improve their operational efficiency through advanced data collection. With its robust scanning technology, rugged design, user-friendly interface, versatile connectivity options, and long-lasting battery life, it equips organizations with the tools necessary to thrive in an increasingly competitive market. This makes it an invaluable asset for industries such as logistics, manufacturing, and retail.