Bacharach AGM300, ADM800 Tubing Considerations, Connecting Purge Line, Connecting Exhaust Line

Page 13

Tubing Considerations

Use ¼" outside diameter (0.040" wall) flex tubing is used for all air lines (P/N 304-2742). The tubing should be clean and free of residual moisture or other contaminants. The tubing should be cut cleanly with a sharp knife and care should be taken not to distort the tubing end.

IMPORTANT: Due to the reactive nature of ammonia gas, it is important to use materials that will not absorb ammonia gas as it passes though the sampling system. The use of unauthorized tubing or any other materials in the gas sampling stream may lead to erroneously low readings.

To connect the air lines to the monitor simply push the tubing firmly onto the connector. All tubing bends should have a radius of no less than 5" to assure proper airflow. If kinks or obstructions occur in any of the air lines the instrument may not function properly.

Connecting Purge Line

A purge line is required to draw fresh air into the instrument and should not exceed 300 feet in length. It is advisable to terminate the line outdoors, provided the input is not exposed to rain, snow, ice, exhaust fumes, or other airborne contaminates. If an outdoor installation is impractical, the line should be run to an area inside the facility that you are certain is not contaminated with ambient ammonia gas. A line-end filter (P/N 3015-3420) should be attached to the end of the purge line.

Connecting Exhaust Line

An exhaust line is required to vent gas samples away from the instrument and should not exceed 300 feet in length. The exhaust line should terminate in a location that is completely isolated from the purge line termination point and other areas of the facility that will be monitored. Ideally this line should terminate outdoors in a location that is not exposed to the elements. This line does not require a line-end filter. If the exhaust line terminates outside the building, position the tubing so that no water or moisture can enter it.

Connecting Sample Intake Lines

The AGM300 is designed to accommodate up to 16 separate sample intake lines. The standard configuration of the unit includes one manifold of 4 intake connectors and 1 purge connector. Additional manifolds can be easily installed to increase monitoring capacity (field installation kit part P/N 3015-3419, and 4 zone line end filter kit P/N 3015-3411).

Sample intake lines can be up to 500 feet in length. All line terminations should be positioned to reduce the possibility of mists, aerosols, oil, water, dust, or other contaminates being drawn into the instrument. A line-end filter (P/N 3015-3420) should be attached to the end of each sample intake line.

IMPORTANT: DO NOT plug any of the zones. Plugging a zone will give the monitor a false indication during start up.

Please refer to the earlier Section Suggested Location of Sampling Points to learn more about where to place the ends of the sample intake lines.

Water Trap

A water trap has been installed as a standard feature. The water trap prevents condensation or moisture from entering the infrared device and causing serious damage. To empty the water trap, loosen the wing nut and allow water to drain – be sure to retighten the wing nut.

CAUTION - The introduction of contaminants through the air intake lines can result in serious and permanent damage to the monitor.

Instruction 3015-4275

5

Image 13
Contents Rev May AGM300 / ADM800 Ammonia Gas Monitoring SystemInstruction Table of Contents Introduction How to Use This ManualPlease Read this Manual Carefully Before Use Safety Precautions Installation Category Hazard Symbols on MonitorCleaning Altitude LimitGeneral Description Functional OverviewCommunication Options Suggested Location of Sampling PointsMachine Room ChillerLED Standard Accessories for a 4 Point SystemLocating the Monitor AGM300 Installation ConsiderationsInspection AGM300 Mounting Instructions InstallationScrew Locations AGM300 Mounting SpecsOverview AGM300 Connecting Air LinesAGM300 Side View Inlet / Purge PortsConnecting Exhaust Line Connecting Purge LineConnecting Sample Intake Lines Tubing ConsiderationsAGM300 Interior Schematic Switches / Fuses Do not Apply PowerON/OFF / OUTVAC Installation AGM300 Electrical WiringAGM300 AC Input Power and Ground Connections RS-485 Connector AGM300 Connecting Communication DevicesAmmonia Display Module ADM800 Connection Integrating with Building Management SystemsPersonal Computer Refer to AGM300 PC Software Section Changing Terminator SettingsOUT Multiple AGM’s Connecting to a Building Management SystemRS-485 Connections Between AGM300’s AGM300 PC Software Programming the AGM300 Using PC SoftwareMultiple AGM300’s Connected to a Building Management System Unit Node Terminator Outout Building Management SystemTo Open a Saved Program Saving the AGM300 Program to a Disk or DriveTo Send a Saved Program to an AGM300 Trend DataSealevel SYSTEMS, INC USB Type LaptopsAGM300 Current Loop Interfaces Current Loop ConnectorOptional 4-20 mAdc Outputs ConnectionAGM300 Relay Connector AGM300 Connecting External AlarmsTypical AGM300 Relay 1 and Relay 2 Wiring Leak Spill Evacuate FaultADM800 Oblique Photo ADM800 InstallationADM800 Installation Considerations ADM800 Mounting Specs ADM800 Mounting InstructionsFront Panel Chassis ADM800 Interior SchematicTo Host To MonitorsADM800 Electrical Wiring ADM800 AC Input Power and Ground Connections AGM300 Network ADM800 Communication ConnectionsIntegration with Building Management System To Monitor Changing Terminator Switch SettingsADM800 Relay Connector ADM800 Connecting External AlarmsADM800 Operation ADM800 Exterior SchematicADM800 Overview System Screen ADM800 Screen DisplaysPassword Protection Setup ParametersADM800 System Programming Setting the Clock ADM800 Setup ProgrammingClock Setup Screen Contrast Navigating to the 1st ADM Setup ScreenNumber of AGM Units AGM Baud RatePassword Audible AlarmEnabling Building Management System Connection Building Management System Stop BitsSetting Relay Parameters Navigating to the 2nd ADM Setup ScreenADM Setup Screen #2 AGM Node AddressNavigating to the 1st and then 2nd AGM Setup Screen AGM300 Setup ProgrammingScreen #1 AGM Setup Screen #1 AGM Setup Screen #2Alarm Ack Mode Number of Zones InstalledLocation Zone Hold TimeLoop 2 Factor Re-Zero ModeAuto Zone ChangeService Timeout Navigating to the 3rd AGM Setup ScreenAGM Setup #3 Screen Navigating to the 1st Zone Setup Screen ADM800 Zone Setup ProgrammingZone Setup Screen #1 DistanceNavigating To the 2nd Zone Setup Screen Average TemperatureCurrent PPM Log IntervalSpill Level Re-Setting the Peak PPM ValueEvacuation Level Functional Overview General OperationWorking with the Zone Screen Zone ScreenZone Screen Alarm Mode Zone Screen Hold ModeFault Conditions Working with the System Screen System Screen Alarm ModeAlarm Log Screen AGM Setup #1 ScreenSystem Screen Fault Mode Responding To Alarms Working with AlarmsAlarm Summary Screen Alarm Detail Screen Alarm Detail ScreenAlarm Summary Screen Acknowledge Mode Acknowledging AlarmsOverview Log Interval Working with the Trend ScreenNavigating To the Trend Screen Trend ScreenNavigating to the Fault Screen Working with System FaultsFault Screen Critical Faults Reset to Factory Default SettingsViewing Fault Log Clearing System FaultsFault Log Screen Working with the Calibration Screen Adjusting Calibration FactorNavigating to the Calibration Screen Calibration ScreenCalibration Procedure Navigating to the Diagnostic Screen Working with the Diagnostic ScreenDiagnostic Screen Overview Diagnostic ScreenInstruction System Screen Service Mode Service ModeInstruction Appendix Servicing Inline Filter AGM300 / ADM800 MaintenanceServicing Air Lines Replacing FusesIntake Manifolds Optional AccessoriesMA Interface Board ADM800 Logic Diagram Modbus RTU Protocol RS-485 Communication ProtocolProtocol Details AGM300 Modbus RTU OperationKey Comm Protocol Parameters Modbus Mode RTU onlyData Type Abbreviations Summary of RegistersRegister Name Number Type Description TIMUnused TIM REVUnused Minutes RS-485BAUDMode. do not Modify use zone hold register or Service mode register to change this parameterMSB LSBVariable Type Length Description Zone Data Register 0x12xxh R/W 78 bytesGood. do not Modify Instruction Instruction Stpppm To Release the Zone Hold Use the Following Sequence of Steps Fault Log Register Register 0x1900, 0x1901h Bytes Instruction Time record for each of the 100 log points. The format Point to current readingLast 100 log points 2 byes per point Warranty Warranty and ServiceService Products Covered under Warranty and Service Policy Return ProcedureField Repair AGM300 Specifications ADM800 Specifications Instruction Headquarters Hunt Valley Circle, New Kensington, PA

AGM300, ADM800 specifications

The Bacharach ADM 800 and AGM 300 are advanced analyzers designed for efficient monitoring and detection of gases in various applications. Known for their reliability and accuracy, these instruments cater to commercial and industrial sectors, ensuring safety and compliance with environmental regulations.

The Bacharach ADM 800 is a portable gas detection device renowned for its ability to detect multiple refrigerants. With a user-friendly interface, it features a high-resolution display that provides real-time data on refrigerant concentrations, allowing technicians to quickly identify leaks during maintenance operations. One of its standout technologies is a highly sensitive thermal conductivity sensor, which enables the ADM 800 to differentiate between various hydrocarbon refrigerants with precision.

Equipped with data logging capabilities, the ADM 800 can store and retrieve measurement data, making it an invaluable tool for tracking refrigerant trends over time. The device supports USB connectivity for easy transfer of data to computers, facilitating detailed reporting and analysis. Its robust design incorporates a protective casing that ensures durability in challenging work environments, making it ideal for both field use and stationary applications.

On the other hand, the Bacharach AGM 300 is specifically crafted for continuous gas monitoring in HVAC systems. This stationary device excels in measuring concentrations of gases such as CO, CO2, and various refrigerants, ensuring optimal performance and compliance. The AGM 300 uses advanced electrochemical sensors for precise gas measurements, providing real-time feedback and alerting users to any hazardous conditions.

One of the notable features of the AGM 300 is its ability to integrate seamlessly with building management systems, enabling centralized control and monitoring of gas levels across multiple locations. This connectivity enhances the safety of industrial and commercial spaces by allowing for automated responses to detected gas levels, which can significantly mitigate risks associated with gas leaks.

Both models emphasize user-centric design, with intuitive interfaces and clear displays, making them accessible even to those with minimal training. Additionally, their low maintenance requirements and long sensor life contribute to reduced operational costs.

In conclusion, the Bacharach ADM 800 and AGM 300 are exemplary solutions for gas detection and monitoring. Their advanced technologies, robust features, and user-friendly designs make them indispensable for ensuring safety and regulatory compliance in various environments.