IFS-2600Installation & Programming Manual

ACF OUTPUT

ACF OUTPUT

(NON-LATCH ND)

Use the "NEXT" & "PREVIOUS" keys to scroll through:

LATCHING ND

NON-LATCH NE

LATCHING NE

Note: The option previously set is displayed in brackets and is the first to be displayed.

ND = Normally De-energised i.e.: Output is not energised until an alarm occurs.

NE = Normally energised i.e.: Output is energised and then is de-energised once an alarm occurs.

AVF

AVF TIMEOUT

(3 MINUTES)

Use the "NEXT" & "PREVIOUS" keys to scroll through:

DISABLED

2MINUTES

3MINUTES

4MINUTES

5MINUTES

Note: The option previously set is displayed in brackets and is the first to be displayed.

RELAY (GLOBAL RELAY UNITY MAP)

MAP RELAY (XX) >>

FROM ZONE (XX)

Use the "NEXT" & "PREVIOUS" keys to change the first relay to start from, together with the matching zone. Use the “ENTER” key to toggle between the two and press “SELECT” once finalised. “Exit” will abort unity map.

This function will start programming relays starting from the relay number specified in a 1 to 1 configuration with zones starting from the first zone number specified.

Example 1: if the above table was to look like this:

MAP RELAY (10) >>

FROM ZONE (01)

Then relay #10 would be set as MAP OR with its mapping as (01) 00 00 00 00, relay #11 would be set as MAP OR with it’s mapping set as (02) 00 00 00 00 and so on all the way up to relay #64. Relays number 1-through 9 remains unaffected by this function.

Example 2: if the above table was to look like this:

MAP RELAY (01) >>

FROM ZONE (09)

P/N 10069 ECN08-0066

Image 38
Contents IFS-2600 Page Installation Precautions Documentation Feedback Table of Contents Programming Placing Into OperationInstructions to Operators Appendix C Appendix aAppendix B Appendix DAppendix H Appendix FAppendix G AppendixCompatible Detectors Overview Environmental Limits SpecificationApprovals VDCAdditional relay outputs Internal 27.3V DC 1.5A Battery Charger Power Supply Ratings and SettingsInternal 24 VDC nom 3.0A Main Power Supply Internal 5VDC 2A Power SupplyBattery Type and Capacities External 27VDC Power SupplyTransient Suppression Technical DescriptionGeneral Current ConsumptionAZF Supervisory Current Zone Overload Self ResetAZF Description Overload ProtectionProgramming by Computer Printer OutputCable Connection DB9 Female DB25 Male DB9 MaleNON Adjustable Test Points Alignment and AdjustmentPCB2006 Power Supply Board PCB2005 Termination BoardAlarm Threshold Comparator TP7 Fault Threshold Comparator TP6Configuration Jumpers Equipment AS Fitted Initial ChecklistPlacing Into Operation Power UP Checklist Functional TestingTests Satisfactorily Completed Fault RecordFault Correction Date Indicators Instructions to OperatorsOperator Instructions Suggested Alarm ProcedureReset Acknowledge ACKBell Isolate EXT Bell Battery Test Batt TestAuto Test Mode Warn SYS IsolateACF Isolate Walk Test ModeACF Reset Alarm Test ENT Zone FunctionsFault Test Enter Reset Enter Isolate EnterZone Options ProgrammingGlobal Options Output Relay Options Select → Program ModePrevious → Global Main MenuRelays PrintSelect Zone # Exit Programming ModeZone Programming Zone SelectedSelect Relay # Relay Programming ModeZone Output Configuration Relay SelectedRelay Mapping Global ProgrammingRelay Type Relay #ALL Type GeneralRelay Global Relay Unity MAP ACF OutputAVF Print Programming Data Time Date & TimeLatching Type Description of Alarm Zone TypesAppendix a NON Latching TypeTime Delay AZF Zone Output Configurations Appendix BAppendix C Alarm Verification Facility AVFAVF Timeout Global Programmable OptionsAncillary Trip ACF Appendix DAncillary Trip ACF NON-LATCHING ND Latching ND NON-LATCHING NE LatchingneRelay Output Mapping Fault MappingAppendix E MappingFAULT/ISOLATE Mapping Isolate MappingAppendix F Glossary of TermsAppendix G Summary of Terminations and CautionsOutput Relays BatteryDoor Holder AC Input Appendix H IFS-2600 Programmed OptionsZone Type Programming 48IFS-2600Installation & Programming Manual Zone Output Programming Indicate IBG Ibga Bell General ACF BR1 BR2 BR1&BR2 Relay Output Mapping Mapping RLY ISO ACF BR1 BR2 FLT Mains GEN Bell Main Keypad and Display Expansion Display AppendixTechnical Drawings Block Connection Diagram 12V BatterySystem Sensor Conventional Detector Connection Diagram DET B DET C RIP Hochiki Conventional Detector Connection DiagramDET a DET a DET B DET CAncillary Connection Diagram Strobe UsedASE Bracket ASE Connection DiagramTermination Auto Changeover Dual Sounder Connection Diagram Changeover from Alert to EvacAuto Change Over Dual Sounder Connection Diagram Manual ChangeoverFitted with IFS2600 Mimic Driver Mimic Connection DiagramZones MIM/EXT/26Front Panel Control Single Fan Connection DiagramFAN Termination Board AUX Power Dual Fan Connection Diagram FANExhaust Fan Connection Diagram Stops the FAN From FIPSupply Fan Connection Diagram FAN Termination BoardSmoke Spill Fan Connection Diagram From FIP Front Panel Control10W Evac Connection Diagram Sound10W Evac Slave Connection Diagram From Slave30W Evac Connection Diagram AC230W Evac Slave Connection Diagram AcinputPCB 50W Evac Connection Diagram50W Evac 50W Evac Slave Connection Diagram FAN 50W EvacPage Page Page New South Wales Queensland Victoria Head Office

IFS-2600 specifications

The Honeywell IFS-2600 is a cutting-edge portable data collection device that has gained recognition for its robustness and efficiency in various industrial settings. Designed to enhance productivity in rugged environments, the IFS-2600 is a powerful tool for data acquisition and operational optimization.

One of the key features of the Honeywell IFS-2600 is its advanced scanning technology. It is equipped with a superior imaging engine that provides high-speed scanning capabilities. This makes it ideal for scanning barcodes, even in challenging conditions. The ability to read both 1D and 2D barcodes ensures versatility in applications ranging from inventory management to shipping and receiving.

Another significant characteristic of the IFS-2600 is its rugged design. Built to withstand harsh conditions, this device is compliant with military-grade specifications and offers an impressive drop resistance. It is capable of enduring extreme temperatures, humidity, and dust, making it suitable for use in warehouses, manufacturing plants, and outdoor environments.

The IFS-2600 also boasts a user-friendly interface. Featuring a high-resolution display with touchscreen capabilities, users can easily navigate through applications and access necessary data. The device is designed for efficiency, allowing users to efficiently input information and manage tasks.

Connectivity is another prominent aspect of the Honeywell IFS-2600. With support for multiple communication protocols, including Wi-Fi, Bluetooth, and cellular options, the device ensures seamless integration into existing workflows. This connectivity allows real-time data transmission to central systems, enhancing decision-making capabilities and operational oversight.

Battery life is crucial for a portable device, and the IFS-2600 does not disappoint. It is equipped with a high-capacity battery that supports prolonged usage without frequent recharging. This makes the device perfect for long shifts, ensuring that employees can continue working without interruptions.

In summary, the Honeywell IFS-2600 is a formidable solution for businesses aiming to improve their operational efficiency through advanced data collection. With its robust scanning technology, rugged design, user-friendly interface, versatile connectivity options, and long-lasting battery life, it equips organizations with the tools necessary to thrive in an increasingly competitive market. This makes it an invaluable asset for industries such as logistics, manufacturing, and retail.